Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Data Sheet Explanation When filling out the AABC data sheets, it is important to correctly fill in the various data blocks, or cells, so that others reading the report will be able to properly interpret the information. In order to achieve this, the data sheets should be filled out the same way with the same type of information every time. It is also important that the data sheets be arranged in a standard order. These instructions will explain the type of data that is to be entered in each cell on each data sheet. When filling in the data the manuscript should be neat and legible. Common Fields Every data sheet has several common fields. While they may seem selfexplanatory, a few comments are in order. Date The date when the report is issued. Page _ of _ Appropriate page numbers should be assigned to each data sheet when the agenda is prepared. While it is appreciated that findings in the field may cause some pages to be reassigned, putting the pages in a preliminary order reduces confusion and makes keeping track of the various parts of the report much easier. This is especially helpful if more than one technician works on a job. Project Name The name assigned to the project by the supervisor or office. System The air or water system for which data is entered on a given sheet. On data sheets that contain information for more than one system, all appropriate system designations should be entered. System designations will usually be assigned by the design engineer. If no such designations exist, or there are duplicate designations, the person preparing the agenda will assign them. Remarks At the bottom of each data sheet are several lines for remarks. The exact nature of these remarks varies by TAB firm, but generally explanations for discrepancies or procedures go here. Individual Data Sheets The individual data sheet explanations will be presented in the order in which the TAB report should be assembled. A summary of the data sheets intent will be given and the cell headings will be listed on the left along with an explanation of type of information to be entered. Instrument List The TAB supervisor will prepare a list of the instruments that they expect will be necessary for the job. Once the field phase of the project begins, any additional tools or instrumentation should be entered on this sheet. Instrument A specific TAB instrument or piece of equipment. Examples would be pitot tubes, anemometers, amp probes, balometers, tachometers, temperature probes, etc. Manufacturer The manufacturer of the specific instrument. Model The model number of the instrument. Serial Number The serial number of the instrument. Calibration Date Most test equipment must be calibrated on a regular basis and this information will be on a sticker applied by the testing firm. Enter the date of the most recent calibration here. Some devices, such as pitot tubes, have no moving parts and this space does not apply for them. Air Moving Data This sheet is generally used for all air moving equipment except for exhaust and ventilation fans. Note that not all data will be required or available for every unit. The AABC data sheet has space for two pieces of equipment. Note that for air moving equipment containing two fans in one unit, such as a unit equipped with a supply and return fan, each fan should be entered individually. In those instances the System field at the top of the sheet will have only the name of the complete unit, indicating that this is one unit with two fans. Some TAB firms use this sheet to show performance data for the same unit under two different conditions, such as performance at minimum and maximum outside air setting. In those instances the common data should be filled in for both conditions. Each TAB firm will establish their own methods of differentiating between the two conditions. Fan The name of the fan. If the unit has one fan, this will be the same as the system name. If the unit has multiple fans, the naming convention outlined above will be used. For example, if System AHU-1 has one fan, then AHU-1 will be entered in the Fan field. If System AHU-1 has both a supply and return fan, then one might enter SF-1 in one cell and RF-1 in the adjacent cell. Equipment Location Area Served Equipment Manufacturer The physical location of the equipment. If the equipment is located in a room, the room number or other uniquely descriptive designation should be used. The general area served by the ductwork associated with a given unit. Examples might be ‘2nd Floor’, ‘West Side’, etc. The mfg. of the equipment. This can be found in the submittal data or on the unit. Model The manufacturer’s model number. This can be found on the submittal information or on the manufacturer’s data plate on the unit. Serial Number The manufacturer’s unique unit serial number. This is usually found on the unit data plate. The following fields have provisions for two sets of data, Specified and Actual. Specified The design data for the unit. This information is usually found in the submittal data or on the unit data plate. Actual