P R O D U C T S P E C I F I C AT I O N S
Single Stage Heat/Cool 24 Volt Thermostats
Models 8553 and 8534
(SHC 7) and (DSL 300)
PRODUCT DESCRIPTION
These Aprilaire® thermostats are designed for new or replacement residential or
commercial applications. Each one represents the latest in solid-state, surface-mounted electronics
and manufacturing techniques, incorporated into a unique, ultra-thin ABS plastic case. They offer
“user-friendly” control {and programming with model 8553} of the heating and cooling system along
with an easy-to-read vertical LCD that displays complete equipment operation status. An easily
installed direct wire sub-base mounts on a standard vertical outlet box or any dry wall surface using
provided anchors and hardware.
STANDARD FEATURES
8553
8534
•
Energy Star Compliance
■
•
Meets CA Title 24 Requirements
■
•
Selectable Celsius or Fahrenheit temperature display.
■
■
•
Fan button for continuous fan operation.
■
■
•
Built-in short cycle protection.
■
■
•
Electronic circuitry instead of conventional mechanical anticipator.
■
■
•
Internal keypad lockout switch to prevent unauthorized tampering.
■
■
•
Lockable access cover.
■
■
•
No battery required {always maintains the program and mode
■
■
of operation following power outages of any duration}.
■
•
Day/Night button for one-touch set-back.
•
Outdoor temperature sensor {optional}.
■
■
•
Indoor remote temperature sensor {optional}.
■
■
•
Adapter plate to cover unpainted walls or discolored wallpaper {optional}.
■
■
•
Independent circuit switching {allows 24-volt AC or DC power}.
■
■
•
Remote clock terminals for automatic temperature set-back.
•
Selectable fan with heat call.
■
•
Copy feature to allow one program to be copied to subsequent days.
■
•
Dry contact relay outputs.
■
•
Smart Fan function.
■
•
7 day programming with 2 or 4 events per day {selectable}.
■
•
12- or 24-hour clock.
■
•
Temperature override {3 hours} and Continuous override {Hold}.
■
•
2˚F {1˚C} minimum Heat/Cool separation.
■
■
•
Short cycle protection – minimum on/off time {2- or 4-minute selectable}.
■
■
•
Auto changeover.
■
■
•
1-stage heat; 1-stage cool.
■
■
■
■
■
Product Profile:
Actual Size
WIRING DIAGRAM
Models 8553, 8534
OUTPUT TERMINALS
Aprilaire® ®
PerfectTemp
Thermostat
Thermostat
Models SHC-7 or DSL-300
EQUIPMENT
Y1
1st Stage
Heat
W
1st Stage
Cooling
Y
G
NOTE 1
R
Fan
Relay
G
NOTE 2
RS2
RS1
R
120 V
{hot}
Y1
1st Stage Cool
G
Fan
R
24V hot – used with terminals above to
complete switched circuit.
24V
24V {AC or DC} hot from transformer
{or positive if DC voltage source is used}.
C
CLK1
CLK2
24V{c} 24V {AC or DC} common from transformer
{or negative if DC voltage source is used}.
REMOTE
SENSOR{S}
RS1,
RS2,
RS+v
CLOCK
TERMINALS
CLK1, A completed circuit between these two
CLK2 terminals automatically adjusts the set point
to the night setting in the current mode of
operation {8534 only}.
RS+v
{com}
1st Stage Heat
24V
24V(c)
24 V
EQUIPMENT
W1
W1
FACTORY WIRING
24V FIELD WIRING
These terminals are used to connect Remote
Sensors {i.e. 8040, 8041}.
NOTE 1: Do not remove jumper unless using a transformer different from system
transformer to power the thermostat.
NOTE 2: Thermostat will accept 24V DC. Connect pos. {+} to 24V terminal and
neg. {–} to 24V{c} terminal.
PRODUCT SPECIFICATIONS
Rated Voltage
20 to 30 Volts AC or DC, 24 Volts Nominal
Rated AC Current
.050 Amps to 0.75 Amps continuous per output with surges to 3 Amps maximum
Rated DC Current
0.0 Amps to 0.75 Amps continuous per output with surges to 3 Amps maximum
Control Range
Heating: 38 to 88˚F in 1˚ steps {5 to 30˚C in 1˚ steps}
Cooling: 60 to 108˚F in 1˚ steps {16 to 40˚C in 1˚ steps}
Thermostat Measurement Range
28 to 124˚F {0 to 48˚C}
ODT Measurement Range
–50 to 124˚F {–48 to 48˚C}
Control Accuracy
±1˚F at 68˚ {0.5˚C at 20˚C}
Minimum Deadband
{between heating and cooling set points} 2˚F {1˚C}
Dimensions
41/2"H x 4"W x 7/8"D {114mm x 102mm x 22mm}
Available Equipment Terminals
24 Vac, 24 Vac{c}, W1, Y1, G
Minimum Wires Required
5
NOTE: These thermostats contain electronic circuitry in place of the conventional mechanical anticipator. Specifications are subject to change without notice.
®
P.O. BOX 1467 • MADISON, WI 53701-1467 • Call toll-free 1-800/334-6011 • FAX 608/257-4357 • Products For Better Indoor Air Quality ™
Form #5151 3.1.03
©Research Products Corporation 2003