Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
873997698 Version 1.1 December 5, 2000 Data Dictionary for Electric System Security Data Introduction The data and terms described here are intended as a definition and clarification of the electric system security data listed in Appendix 4B-A of NERC Policy 4B, System Coordination – Operational Security Information. Each term is defined and its current or expected method of exchange is specified. A number of additional security data types that would be useful to security coordinators and control areas are also identified, although they have not been defined. Issues and Limitations 1. Some systems are incapable of sending derived data, or using derived data from other systems. 2. It is assumed that Ampere measurements are used only for thermal limits calculations, and therefore, only an absolute value is required. 3. In some cases, MVAR Gross Output is measured rather than MVAR Net Output. Either value is usable provided the actual data type is known by the receiver. 4. There are a number of data types in existence today that did not exist when the original data types were defined (e.g. retail items). These are not included in this data dictionary. 5. The only reference in NERC documentation to the direction that is to be assigned to negative and positive flows is in the Area Interchange Error Survey Training Document. This document specifies that net power into a control area is to be entered into the survey as a negative number, and net power out of a control area is to be entered as a positive number; no other reference to sign and direction has been found in NERC documents. This practice has not been adopted for normal operations by all security coordinators and control areas. As no industry standard for direction exists, the following convention is adopted for data transferred over the ISN: flow out of a metering point is positive, and flow into a metering point is negative. Specific meanings for the power system elements lines, generators, and loads are as follows: Flow out of a company over a tie line is positive. Flow out of a generating unit into a station is positive. Flow out of a load station is positive. 6. The ICCP standard does not discuss the scaling of analog quantities. In order to address this deficiency, the ISN Data Point Definition – Analog and Status Value Format document specifies that the source control area must define the ax + b scaling parameters required to convert the units and sign of each data point into the units and direction as specified above. It is the responsibility of the entity receiving the data to apply the scaling parameters to the data value received. 7. There is no standard way of determining exactly what is being measured. (i.e. there is no standard naming convention across all control areas and security coordinators.) Additional Data Types to be Considered The data types that are currently listed in Appendix 4B-A of NERC Policy 4B are defined in the sections below. This section lists additional data types that may be considered for exchange over NERCnet in the future in order to support the following information requirements: 1. Real-time information so that security coordinators and control areas have the information they need to assess the present state of the power system and to take appropriate actions to ensure its reliability. 2. Operational planning information so security coordinators can sufficiently assess expected operation and can coordinate plans to maintain a reliable state. Security coordinators would want this data for up to a week into the future; others may need to cover a longer period. 3. Other information. This is longer-term data similar to operational planning information and would include items that change the bulk power system. 1 873997698 Version 1.1 December 5, 2000 As a minimum, the following additional data types are needed to support these information requirements: 1. MVar loading. 2. Instantaneous interchange total and limits for all lines contributing to a flow gate, not just by individual line. 3. Current total interchange schedules with each control area. 4. All real-time operating security limits being used that are applicable to the bulk system and of interest to other control areas and security coordinators, not just special limits. 5. Forecast of operating reserve at peak and time of peak for next 7 days (only current and next day given below). 6. Forecast peak demand for next 7 days (only current and next day given below). 7. Modified equipment being returned to service, including description of its operating characteristics (i.e. nameplate ratings, location of connection, etc). (Only new facilities given below.) 8. Modified special protection systems (only new special protection systems given below). 9. All types of security alerts. Transmission Data Status Description Status of the switching devices (breakers, switches, disconnects) at each end of a transmission line. Possible values are Open, Closed, and Between. Derived status of lines, line segments, transformers, capacitors, and reactors, subject to the derived status limitation noted above. Possible values are Inservice, Out-of-service, and Between. The meaning of In-service and Out-of service for lines and line segments is as agreed between the parties exchanging this data. Exchange Mechanism ISN (ICCP) MW Loading Description Instantaneous real power flow on the transmission line. Direction indicated by positive and negative values is determined by the location of the metering point. Flow is positive out of a metering point into the line. Exchange Mechanism ISN (ICCP) Ampere Loading Description Instantaneous current flow at a defined location on the transmission line Exchange Mechanism ISN (ICCP) MVA Capability Description MVA limit for transmission devices. This may be either a static or dynamic limit. Exchange Mechanism ISN (ICCP) 2 873997698 Version 1.1 December 5, 2000 Transformer Tap Setting Description Predefined, fixed positions on one or both sides of a transformer. Each Tap position represents a specific voltage value, (i.e. changing a Tap Position changes the voltage.) There is no standard numbering scheme for the tap position. For example, some utilities number beginning at 0, others at 1. Other utilities refer to the nominal position as position 0, with positive integers for positions above nominal, and negative integers for positions below nominal. Still other utilities use turns ratio and not position notations. Exchange Mechanism