Download Self-test GFCI tamper resistant hospital grade spec sheet

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Switched-mode power supply wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Ground (electricity) wikipedia , lookup

Opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Earthing system wikipedia , lookup

Wire wrap wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Residual-current device wikipedia , lookup

National Electrical Code wikipedia , lookup

Transcript
Technical Data
Effective June 2015
Arrow Hart hospital grade tamper
resistant self-test GFCI receptacles
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Description
2-pole, 3-wire grounding
15A, 125V/AC; 20A, 125V/AC
NEMA 5-15, 5-20
TAMPER
RESISTANT
Design features
SGFH15
TAMPER
RESISTANT
TRSGFH20
•
Performs periodic self-tests to ensure integrity of GFCI protection.
•
Meets and exceeds 10 kA short circuit testing and Underwriters
Laboratories (UL) UL943 safety standards
•
Visual trip indicator light gives quick notification of a tripped or
“end of life” condition
•
Automatic grounding system eliminates need for bonding jumper
in grounded metal enclosure, provides redundant measure of
ground continuity where jumper is used
•
Ground termination with back wire clamp provides secure wiring
and reduces installation time
•
Tamper resistant shutters help prevent foreign objects from
being inserted
•
Line side terminals are backed out and staked for fast installation
•
Horizontal test/reset button alignment provides larger
unobstructed area
•
Test and reset buttons are color matched to provide superior
aesthetics
•
Tapered back wire openings handle multiple wire sizes and types
for applications up to #10 AWG solid or stranded wire
•
When downstream receptacles are wired from load side, a
20A feed-through rating offers full protection
•
Line-load miswiring protection: GFCIs will not provide power
downstream when wired incorrectly
•
Tri-combo head terminal and mounting screws
•
Hospital grade models UL Listed, fully compliant with all latest
UL943 Class A GFCI and UL498 hospital grade requirements
•
Tamper resistant models comply with 2014 NEC Article 406.12 for
all dwelling units
•
Lock-out functionality prevents miswired line-load connections and
GFCI circuitry damage
•
Each device carries a 20A feed-through rating
•
Longer, wider “bridged” strap provides 40% more contact area
with wallboard, virtually eliminating floating installations
•
Matching standard size thermoplastic wallplate included
Compliances, specifications and availability are subject to change without notice.
Technical Data
Arrow Hart hospital grade tamper
resistant self-test GFCI receptacles
Effective June 2015
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Table 1. Hospital grade self-test GFCIs
Catalog no.
Table 2. Hospital grade self-test tamper resistant GFCIs
Rating
A
V/AC
Description
NEMA
Color suffix
B, GY, LA,
RD, V, W
B, GY, LA,
RD, V, W
B, GY, LA,
RD, V, W
B, GY, LA,
RD, V, W
SGFH15___
Hospital GFCI, back & side wire 15
125
5-15R
SGFH15F___
Hospital GFCI, back & side wire 15
125
5-15R
SGFH20___
Hospital GFCI, back & side wire 20
125
5-20R
SGFH20F___
Hospital GFCI, back & side wire 20
125
5-20R
Catalog no.
Description
TRSGFH15___ Tamper resistant hospital GFCI,
back & side wire
TRSGFH15F___ Tamper resistant hospital GFCI,
back & side wire
TRSGFH20___ Tamper resistant hospital GFCI,
back & side wire
TRSGFH20F___ Tamper resistant hospital GFCI,
back & side wire
A
Rating
V/AC
NEMA
Color suffix
15
125
5-15R
15
125
5-15R
20
125
5-20R
20
125
5-20R
B, GY, LA,
RD, V, W
B, GY, LA,
RD, V, W
B, GY, LA,
RD, V, W
B, GY, LA,
RD, V, W
Table 3. GFCI status indicator
Test indicator Test indicator
RED LED
AMBER LED Diagnosis
OFF
OFF
OFF
ON
Blinking
OFF
Blinking
ON
Color suffix
Manually depress TEST button to trip device. Amber light should come ON
• If Amber light does not come ON, check if there is power to the branch
• If Amber light does come ON, manually depress the RESET button to restore power to the device
• If GFCI does not reset, replace GFCI
• If GFCI does reset, device is functioning properly
Device is in tripped state
Manually depress the RESET button to restore power to the device
• If GFCI does not reset, replace GFCI
Device’s “end of life” indication Manually depress TEST button to trip device. Amber light should come ON
OR device is in reset state
• If Amber light does not come ON, check if there is power to the branch
