Download Sensitivity measurements

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rectifier wikipedia , lookup

Fault tolerance wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Three-phase electric power wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electrical substation wikipedia , lookup

Buck converter wikipedia , lookup

Triode wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power electronics wikipedia , lookup

Public address system wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Rectiverter wikipedia , lookup

Voltage regulator wikipedia , lookup

Islanding wikipedia , lookup

Distribution management system wikipedia , lookup

Surge protector wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Conditional Based Maintenance with Online Partial Discharge Measurements of HV
and MV Switchgear Systems
R.G.A. Zoetmulder, S. Meijer and J.J. Smit
Presented by
J.J. Smit
Question number 8
Introduction and Goal
Insulation test:
1: Detection
2: Defect identification
3: Defect localization
4: Risk assessment
Goal:
To apply the UHF measuring technique
used for High Voltage Switchgear (HV GIS) also for :
- Medium Voltage Gas Insulated Systems (MV-GIS)
- Medium Voltage Air Insulated Systems (MV-AIS)
- Medium Voltage Oil Insulated Systems (MV-OIS)
The measuring system
* Hard-ware
• Broadband detection >
UHF (till several GHz)
• With this method noises
can be suppressed by
measuring at a frequency
band with a low noise-level
Components:
1 a: Internal UHF coupler
1 b: external UHF coupler
2 : Pre-amplifier
3 : Spectrum analyzer
4 : Computer
10 kV Air Insulated Switchgear system-1
- 10 kV Air Insulated
- Measuring locations are
small inspection windows
- Vacuum Circuit-Breaker
- UHF signals can propagate
through these inspection
windows and can than be
detected
Front-side
Back-side
Begin stadium
(less affected)
Advanced stadium
(More affected)
Surface discharge at one of the phase connectors of the circuit-breaker
10 kV Air Insulated Switchgear system-2
Conclusions
Measurements with the external UHF coupler are applicable to medium
voltage switchgear installations, e.g. air insulated switchgear, as well as
to HV switchgear systems.
Using advanced PD analysis techniques distinction can be made
between the different patterns detected by the external UHF coupler.
UHF PD measurements can contribute to CBM procedures.
With UHF PD measurements one can also determine the position of
system design errors, which then can be corrected.