Download Chapter 2

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rectifier wikipedia , lookup

Mains electricity wikipedia , lookup

Electronic paper wikipedia , lookup

Electrical substation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

History of electric power transmission wikipedia , lookup

Alternating current wikipedia , lookup

Metadyne wikipedia , lookup

Three-phase electric power wikipedia , lookup

Transformer wikipedia , lookup

Transcript
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
PowerPoint Slides
to accompany
Electric Machinery
Sixth Edition
A.E. Fitzgerald
Charles Kingsley, Jr.
Stephen D. Umans
Chapter 2
Transformers
2-0
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Transformer with open secondary.
Figure 2.4
2-1
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
No-load phasor diagram.
Figure 2.5
2-2
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Ideal transformer and load.
Figure 2.6
2-3
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Three circuits which are identical at
terminals ab when the transformer
is ideal.
Figure 2.7
2-4
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Equivalent circuits for Example 2.2 (a) Impedance
in series with the secondary. (b) Impedance referred
to the primary.
Figure 2.8
2-5
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Schematic view of mutual
and leakage fluxes in a
transformer.
Figure 2.9
2-6
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Steps in the
development
of the
transformer
equivalent
circuit.
Figure 2.10
2-7
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Equivalent circuits for transformer of Example 2.3
referred to (a) the high-voltage side and (b) the
low-voltage side.
Figure 2.11
2-8
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Approximate transformer equivalent circuits.
Figure 2.12
2-9
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Cantilever equivalent circuit for Example 2.4.
Figure 2.13
2-10
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
(a) Equivalent circuit and (b) phasor diagram
for Example 2.5.
Figure 2.14
2-11
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Equivalent circuit with short-circuited secondary.
(a) Complete equivalent circuit. (b) Cantilever equivalent
circuit with the exciting branch at the transformer
secondary.
Figure 2.15
2-12
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Equivalent circuit with open-circuited secondary.
(a) Complete equivalent circuit. (b) Cantilever equivalent
circuit with the exciting branch at the transformer primary.
Figure 2.16
2-13
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
(a) Two-winding transformer. (b) Connection
as an autotransformer.
Figure 2.17
2-14
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
(a) Autotransformer connection for Example 2.7.
(b) Currents under rated load.
Figure 2.18
2-15
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Common three-phase transformer connections; the
transformer windings are indicated by the heavy lines.
Figure 2.19
2-16
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
2.8 VOLTAGE AND CURRENT TRANSFORMERS
Used in instrumentation applications
765 000 Volt, 10 000 Ampers can not be measured directly
Most instruments range: Voltage (Potantial) Transformers (PT)
0-120 V rms; Current Transformers (CT) 0-5 A rms
Equivalent circuit for an instrumentation transformer. Figure 2.21
Rc (core loss resistance) neglected in equivalent circuit.
Zb is referred to as the BURDEN on that transformer.
2-17
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
FOR PT:
Z eq Z b
Vˆ2  N 2 



ˆ
V1  N1  ( R1  j X 1 )( Z eq  Z b  R2  j X 2 )
Z eq 
j X m ( R1  j X 1 )
R1  j ( X m  X 1 )
Zb  ( N1 / N2 )2 Zb
FOR CT:
j Xm
Iˆ2  N1 

 
Iˆ1  N 2  Zb  R2  j ( X 2  X m )
2-18
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Example 2.10: A 2400:120 V, 60 Hz potential transformer has the
following parameter values (referred to the 2400 V winding
side):
X1 143 
X 2  164 
R1 128 
X m  163 k
R2  141 
a) Assuming a 2400 V input, which ideally should produce a
voltage of 120 V at the low voltage winding, calculate the
magnitude and relative phase-angle errors of the secondary
voltage if the secondary winding is open-circuited.
b) Assuming the burden impedance to be purely resistive
(Zb=Rb), calculate the minimum resistance (maximum burden)
that can be applied to the secondary such that the magnitude
error is less than 0.5 percent.
c) Repeat part (b) but find the minimum resistance such that the
phase-angle error is less than 1 degree.
2-19
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
2.9
THE PER-UNIT SYSTEM
Computations relating to machines, transformers, and systems
of machines are often carried out in per-unit form.
Quantities are expressed as ratios to chosen BASE values.
V, I, P, Q, S, R, X, Z, G (conductance), B (susceptance), Y
can be translated.
Quantity in per  unit 
Single Phase:
Sbase  Vbase I base
Base Change:
Z pu2
2-20
Actual quantity
Base value of quantity
Zbase  Vbase / I base
2
Vbase
1 Sbase2
 Z pu1 2
Vbase2 Sbase1
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Example 2.12: The equivalent circuit for a 100 MVA, 7.97 kV:79.7
kV transformer is shown in Fig. 2.22a. Convert the equivalent
circuit parameters to per-unit using the transformer rating as
base.
7.97 kV:79.7 kV
X L  0.04 
X H  3.75 
X m  114 
RL  0.76 m
RH  0.085 
2-21
Copyright © The McGraw-Hill Companies, Inc. Permission required for reproduction or display.
Example 2.8: Three single-phase, 50 kV 2400:240 V transformers,
each identical with an impedance of 1.42+j1.82 Ohm referred to
high voltage side is connected Wye-Delta in a three-phase 150
kVA bank to step down the voltage at the load end of a feeder
whose impedance is 0.15+j1 Ohm/phase. The voltage at the
sending end of the feeder is 4160 V line-to-line. On their
secondary sides, the transformer supply a balanced threephase load through a feeder whos impedance is 0.0005+j
0.0020 Ohm/phase. Find the line-to-line voltage at the load
when the load draws rated current from the transformer at a
power factor of 0.8 lagging.
2-22