ISN (ICCP) Transformer Phase Angle Setting Description Represents the Phase Angle between the current and voltage. (i.e. changing the Phase Angle changes the power.) The angle settings can typically vary between -90 and +90. The unit of measurement is Degrees. Exchange Mechanism ISN (ICCP) Key Voltage Description Instantaneous voltage measurement at a defined location on the transmission network. Unit of measurement is kV. PerUnit, 100Base, 120Base, etc. voltages must be converted to simple kV readings by the receiver. Exchange Mechanism ISN (ICCP) Generator Data Status Description Status of the generator as telemetered, or as derived from the status of the breaker associated with the generator unit. Possible values are In-service, Out-of-service and Between, or On, Off and Between. Some utilities have additional statuses such as Dispatchable, On AGC, Off AGC, and Unavailable. These additional statuses require the use of the ICCP Discrete Point Type. Since no standard exists for using this data type for status information, the meanings of the values are determined by agreement between the parties exchanging the information. Exchange Mechanism ISN (ICCP) MW Capability Description Limit on the gross or net MW output of a generator unit. This value may be either a static or dynamic limit. The direction indicated by positive is out of the generator into the station. Exchange Mechanism ISN (ICCP) 3 873997698 Version 1.1 December 5, 2000 MVAR Capability Description High or low limit on the gross or net MVAR output of a generator unit at the current MW output. This value may be either a static or dynamic limit. The direction indicated by positive is out of the generator into the station. Exchange Mechanism ISN (ICCP) MW Net Output Description Instantaneous measurement of the net real output power from the generator. The direction indicated by positive is out of the generator into the station. Exchange Mechanism ISN (ICCP) MVAR Net Output Description Instantaneous measurement of the net imaginary output power from the generator. The direction indicated by positive is out of the generator into the station. Exchange Mechanism ISN (ICCP) Status of Automatic Voltage Control Facilities Description Instantaneous status of automatic voltage regulators, and if they exist, the statuses of fast acting exciters and stabilizers. Possible values are In-service, Out-of-service, and Between, or On, Off, and Between. Exchange Mechanism ISN (ICCP) Operating Reserve MW Reserve Available Within Ten Minutes Description The amount of additional power that can be made available to the system within 10 minutes, as defined in Policy 1 of the NERC Operating Manual. Exchange Mechanism ISN (ICCP) Control Area Demand Instantaneous Control Area Demand Description Instantaneous reading of the primary demand for the control area. The unit of measurement is MW. Exchange Mechanism ISN (ICCP) 4 873997698 Version 1.1 December 5, 2000 Interchange Instantaneous Actual Interchange With Each Control Area Description Instantaneous reading of the MW flow between control areas. Direction indicated by positive is out of the source control area. Exchange Mechanism ISN (ICCP) Current Interchange Schedules With Each Control Area By Individual Interchange Transaction Description Current scheduled MW flows between control areas, and may include interchange identifiers and reserve responsibilities. Exchange Mechanism E-Tagging and IDC. Interchange Schedules For the Next 24 Hours Description Interchange schedules with each control area by individual interchange transaction for the period encompassing the next hour to 24 hours into the future. Exchange Mechanism E-Tagging and IDC. Area Control Error and Frequency Instantaneous Area Control Error Description Instantaneous measurement of the area control error. Unit of measurement is MW. Value may be positive or negative. Exchange Mechanism ISN (ICCP) Clock Hour Area Control Error Description Instantaneous Area Control Error averaged since the start of the current hour. This value may be positive or negative. Unit of measurement is MW. Exchange Mechanism ISN (ICCP) (future) System Frequency At One or More Locations in the Control Area Description Instantaneous reading of the actual frequency in Hz. This is not the deviation from a value (nominally 60 Hz). Exchange Mechanism ISN (ICCP) 5 873997698 Version 1.1 December 5, 2000 Other Operating Information Special Operating Security Limits in Effect Description Notification of special operating security limits in effect. Exchange Mechanism SCIS in the past. Slowly migrating from SCIS to SDX. Forecast of Operating Reserve at Peak, and Time of Peak for Current Day and Next Day Description Estimate of the operating reserve at the time of peak demand. Unit of measurement is MW. The time is the local clock time, with time zone specified, for the peak demand. Exchange Mechanism SDX Forecast Peak Demand for Current Day and Next Day Description Estimate of the peak demand for the day. Unit of measurement is MW. Exchange Mechanism SDX, SCIS Forecast Changes in Equipment Status Description Notification of expected changes in availability of equipment, or special protection schemes, such as equipment being placed into service or taken out of service for periods of time exceeding one hour (negotiable), such as for maintenance. Exchange Mechanism SDX, SCIS New Facilities in Place Description Notification of new equipment being placed into service Exchange Mechanism SCIS, SDX New or Degraded Special Protection Systems Description Notification of changes to the status of special protection schemes and systems. Exchange Mechanism SCIS, SDX 6 873997698 Version 1.1 December 5, 2000 Emergency Operating Procedures in Effect Description Notification of Emergency conditions and procedures and expected duration. This may also include Transmission Loading Relief states, Capacity Deficiency Alerts, and relevant information such as action taken or planned. Exchange Mechanism SDX, SCIS, IDC Severe Weather, Fire, or Earthquake Description Notification of severe weather conditions such as hurricanes, tornadoes, and severe thunderstorms. May also include tornado and severe weather warnings and watches, and solar magnetic disturbance alerts. Also includes notification of earthquakes, and fires that affect or could potentially affect the power system operation. Exchange Mechanism SDX, SCIS Multi-site Sabotage Description Notification of cases of sabotage to power system equipment at multiple sites. Exchange Mechanism SDX, SCIS 7