Field-measured data for the unit. Total CFM – Fan The total supply airflow volume in Cubic Feet per Minute for the unit. Total CFM – Outlet The supply airflow volume in Cubic Feet per Minute at the supply grilles. R/A CFM The total Return Air airflow volume in Cubic Feet per Minute. O/A CFM Total/External Static Pressure The total Outside Air airflow volume in Cubic Feet per Minute. Total static pressure is taken across the fan and External static pressure is taken across the unit. Static pressure is measured in inches water gauge and is written n in. w.g. or n“. Usually only one measurement or the other will be required. Inlet Pressure The static pressure at the unit intake. Discharge Pressure The static pressure at the unit discharge. Fan RPM Motor Manufacturer The RPM (Revolutions Per Minute) of the fan rounded to the nearest whole number. The manufacturer of the fan motor. Motor HP/BHP Motor horsepower is usually given on the motor data plate. Brake horsepower is usually a calculated quantity but may be given in the manufacturer’s submittal data. Phase/Hz The motor electrical phase, either 1 or 3, and the Hertz, usually 50 or 60. Voltage The operating voltage of the supplied power. It is not uncommon for a motor to be capable of operation with multiple voltages. The correct voltage is either given in the submittal data or field verified. Amperage The operating amp draw of the motor. On the data plate this is usually shown as FLA for Full Load Amps. Note that the FLA of a motor will vary depending on what voltage it is wired for. Motor Service Factor/Frame # Starter Location/ The motor Service Factor is usually shown on the motor data plate and abbreviated SF. The Frame # is also on the motor data plate. Size O.L. Heater Size/ Rating Motor Sheave & Shaft Fan Sheave & Shaft Applicable to units equipped with motor starters. The motor starter’s physical location is put here. The size of the motor starter is usually located on the starter. The Overload Heater is located with the motor starter. The size and rating are located on the heater. The motor sheave is identified by the manufacturer’s model number, usually located on the sheave itself. The shaft size is measured to the nearest 1/16 of an inch. The format is motor sheave model number x shaft size. This information is entered in exactly the same way as that for the motor sheave & shaft. Belt Size/Number The Belt Size is usually printed on the belt. The Number is the number of belts on the drive. Sheave Adjustment C to C/ Motor Mount Adjustment This is given in the number of turns from the closed position. If the two sheave halves are touching, then the sheave is said to be ‘0 Turns Open’. A sheave in which the two halves are as far apart as possible is said to be ‘4 (or whatever the maximum number of turns is) Turns Open. A manufacturer’s catalog will give the total number of turns available for a given sheave. C to C is the center-to-center distance between the motor and fan shafts. The measurement is taken from the center of one shaft to the center of the other. The Motor Mount Adjustment is given in the distance that the center of one shaft, usually the motor, can move In or Out in relation to the other. Static Pressure Profile This form is where the static pressure test points for a given piece of equipment is recorded. There is a representative drawing of a piece of air moving equipment at the top of the sheet. Test points are marked with letters and the spaces between the letters represent components such as coils, filters, etc. The sheet is designed so that multiple units can be recorded on the same form. While this reduces the number of data sheets required for a given job, this form works best when all of the units on the same sheet share common components. Write the names of the various components in the blocks between the lettered test points. Not all blocks may be filled, depending on the configuration of the unit. The unit names are recorded in the far left cells on the table. The static pressure value for each test point is then placed in the appropriate letter column and unit row. Note that the letters ‘a’ and ‘j’ correspond to the Inlet Pressure and Discharge Pressure cells on the Air Moving Equipment Data sheet. Fan Data Exhaust and ventilation fan information are usually recorded on this data sheet. Fan The name of the fan. If the unit has one fan, this will be the same as the system name. If the unit has multiple fans, the naming convention outlined above will be used. For example, if System AHU-1 has one fan, then AHU-1 will be entered in the Fan field. If System AHU-1 has both a supply and return fan, then one might enter SF-1 in one cell and RF-1 in the adjacent cell. Equipment Location Area Served Equipment Manufacturer Model The physical location of the equipment. If the equipment is located in a room, the room number or other uniquely descriptive designation should be used. The general area served by a given unit. Examples might be ‘2nd Floor’, ‘West Side’, etc. The mfg. of the equipment. This is found in the submittal data or on the unit housing. The manufacturer’s model