Download Edco SLAC Series

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground (electricity) wikipedia , lookup

Electrification wikipedia , lookup

Electrical substation wikipedia , lookup

Phone connector (audio) wikipedia , lookup

Electric power system wikipedia , lookup

Dynamic range compression wikipedia , lookup

Stray voltage wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Audio power wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power over Ethernet wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Power engineering wikipedia , lookup

Voltage optimisation wikipedia , lookup

Spectral density wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Islanding wikipedia , lookup

AC adapter wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Surge protector wikipedia , lookup

Transcript
Data/Signal Line Protection
Edco SLAC Series
AC Power/Signal
The Edco SLAC Series suppressor was specifically designed to protect electronic
instruments used by the water/wastewater industries. It combines hybrid AC
power protection and signal line protection in a NEMA-4X polycarbonate case.
The AC power suppressor can supply up to 1875 Watts and has a 15 Amp
replaceable fuse to prevent overloading of the protective elements. A “Power
ON” LED provides visual indication that power is applied to instruments. Signal
line protection is accomplished by the Edco PC642 Series available in a variety
of voltage clamps. Signal current can be monitored by reading the voltage
across the 10 V, 1% resistors (TP1 & TP2 or TP3 & TP4). All leads going to the
Edco SLAC board are terminated by quick disconnect or barrier block
connectors to facilitate easy removal for service or replacement.
Features
■ Optional twist lock plug lightning & surge
suppression for AC power and low-voltage
signal lines
■ Test jacks for signal line monitoring
■ Series hybrid AC suppressor/filter
■ Optional stainless steel or fiberglass
enclosure
■ “Power ON” indicator
■ Plug-in protection module
■ 5 year warranty
■ 15 Amp replaceable fuse
General Technical Specifications
AC Power
Standard Enclosure
Optional Enclosure
Technology
NEMA-4X
NEMA-4X
Glass-Filled Polycarbonate Base
Stainless Steel or Fiberglass
Cover Molded in Clear Polycarbonate
Continuous Hinge
Knockouts for 1/2" and 3/4" hubs
Nominal Outside Dimensions (Inches)
H=10, W=8, D=4
Three-Stage Series Hybrid
Input Voltage
120 VAC 50/60 Hz
Output Current
15 Amps Max.
Response Time
<5 Nanoseconds
Maximum Surge Current (8x20 µs)
10 kA
Occurrences at 500 Amps
Parameter
Normal Mode
(L-N)
>50
Common Mode
(L-G) (N-G)
Bosses for 6 BZ x 3/8" Self-Tapping Screws
Maximum Protection—Total Insulation
Corrosion Resistant
Resists Temperature of 248°F
IEEE 587 CAT A Ring*
172 V
280 V
Flammability Rating UL94-5V
IEEE 587 CAT B Ring*
205 V
280 V
IEEE 587 CAT B Impulse* 330 V
360 V
Nominal Outside dimensions (Inches)
H= 6.89, W=6.89, D=2.95
How to Specify the Appropriate Model
*Measured from zero volts, 90° Phase angle
General Technical Specifications
Signal Line
Technology
Peak Surge Current
Response Time
Voltage Clamp (customer selected)
Series Resistance
Series Hybrid
10 kA
<1 Nanosecond
Ordering Information
These blocks are for PC642
VoltageSelection if applicable. See
PC 642 Datasheet for additional
information. 0 3 6 is standard for
4-20 mA Signal Line.
8–200 Volts
5 V (Typical)
23