Download KB ELECTRONICS, INC. 12095 NW 39th Street, Coral Springs

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Three-phase electric power wikipedia , lookup

Rectifier wikipedia , lookup

Ohm's law wikipedia , lookup

Islanding wikipedia , lookup

Heterodyne wikipedia , lookup

Ground (electricity) wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Electrical substation wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Stepper motor wikipedia , lookup

Buck converter wikipedia , lookup

Voltage regulator wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Surge protector wikipedia , lookup

Rectiverter wikipedia , lookup

Metadyne wikipedia , lookup

Potentiometer wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Opto-isolator wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical wiring wikipedia , lookup

National Electrical Code wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
"The Right Control
for your Application"
KB ELECTRONICS, INC.
12095 NW 39th Street, Coral Springs, Florida 33065 USA
(954) 346-4900 FAX (954) 346-3377
SUBJECT: PROPER WIRING PRACTICES FOR AC and DC DRIVES
The subject of electrical noise (Radio Frequency Interference and Electro-Magnetic
Interference) is a hot topic. Electrical noise can cause erratic performance, and even
failures, of AC and DC Drives. It often occurs because customers do not pay attention
to proper wiring techniques when installing AC and DC Drives.
When investigating possible noise problems, please check that the following
guidelines have been followed during the installation and wiring of AC and DC Drives.
These guidelines are just as important inside the customer’s cabinet as they are in
wiring on the machine.
1.
Power leads must be separated from signal leads. High voltage leads such as
incoming line, or outgoing armature and field circuits can be run together, but
must be separated from low voltage signals. In addition, stranded copper wire
should be used, not a solid conductor.
2.
If a noise filter is installed in advance of the AC or DC Drive, the wiring from the
filter to the drive should be as short as possible. It is also necessary to shield
the motor leads once a noise filter is installed.
3.
Low voltage leads such as potentiometers, inhibit and enable circuits, start/stop
and reversing commands can be further divided into two groups, switching and
analog signals. These leads can be run together as long as the analog signals
(potentiometer or voltage following) are shielded from the switching signals
(inhibit, start/stop or reversing). Signal leads, such as potentiometers,
transducers or milliamp signals, should be wired with either shielded or twisted
wire. Multi conductor twisted cable is recommended. If shielded wire must be
used, the shield must be securely grounded at the AC and DC Drive end only.
However, there may be times when grounding the shield is not necessary. This
may only be determined by trial and error.
4.
When low voltage and/or high voltage leads must go to the same location, for
example, to an in-cabinet terminal strip, or through conduit to the machine, they
must be wired separately. It is not acceptable to use a cable or “drop cord”
which mixes these leads together. If these leads cross in a cabinet, they
should do so at right angles to minimize the influence of induced magnetic
fields.