number. This can be found on the submittal information or on the manufacturer’s data plate on the unit. Serial Number The manufacturer’s unique unit serial number. This is usually found on the unit data plate. The following fields have provisions for two sets of data, Specified and Actual. Specified The design data for the unit. This information is usually found in the submittal data or on the unit data plate. Actual Field-measured data for the unit. Total CFM – Fan The total airflow volume for the unit in Cubic Feet per Minute. Total CFM – Air Distribution Total/External Static Pressure The total airflow volume in Cubic Feet per Minute at the distribution terminals associated with the unit. For fans without ductwork this will be the same as the Total CFM – Fan cell. Total static pressure is taken across the fan and External static pressure is taken across the unit. Static pressure is measured in inches water gauge and is written n in. w.g. or n“. Usually only one measurement or the other will be required. Inlet Pressure The static pressure at the unit intake. Discharge Pressure The static pressure at the unit discharge. Fan RPM Motor Manufacturer The RPM (Revolutions Per Minute) of the fan rounded to the nearest whole number. The manufacturer of a given fan motor. Motor HP/BHP Motor horsepower is usually given on the motor data plate. Brake horsepower is usually a calculated quantity but may be given in the manufacturer’s submittal data. Phase/Hz The motor electrical phase, either 1 or 3, and the Hertz, usually 50 or 60. Voltage The operating voltage of the supplied power. It is not uncommon for a motor to be capable of operation with multiple voltages. The correct voltage is either given in the submittal data or field verified. Amperage Motor Service Factor/Frame # Starter Location/ Size O.L. Heater Size/ Rating Motor Sheave & Shaft Fan Sheave & Shaft The operating amp draw of the motor. On the data plate this is usually shown as FLA for Full Load Amps. Note that the FLA of a motor will vary depending on what voltage it is wired for. The motor Service Factor is usually shown on the motor data plate and abbreviated SF. The Frame # is also on the motor data plate. Applicable to units equipped with motor starters. The motor starter’s physical location is put here. The size of the motor starter is usually located on the starter. The Overload Heater is located with the motor starter. The size and rating are located on the heater. The motor sheave is identified by the manufacturer’s model number, usually located on the sheave itself. The shaft size is measured to the nearest 1/16 of an inch. The format is motor sheave model number x shaft size. This information is entered in exactly the same way as that for the motor sheave & shaft. Belt Size/Number The Belt Size is usually printed on the belt. The Number is the number of belts on the drive. Sheave Adjustment C to C/ Motor Mount This is given in the number of turns from the closed position. If the two sheave halves are touching, then the sheave is said to be ‘0 Turns Open’. A sheave in which the two halves are as far apart as possible is said to be ‘4 (or whatever the maximum number of turns is) Turns Open. A manufacturer’s catalog will give the total number of turns available for a given sheave. Adjustment C to C is the center-to-center distance between the motor and fan shafts. The measurement is taken from the center of one shaft to the center of the other. The Motor Mount Adjustment is given in the distance that the center of one shaft, usually the motor, can move In or Out in relation to the other. Duct Traverse Data This is where data for duct traverses are recorded. This data sheet has two unique fields at the top of the sheet, Area Served and Traverse Location. Area Served Traverse Location This is the same type of information recorded on the Air Moving Equipment Data sheet for this cell. In this case the area served is the area downstream of the traverse location. The physical location of the traverse. This should be a room number or some other uniquely identifiable location. The Duct Traverse Data sheet contains a table on which each reading of the traverse is recorded. After the traverse points have been determined for a given duct, the corresponding readings are entered into the table at the appropriate spot. Readings are recorded in FPM. The Total row at the bottom of the table is the sum of each of the columns. At the bottom of the table is the formula for determining the CFM of the duct with spaces to fill in the required information. Total FPM The sum of all the cells in the Total row. No. Readings The total number of readings taken for the traverse. Average FPM This is the calculated average of the airflow FPM in the duct. Record this data to the nearest whole number. Area The area of the duct cross-section in square feet. Total CFM This is the calculated airflow in Cubic Feet per Minute. Record to the nearest whole number. The Design and Test Data tables at the bottom of the page serve the same purpose as the Specified and Actual fields on other data sheets. Duct Size I.D. The interior