Download EECE 581

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Tube sound wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

War of the currents wikipedia , lookup

Stepper motor wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Electrical ballast wikipedia , lookup

Islanding wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Ground (electricity) wikipedia , lookup

Power inverter wikipedia , lookup

Ohm's law wikipedia , lookup

Tesla coil wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Multimeter wikipedia , lookup

Power electronics wikipedia , lookup

Current source wikipedia , lookup

Power MOSFET wikipedia , lookup

Power engineering wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Buck converter wikipedia , lookup

Metadyne wikipedia , lookup

Surge protector wikipedia , lookup

Rectifier wikipedia , lookup

Voltage regulator wikipedia , lookup

Opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Distribution management system wikipedia , lookup

Single-wire earth return wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

History of electric power transmission wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Three-phase electric power wikipedia , lookup

Transformer wikipedia , lookup

Transcript
EECE 581
HW #5
1. Given the transformer test results below, draw the simplified transformer circuit with
all impedance values given on the primary side. Assume the transformer is rated
16,200/480 V, and 10 kVA.
OC Test (done on secondary side): Voc = 480 V, Ioc = 0.5 A, Poc = 200 W
SC Test (done on primary side): Vsc = 1000 V, Isc = 15 A, Psc = 2000 W
2. Assume a system consisting of a voltage source, connected to a j5 Ohm transmission
line to a transformer which has a 20 kW (pf = 0.8 lag) load connected to it’s
secondary. Assume a 25 kVA, 4800/120 V transformer with Req = 3 Ohms, Xeq =
5 Ohms, Rc = 500 Ohms, and Xm = 700 Ohms. Assume the load is at the rated
voltage.
a. Draw the complete circuit in pu using Sbase = 25 kVA and the transformer ratings
for the base voltages.
b. Find the source current in pu and in Amps.
3. A 3-phase 345 kV/16.2 kV transformer bank is to be connected in a Delta-Y
connection.
a. What must the voltage ratings of the three individual transformers be?
b. Draw the transformers and their connections to the lines.
4. 3 single-phase, 16.2 kV/208 V transformers are to be connected Y-Delta with a load
on the low voltage side. The load takes 20 Amps at a power factor of 0.7 lag when it
is at the rated voltage. Each transformer has Req = 2 Ohms, Xeq = 3 Ohms and Rc
& Xm infinite.
a. What is the line voltage on the high voltage side of the transformer?
b. What is the phase angle difference between the line voltages on either side of the
transformer? What causes this?