Download 260519 Wires and Cables (600V or Less)

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Alternating current wikipedia , lookup

Loading coil wikipedia , lookup

Wire wrap wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Electrical connector wikipedia , lookup

National Electrical Code wikipedia , lookup

Electrical wiring wikipedia , lookup

Transcript
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
SECTION 260519
WIRES AND CABLES (600V OR LESS)
INSTRUCTIONS:
NOTE: This Section refers to Section 260533 16110 Raceways. It is necessary to include Section
260533 16110 with the project specifications when this Section is used.
PART 1 GENERAL
1.01
SUMMARY
A. Section Includes: Cables and wires rated 600 volts or less, as specified, including wiring of all
devices.
1.02
SUBMITTALS
A. Shop Drawings: The location of such items as fire alarm horns, manual pull stations, detectors,
and telephone outlets are shown on Drawings without wiring. Submit drawings of equipment
being used and appropriate schematic wiring diagrams.
B. Product Data: Submit manufacturer's data demonstrating compliance with this Specification.
1.03
QUALITY ASSURANCE
A. Comply with the following Codes and Standards:
1.
NFPA 70
2.
UL listing for materials.
3.
ICEA S-66-524
4.
NEMA WC-7
5.
ASTM B-3 or B-8
PART 2 PRODUCTS
2.01
ACCEPTABLE MANUFACTURERS
A. Cable:
1.
2.
3.
4.
5
6.
7.
8.
General Cable
Triangle
American Insulated Wire Corp.
Rome
Okonite
Southwire
Carol
Amercable
B. Connectors:
260519 - 1
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
1.
2.
3.
4.
5.
6.
7.
8.
2.02
Ideal
Anderson Electric Corp.
Burndy Corp.
Thomas and Betts Co.
Panduit
Buchanan Electrical Mfg. Co.
O.Z. Gedney
Minnesota Mining & Manufacturing (3M)
MATERIALS
A. Conductors for wire and cable shall be copper based on 98 percent conductivity and shall be
tinned or untinned in accordance with established standards for the type of insulation around the
conductors. No. 10 AWG and smaller shall be solid and No. 8 AWG and larger shall be stranded.
B. Wire and cable shall be stamped approximately every two feet to indicate voltage, type,
temperature rating, and other significant data or warnings.
C. Cable or wire 600 volt or less shall meet the following requirements:
1.
600 volt insulation.
2.
Not less than No. 12 AWG.
3.
No. 14 AWG may be used for control and low voltage wiring only.
4.
Type THWN, THHN or XHHW insulation.
D. Direct buried cables: Underground cables of the direct burial type, shall be UL approved for direct
burial, with type XHHW or THWN insulated conductors within the jacket. Overall outer edge
covering to be flame-retardant, moisture-resistant; fungus-resistant, and corrosive resistant, such
as type UF.
E. Communications (low voltage) type wires and cables:
1.
Wires (cables) shall be of the size, type, materials, as required by the specific system
specification and as required by the system equipment manufacturer.
2.
When run in raceways separate from the power wiring and not mixed with the power
wiring, communications cables may have 300 volt insulation.
3.
When run without conduit in accessible locations and not laid on ceiling tiles or tee bars,
wires shall be supported every 4 feet, and have plenum rated insulation.
F. Wire Pulling Lubricant: Lubricant shall be UL listed and be of a consistency which will not leave
an obstruction or tackiness that prevents pulling out old wires, pulling in new wires, or adding
more wires. No soap flakes or vegetable soaps will be permitted. Lubricant in steel conduit shall
be Ideal Wire Lube or equal.
G. Cable Ties: Wiring in panels, cabinets, etc. shall be neat and tied with "TyRap" T&B "TY5418"
series, or Panduit Co. "Cable Wrap".
H. High voltage (above 600 volt) cable and terminations: See Section 16121.
I.
Splices and Connectors:
1.
No. 18 No. 22 AWG: Use 3M Scotchlok Type 557 and 558.
2.
2 No. 28 thru 4 No. 24 or 3 No. 12 AWG: Use 3M Scotchlok Hy Flex No. 212.
3.
5 No. 24 thru 5 No. 12 or 3 No. 10 AWG: Use 3M Scotchlok Hy Flex No. 310.
4.
No. 10 AWG up to No. 6 AWG: Use 3M Scotchlok Types Y, R, G and B.
5.
No. 8 and larger sizes, use:
260519 - 2
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
a. 3M Scotchlok lugs and connectors copper.
b. OZ Company solderless connectors and power connectors.
c. Burndy Cable to cable type UC, CP, QPX, VP, QPR, GX, CC1, CC2, CC4, NT, NTHC,
NNTRHC, NTR, QT, NS, VR, KP, KS, KS3, CKS, SC, QR, RN, KVS, KVSW, VT, or NVT
as appropriate for cable size and configuration.
J.
Terminations:
1.
3M Scotchlok lugs and connectors copper.
2.
OZ solderless connectors, grounding devices, power connectors, armored cable fittings,
and cable terminations.
3.
Burndy copper all types as appropriate for cable size and configuration
K. Connector material shall be compatible with conductor material to prevent corroding, differences
in coefficients of expansion or electrolysis.
PART 3 EXECUTION
3.01