cross-section dimensions of the duct. This is recorded as a single number for circular ducts (12”, 8”, etc.) or as the height and width for rectangular ducts (12” x 8”, etc.) CFM The design airflow volume in Cubic Feet per Minute for that particular duct. This is usually found by summing up the terminal devices such as grilles, outlets, etc., for the area served by the duct. Areas The cross-sectional area of the duct in square feet. Center Line Static Pressure Density Correction CFM Standard Correction The static pressure recorded in the center of the duct. Air pressure is recorded in inches water gauge and is written n in. w.g. or n”. When the air in the system is significantly warmer than standard or if the measurement is performed at altitude allowance must be made for the change in air density under those conditions. The result of the air density correction formula will be entered in this cell. If there is no correction needed, enter a ‘1.0’. This is the entry in the Total CFM cell from the CFM formula multiplied by the entry in the Density Correction cell. The result gives the actual CFM in the duct. This entry is rounded to the nearest whole number. Air Monitoring Station Data An air monitoring station is a mass airflow sensor located in the duct to read velocity and volume of airflow in the system. Station Number The unique designation of a given station. System The specific system ductwork in which the air monitoring station is located. Area Served The area served by the ductwork in which the air monitoring station is located. Size The cross-sectional dimensions of the duct. Area Sq. Ft. The cross-sectional area of the duct in square feet. Design FPM The design velocity of the airflow in Feet Per Minute in the duct. CFM The design volume of the airflow in Cubic Feet per Minute in the duct. Test The first two columns are for recording the velocity of the airflow in FPM for each balancing pass through the system. The CFM column is the final volume of airflow in the duct. Air Distribution Data The information for terminal devices such as diffusers or grilles is entered on this data sheet. Because many mechanical specifications require that all adjustments be documented, it is important to record every pass through the system. Terminal Number Room Number Terminal Type The number given to each air terminal device. This number is usually assigned when the agenda is created. The physical location of the terminal. If no room number is available, then a uniquely descriptive designation should be used. The type of air terminal. This information is usually found on the drawing or in the mechanical schedule. Size The size of the air terminal. This information is usually found on the drawing or in the mechanical schedule. Factor This is the Ak value of the air terminal. This information may be found in the submittal data but will most likely have to be calculated. If a balometer or some other total capture device is used, this value will be 1.0. Design FPM The required air velocity in Feet Per Minute for an air terminal. This is usually a calculated quantity and is found by dividing the value in the Design CFM cell by the value in the Factor cell. CFM The design airflow quantity in Cubic Feet per Minute for a given air terminal. This is usually found on the drawing but may be given in the schedule. Test-FPM or CFM Circle the appropriate value depending on whether the air terminals are tested for velocity or volume. Test 1, 2, 3 Final FPM CFM Record all air terminal readings for each pass through the system in these cells. The final velocity readings at each air terminal in Feet Per Minute. The final volume readings at each air terminal in Cubic Feet per Minute. Terminal Unit Data The Terminal Unit data sheet is for the recording of VAV box information. There are several unique fields on this data sheet. Manufacturer The manufacturer of the VAV box. There are four boxes below the data sheet title to indicate which type of box is represented on the sheet. The fields are Constant, Variable, Single, and Dual. It is necessary that all of the boxes on the data sheet be of the same type. Check the appropriate cell to indicate they type of VAV box. Box Number This is the unique box designation. This will usually be found on the drawing. If the designation is not on the drawing or duplicate designations exist, the specific designations will be assigned by the person preparing the agenda. Location The physical location of the VAV. As with other system components, this should be easily identifiable with a specific box. Model The manufacturer’s model number for the box. Size The inlet size of the box. Calibration Factor Design CFM Minimum Maximum Actual CFM Minimum Maximum After a box has been properly set up and balanced, the final calibration factor is entered here. Enter the design minimum and maximum airflow setpoints in Cubic Feet per Minute in these cells. The field-measured minimum and maximum airflow volumes in Cubic Feet per Minute are entered here. Induction Unit Data What is this? Temperature Reading Data The data on this sheet is used to assist in evaluating