Download CA-NLH-106 Island Interconnected System Supply Issues and Power Outages Reference: PUB-NLH-470:

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Decibel wikipedia , lookup

Fault tolerance wikipedia , lookup

Power engineering wikipedia , lookup

Electrical substation wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Variable-frequency drive wikipedia , lookup

History of electric power transmission wikipedia , lookup

Loading coil wikipedia , lookup

Buck converter wikipedia , lookup

Stray voltage wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage optimisation wikipedia , lookup

Power over Ethernet wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
CA-NLH-106
Island Interconnected System Supply Issues and Power Outages
Page 1 of 1
1
Q.
Reference: PUB-NLH-470: The spare 350kV cable will need to be rapidly
2
discharged from one potential and then connected to the opposite polarity pole.
3
This means the spare 350kV cable will be exposed to a polarity reversal over a short
4
period of time. Please confirm that the 350kV cable insulation, factory joints, field
5
joints and station terminations will be designed to withstand the polarity reversal,
6
and will be factory tested with the polarity reversal. Please also provide the
7
amount of years of life that are reduced due to each polarity reversal for the 350kV
8
cable insulation, factory joints, field joints and station terminations.
9
10
11
A.
The Strait of Belle Isle HVdc mass-impregnated cables, joints, and terminations have
12
been successfully type tested in accordance with Electra 189 (CIGRE), to withstand
13
polarity reversals with voltage 1.4 times the rated DC voltage of +/-350 kV, with no
14
impact on the design life of 50 years.
15
16
Polarity reversals are normal operating events for line commuted converter (LCC)
17
systems, as a polarity reversal is required to facilitate a reversal in the direction of
18
power flow.