INSTALLATION - WIRES AND CABLES
A. Install wires and cables in NFPA 70 approved raceways (Section 16110).
B. Internal fixture wiring shall be minimum No. 14 AWG, type AF or TF (150 deg. C) with minimum
300-volt insulation. This means 90 deg C cannot enter the fixture.
C. Branch circuit wiring shall be done with color coded conductors, using the same code throughout.
1.
Mechanical Ground-Green; Single & 3Way Return, Orange Tracer.
2.
Neutral 208/120White; 3Way Traveler, Yellow Tracer.
3.
Phase A 208/120Black; Start Control, Black Tracer.
4.
Phase B 208/120Red; Stop Control, Red Tracer.
5.
Phase C 208/120Blue; Hold Control, Brown Tracer.
6.
Phase A 480/277Brown.
7.
Phase B 480/277Orange.
8.
Phase C 480/277Yellow.
9.
Neutral 480/277Natural Gray.
D. Colors as selected for the purpose of identifying circuits shall be applied to the wire. The color
shall be color fast, and capable of withstanding cleaning in the event wire becomes soiled.
E. Tag circuit wires in cabinets with 1/2 inch diameter l/16 inch thick tags securely fastened to
conductors or with approved tape numbering at time wires are pulled in and tested. Circuit
numbers shall be stamped into the tags or permanent tape numbers. Tags or tape shall not be
removed.
F. A minimum of 6 inch loops or ends shall be left at each outlet for installation of future devices or
fixtures. Wires in outlet boxes not for the connection to fixtures at that outlet, shall be rolled up,
connected together and taped or capped with wire nuts.
G. Branch circuit sizing:
1.
Branch circuit wiring from panels to an outlet on the circuit shall be minimum No. 12
AWG. Exit light or emergency wiring shall be minimum No. 10 AWG.
2.
Conductors for branch circuits of 129 volts over 100 feet long and of 277 volts over 230
long shall be minimum No. 10 AWG.
3.
Class 1 remote control and signal circuit conductors shall be minimum No. 14 AWG.
260519 - 3
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
4.
5.
6.
Class 2 low energy remote control and signal conductors shall be minimum No. 16 AWG.
Fire alarm No. 26 allowed if adequate.
Special signal communications or similar systems wiring (cables) shall be sized as shown
on the Drawings or as required by the manufacturer for satisfactory operation.
7.
As noted on the Drawings.
H. Buried Cables: Underground feeders of the direct burial type are allowed only where called for or
noted on the Drawings. Direct buried cables, unless otherwise noted on the Drawings, shall be
installed a minimum of 30 inches below finished grade and rest on and be covered with a six inch
layer of sand to prevent cable damage. Cables shall be protected by a creosoted plank where
physical protection is required. Buried cables shall enter manholes, building walls, or termination
points through a protective steel conduit sleeve of appropriate size. Open ends of sleeves shall be
provided with a moisture seal after cable is installed. Seal shall be type approved for system
voltage and cable insulation. Install a buried warning tape 12 inches above all buried cables.
I.
3.02
Pulling Cables:
1.
Wires and cables shall be carefully handled during installation. Lubricant used for pulling
in wires and cables shall be an approved type.
2.
Pulling tension: Pulling eyes, basket grips and pulls in straight ducts are permitted by
tensions shall not exceed the following:
a. Pulling eyes: T = 0.008 x N x CM, T = tensions (lbs.), N = No. of conductors, CM =
circular Mil area.
b. Basket grips: T = 4712 x t x (Dt) T = tension (lbs. sq. in.), t = sheath thickness (in.), D =
cable outside diameter (in.). Maximum strain should not exceed 1,000 lbs./sq. in.
c. Straight ducts: T = L x W x F, T = tension (lb.), L = length of duct run, W = weight of
cable (lb./gt.), F = coefficient of friction (0.5 for most well made ducts).
INSTALLATION - CONNECTORS AND TERMINATIONS
A. Joints and terminations: Joints in conductors shall be as few as possible. Where joints are
necessary, they shall be mechanically strong and well made so that the electrical resistance of a
joint shall not exceed that of two feet of the conductor. Splices and terminations shall be made
only in junction boxes and never in conduit. Do not splice in panels.
B. Stranded cables shall be soldered into lugs. Wrapping around binding posts shall not be
permitted.
C. For 600 volt wire No. 8 and smaller, use wing nut solderless connectors, or solder; No. 6 and
larger, use insulated parallel connectors. Use tape to an equivalent insulation thickness on
uninsulated splices and apply an insulating coat of paint. Follow manufacturer's recommendations
for sizing, stripping, twisting, etc.
D. Connections: Shall be made with screw-on, set-screw, clamp-on, split-bolt, crimp and
compression-type lugs, taps and terminal fittings as permitted by local codes.
E. Where special tools are required to properly install the particular connector the special tools must
be used.
END OF SECTION
260519 - 4