system performance at the time testing and balancing of the system occurs. Location Thermostat Set Point What does this refer to? The actual setpoint of the thermostat of the system when the temperature measurements take place. Time The time the data is collected. DB The Dry Bulb temperature. WB The Wet Bulb temperature. This information is collected with a sling psychrometer. %RH The Relative Humidity in percent. This is found by calculation using the wet and dry bulb temperatures or from a chart. Electric Duct Heater Data Information on this data sheet is used to evaluate the performance of electric duct heaters. The cells in the Rated and Test Data rows are not to be filled in. Required Heater # The individual duct heater designation. Location The physical location of the duct heater. This should be room number or some other locational identifier. Model # The manufacturer’s model number. Rated KW The manufacturer’s kilowatt (KW) rating for the duct heater. Stages The number of stages of heat of the duct heater. Volts/Phase The rated voltage and phase of electric power required by the heater. Test Data Voltage/Phase The actual voltage and phase of the electric power supplied to the heater. Amperage The actual amp draw of the duct heater when all heating stages are engaged. KW This is a calculated quantity found by multiplying the Voltage x Amperage from the Test Data cells and dividing by 1000. Pump Data This data sheet if for the recording of information pertaining to hydronic pumps. Pump No. The individual pump designation. Manufacturer The mfg. of the pump. Size The size of the discharge pipe. This is usually found in the submittal data or on the pump data plate. Impeller The size of the pump impeller. This is also found in the submittal data or sometimes on the pump data plate. Service The type of system on which the pump is located. Examples are ‘domestic hot water (DHW)’, ‘chilled water supply’, etc. Test Data This block contains information collected from the pump under normal operating conditions. Design refers to information supplied by the pump manufacturer while Actual refers to information measured in the field. GPM The volume of water moved by the pump in Gallons per Minute. FT. HD. The height of the water column raised by the pump when operating at design capacity. Because most flow gauges are calibrated in units of pressure, this quantity must be calculated for the Actual cell. This quantity is usually rounded to the nearest tenth HP. BHP The Design Brake Horsepower is usually given in the submittal data. The Actual BHP must be calculated. Discharge The discharge pressure of the pump, usually in Pounds per Square Inch or PSI. Suction The suction pressure of the pump, also in PSI. ∆p The ∆p (read ‘delta p’) is found by subtracting the Suction pressure from the Discharge pressure and is the change in pressure across the pump. This quantity is multiplied by 2.31 to give the FT. HD. measurement. Note that this quantity is also entered in the Actual FT. HD. cell. Shut Off These measurements are taken while the pump is running and the pump discharge valve is shut. Discharge The discharge pressure of the pump, usually in Pounds per Square Inch or PSI. Suction The suction pressure of the pump, also in PSI. ∆p The ∆p (read ‘delta p’) is found by subtracting the Suction pressure from the Discharge pressure and is the change in pressure across the pump. This quantity is multiplied by 2.31 to give the FT. HD. measurement. Note that this quantity is also entered in the Actual FT. HD. cell. Motor MFG. The motor manufacturer. Frame The motor frame, located on the motor data plate. H.P. The rated horsepower for the motor. RPM The rated RPM (Revolutions Per Minute) for the motor. Amps The first cell is where the rated motor amps are entered. The ACT: cell is where the actual amps are entered for each leg. Volts The first cell is where the rated motor voltage is entered. The ACT: cell is where the actual voltage is entered for each leg. Starter Mfg./ Size O.L. Size/ Rating On motors equipped with a motor starter, the manufacturer name and size of the starter go here. On motors so equipped, the overload size and rating are entered here. Water Balance Data Information from the testing and balancing of hydronic systems is entered on this data sheet. Designation Design GPM The unique identifier for a given balancing valve. The flow for which the balancing valve is designed in Gallons Per Minute. Ft. H2O The pressure differential across the balancing valve in feet of water that corresponds to the flow in Gallons Per Minute. In. H2O The pressure differential across the balancing valve in inches of water that corresponds to the flow in Gallons Per Minute. Balancing valves will usually be calibrated in either feet or inches of water. Preliminary For each pass through the system, enter the appropriate differential for each balancing valve in feet or inches as required. Actual The information entered into the cells under this heading is exactly the same type as that entered in the Design section. The only difference is that the data will be observed readings. GPM Totals The sum of the Design and Actual Gallons Per Minute columns. Water Flow Measuring Station A water flow measuring station differs from a balancing valve in that no adjustment is made. The fitting is designed to permit a fixed flow of fluid within a range of pressures. This data sheet has one unique header field: Manufacturer Enter the manufacturer of the measuring stations here. Station Number The assigned station designation. Location The physical location of the station. This should be a room number other easily identifiable location. Size The connecting-pipe size of the station. Model The manufacturer’s model number. Design GPM PD Test Test 1 PD, 2 PD The design flow in Gallons Per Minute. This information is usually found in the submittal data or in the mechanical schedule. The design Pressure Drop across the fitting. This will usually be in feet or inches. Record the Pressure Drop across the fitting here in feet or inches, as required. Final PD The final Pressure Drop across the fitting in feet or inches. GPM The final fluid flow through the fitting in Gallons Per Minute. Cooling Coil Data This data sheet is used to enter information about chilled water cooling coils in air handlers. System The name of the air handler in which the cooling coil is located. Location The physical location of the air handler in which the cooling coil is located. Service The area served by the system. Examples would be ‘3rd Floor South’, ’East Side’, etc. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. CFM The airflow volume across the coil in Cubic Feet per Minute. GPM The fluid flow through the coil in Gallons Per Minute. Coil P.D., FT. The fluid pressure drop across the coil measured as the difference in pressure between the inlet and outlet connections. If the reading gauge is calibrated in Pounds per Square Inch (PSI), then the result will have to be multiplied by 2.31 to obtain the difference in feet. E.W.T., ºF The Entering Water Temperature in degrees Fahrenheit. L.W.T., ºF The Leaving Water Temperature in degrees Fahrenheit. E.A.T., DB ºF The Entering Air Temperature (Dry Bulb) in degrees Fahrenheit. E.A.T., WB ºF The Entering Air Temperature (Wet Bulb) in degrees Fahrenheit. L.A.T., DB ºF The Leaving Air Temperature (Dry Bulb) in degrees Fahrenheit. L.A.T., WB ºF The Leaving Air Temperature (Wet Bulb) in degrees Fahrenheit. Air MBH The heat loss (cooling) of the air across the coil in Millions of BTU per Hour. This quantity is found by calculation. Water MBH The heat gain (heating) of the water through the coil in Millions of BTU per Hour. Direct Expansion Cooling Coil Data This data sheet is to record the information associated with the performance of cooling coils that use a chemical refrigerant for heat transfer. System The unit name in which the cooling coil is located. Location The physical location of the unit. Service The area served by the unit. Examples might be ‘Computer Room’, 4th Floor’, etc. Manufacturer The unit manufacturer. The following fields have two categories, Design and Actual. Design refers to the performance parameters supplied by the manufacturer and can be found on the unit data plate or in the submittal data. Actual is the performance data measured in the field. CFM The volume of airflow through the coil in Cubic Feet per Minute. E.A.T., DB ºF The Dry Bulb Entering Air Temperature to the coil in degrees Fahrenheit. E.A.T., WB ºF The Wet Bulb Entering Air Temperature to the coil in degrees Fahrenheit. L.A.T., DB ºF The Dry Bulb Leaving Air Temperature from the coil in degrees Fahrenheit. L.A.T., WB ºF The Wet Bulb Leaving Air Temperature from the coil in degrees Fahrenheit. MBH The total heat gain (or loss) as the air passes through the coil in Millions of BTU per Hour. This is a calculated quantity. Heating Coil Data This is the same type of information used for the Cooling Coil Data sheet, except that here the air is gaining rather than losing heat. System The name of the air handler in which the heating coil is located. Location The physical location of the air handler in which the heating is located. Service The area served by the system. Examples would be ‘3rd Floor South’, ’East Side’, etc. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. CFM The airflow volume across the coil in Cubic Feet per Minute. GPM The fluid flow through the coil in Gallons Per Minute. Coil P.D., FT. The fluid pressure drop across the coil measured as the difference in pressure between the inlet and outlet connections. If the reading gauge is calibrated in Pounds per Square Inch (PSI), then the result will have to be multiplied by 2.31 to obtain the difference in feet. E.W.T., ºF The Entering Water Temperature in degrees Fahrenheit. L.W.T., ºF The Leaving Water Temperature in degrees Fahrenheit. E.A.T., DB ºF The Entering Air Temperature (Dry Bulb) in degrees Fahrenheit. E.A.T., WB ºF The Entering Air Temperature (Wet Bulb) in degrees Fahrenheit. L.A.T., DB ºF The Leaving Air Temperature (Dry Bulb) in degrees Fahrenheit. L.A.T., WB ºF The Leaving Air Temperature (Wet Bulb) in degrees Fahrenheit. Air MBH The heat gain of the air across the coil in Millions of BTU per Hour. This quantity is found by calculation. Water MBH The heat loss of the water through the coil in Millions of BTU per Hour. Cooling Tower Data This data sheet is used to record the performance and motor data for a cooling tower. Designation The individual cooling tower designation. Manufacturer The manufacturer of the cooling tower. Model No. The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. Rated Capacity In Tons Cooling tower capacities are given in tons of cooling. This information is usually found on the unit data plate or in the submittal data. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Performance GPM The rate of flow of water through the tower in Gallons Per Minute. Entering Water ºF The temperature of the water entering the cooling tower in degrees Fahrenheit. Leaving Water ºF The temperature of the water leaving the cooling tower in degrees Fahrenheit. Entering Wet Bulb ºF Leaving The wet bulb temperature of the air entering the cooling tower in degrees Fahrenheit. Wet Bulb ºF Ambient Dry Bulb ºF The wet bulb temperature of the air leaving the cooling tower in degrees Fahrenheit. The dry bulb temperature of the surrounding air in degrees Fahrenheit. Cooling towers may have more than one fan motor. It is important that data for all motors is recorded. Motor Manufacturer The motor manufacturer. Frame The frame size of the motor. This is usually found on the motor nameplate and may also be in the submittal data. HP/KW Depending on where the motor was manufactured the power rating may be in Horsepower or Kilowatts. Only one of the too should be put in this cell. Phases The phase number of the electrical power supplied to the motor. Nameplate Amps The design Full Load Amps (FLA) of the motor. Note that motors can be designed to run on different voltages and the FLA will vary according to the voltage that the motor is running on. Actual Amps The field-recorded amperage of the motor under normal operating conditions. Nameplate Volts The voltage on which the motor is designed to operate. Care should be taken to ensure that the proper voltage is recorded. Actual Volts The actual voltage on which the motor is operating. Starter Mfg./Size On motors equipped with motor starters, put the manufacturer and size of the motor starter here. Heater Elem. Size/ Rating Put the size and rating of the motor starter heater element here. Design RPM The design speed of the motor in Revolutions Per Minute Actual RPM The measured speed of the motor in Revolutions Per Minute. Chiller Data This data sheet is only for water cooled chillers. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Manufacturer The manufacturer of the chiller. Capacity Chillers are rated in tons of cooling. This information should be recorded here. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Cooler This is also known as the evaporator. Entering Water Temp. The temperature of the water entering the evaporator. Leaving Water Temp. The temperature of the water leaving the evaporator. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the evaporator. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. GPM Condenser Entering Water Temp. The volume of water flow through the evaporator in Gallons Per Minute. The temperature of the water entering the condenser. Leaving Water Temp. The temperature of the water leaving the condenser. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the condenser. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. GPM The volume of water flow through the condenser in Gallons Per Minute. Electrical Voltage The operating voltage of the condenser. Amperage The operating current draw of the condenser. Air Cooled Chiller Data Information for air cooled chillers is put on this data sheet. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Manufacturer The manufacturer of the chiller. Capacity Chillers are rated in tons of cooling. This information should be recorded here. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Cooler This is also known as the evaporator. Entering Water Temp. The temperature of the water entering the evaporator. Leaving Water Temp. The temperature of the water leaving the evaporator. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the evaporator. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. GPM The volume of water flow through the evaporator in Gallons Per Minute. Condenser Entering Water Temp. The temperature of the water entering the condenser. Electrical Compressor Amps The operating voltage of the compressor. Compressor Volts The operating voltage of the compressor. Fan Amps The operating amperage of the fan. Fan Volts The operating voltage of the fan. Air Cooled Condensing Unit Data Information for air cooled condensing units goes on this sheet. Note that there is space on the sheet for up to four units. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Manufacturer The manufacturer of the chiller. Capacity Chillers are rated in tons of cooling. This information should be recorded here. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Condenser Entering Air Temp. The temperature of the air entering the condenser. Electrical Compressor Amps The operating voltage of the compressor. Compressor Volts The operating voltage of the compressor. Fan Amps The operating amperage of the fan. Fan Volts The operating voltage of the fan. Hot Water Boiler Data This data sheet is to be used for the testing of hot water boilers. Note that there are provisions for data for up to four boilers. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Location The physical location of the boiler. Rating BTU/Hour Boilers are rated in terms of how many BTU/Hour they can provide under normal operating conditions. This information may be found in the submittal data or on the boiler data plate. Manufacturer The manufacturer of the boiler. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Secondary Hot Water Entering Temperature The temperature of the water entering the boiler. Leaving Temperature The temperature of the water leaving the boiler. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the boiler. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. Flow GPM The volume of water flow through the boiler in Gallons Per Minute. Control Setting What is this? Steam Boiler Data Information gathered when testing steam boilers is entered on this data sheet. As with the Hot Water Boiler Data Sheet, there is space for up to four units. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Location The physical location of the boiler. Rating BTU/Hour Boilers are rated in terms of how many BTU/Hour they can provide under normal operating conditions. This information may be found in the submittal data or on the boiler data plate. Manufacturer The manufacturer of the boiler. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Steam Pressure PSI The steam pressure in Pounds per Square Inch. Control Setting What is this? Water Exchanger Data Data for the testing of water-to-water heat exchangers is located on this sheet. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Location The physical location of the boiler. Service The service for which the heat exchanger is used. Examples might be ‘Domestic Hot Water (DHW)’, ‘Hydronic Heat’, etc. Manufacturer The manufacturer of the boiler. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Primary Water Entering Temperature Leaving Temperature This is the water from which heat is to be extracted. The entering temperature of the primary water to the heat exchanger. The leaving temperature of the primary water to the heat exchanger. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the primary water to the heat exchanger. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. Flow GPM The volume of primary water flow through the heat exchanger in Gallons Per Minute. MBH The amount of heat rejected by the primary water flow in Millions of BTU per Hour. This is a calculated quantity. Control Setting What is this? Secondary Water This is the water to which heat is to be added. Entering Temperature Leaving Temperature The entering temperature of the secondary water to the heat exchanger. The leaving temperature of the secondary water to the heat exchanger. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the secondary water to the heat exchanger. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. Flow GPM The volume of secondary water flow through the heat exchanger in Gallons Per Minute. MBH The amount of heat gained by the secondary water flow in Millions of BTU per Hour. This is a calculated quantity. Control Setting What is this? Steam Heat Exchanger Data This data sheet is used to record test data for steam-to-water heat exchanger testing. Unit Number The individual unit number as specified on the drawings or in the mechanical schedule. Location The physical location of the boiler. Service The service for which the heat exchanger is used. Examples might be ‘Domestic Hot Water (DHW)’, ‘Hydronic Heat’, etc. Manufacturer The manufacturer of the boiler. Model Number The manufacturer’s model number for the unit. Serial Number The manufacturer’s unique serial number for the unit. The following cells have both Design and Actual fields. The Design field contains information supplied by the engineer or manufacturer and is usually found in the submittal information or in the mechanical schedules. The Actual field contains data that is measured in the field. Steam Pressure PSI The pressure of the entering steam in Pounds per Square Inch. Secondary Hot Water Entering Temperature The temperature of the water entering the heat exchanger. Leaving Temperature The temperature of the water leaving the heat exchanger. Pressure Drop Ft. The difference in pressure between the inlet and outlet of the secondary water to the heat exchanger. If readings are taken in PSI (Pounds per Square Inch) then the difference will have to be multiplied by 2.31 to obtain the differential in feet. Flow GPM The volume of secondary water flow through the heat exchanger in Gallons Per Minute. MBH The amount of heat gained by the secondary water flow in Millions of BTU per Hour. This is a calculated quantity. Control Setting What is this?