• If Amber light does come ON, manually depress the RESET button to restore power to the device
• If it does not reset, and/or the blinking continues, replace GFCI
Device’s “end of life” indication Manually depress the RESET button to restore power to the device
OR device is in tripped state
• If it does not reset, and/or the blinking continues, replace GFCI
Device is functioning properly
OR branch circuit may
have no power
Applications
GFCI receptacles are designed with the safety of the user in mind. In commercial and industrial areas like public bathrooms, breakrooms
and food service areas, the NEC requires GFCI receptacles. Arrow Hart self-test GFCI receptacles are UL Listed and fully compliant
with all of the latest UL943 Class A GFCI and UL498 requirements. The self-test GFCIs conduct an automatic test periodically to ensure
GFCI protection. The device will trip and will not reset if GFCI protection is not available. Additionally, GFCIs incorporate a safety lock-out
functionality to protect against mis-wired line-load connections and GFCI circuitry damage.
Table 4. Specifications
TAMPER
RESISTANT
Catalog no.
SGFH__ and SGFH__F__series
TRSGFH__ and TRSGFH__F__ series
Device type
Wiring type
Testing & code compliance
Hospital grade duplex GFCI 15A & 20A
Back & side wire
• cULus Listed to UL 498 and UL 943, file no. E60120
• Meets all UL 943 (GFCI), UL 498 (receptacles), UL 498
Hospital grade and applicable CSA requirements
• NOM certified
Flammability: Meets UL 94 requirements; V2 rated
Temperature rating: -35ºC to 66ºC (-31ºF to 150.8ºF)
Dielectric voltage: Withstands 2000V per UL 498
Current interrupting: Yes, at full-rated current
Temperature rise: Max. 30ºC (86°F) after 100 cycles of overload
@ 150% of rated current (DC)
Trip time: 0.025 seconds (Class A)
Frequency: 60 Hz; Voltage: 125V; Amperage: 15A/20A
20A feed-through
Short circuit testing: Meets and exceeds 10 kA
Maximum interrupting capacity: 20 Amps
Terminal accommodation: #14 - 10 AWG
Voltage ratings: Permanently marked on device
Hospital grade tamper resistant duplex GFCI, 15A & 20A
Back & side wire
• cULus Listed to UL 498 and UL 943, file no. E60120
• Meets all UL 943 (GFCI), UL 498 (receptacles), UL 498
Hospital grade and applicable CSA requirements
• NOM certified
Flammability: Meets UL 94 requirements; V2 rated
Temperature rating: -35ºC to 66ºC (-31ºF to 150.8ºF)
Dielectric voltage: Withstands 2000V per UL 498
Current interrupting: Yes, at full-rated current
Temperature rise: Max. 30ºC (86°F) after 100 cycles of overload
@ 150% of rated current (DC)
Trip time: 0.025 seconds (Class A)
Frequency: 60 Hz; Voltage: 125V; Amperage: 15A/20A 20A
20A feed-through
Short circuit testing: Meets and exceeds 10 kA
Maximum interrupting capacity: 20 Amps
Terminal accommodation: #14 - 10 AWG
Voltage ratings: Permanently marked on device
Environmental specifications
Electrical specifications
Mechanical specifications
2
EATON www.arrowhart.com
Compliances, specifications and availability are subject to change without notice.
Technical Data
Arrow Hart hospital grade tamper
resistant self-test GFCI receptacles
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Effective June 2015
Table 6. Materials
Catalog no.
SGFH__ and SGFH__F__series
TRSGFH__ and TRSGFH__F__ series
Top housing
Thermoplastic, nylon
Thermoplastic, nylon
Bottom housing
Strap
Line contacts
Polycarbonate
0.047” thick steel, zinc plated
0.030” thick brass
#8-32 steel, brass plated; neutral screw nickel plated,
ground screw green
0.070” thick steel
Polycarbonate
0.047” thick steel, zinc plated
0.030” thick brass
#8-32 steel, brass plated; neutral screw nickel plated,
ground screw green
0.070” thick steel
Terminal & ground screws
Terminal clamps
Table 5. Color ordering information
For ordering devices, include Cat. no. followed by the color code: B (Brown), BK (Black),
GY (Gray), LA (Light Almond), RD (Red), V (Ivory), W (White)
B
BK
GY
LA
RD
V
W
Brown
Black
Gray
Lt. Almond
Red
Ivory
White
Wiring diagrams
Figure 1. One cable (2 or 3 wires) entering the box
Compliances, specifications and availability are subject to change without notice.
Figure 2. Two cables (4 or 6 wires) entering the box
EATON www.arrowhart.com
3
Technical Data
Arrow Hart hospital grade tamper
resistant self-test GFCI receptacles
Effective June 2015
Project Name:
Prepared By:
Project Number:
Date:
Catalog Number:
Type:
Product dimensions
1.68”
(42.7mm)
1.68”
(42.7mm)
1.30”
(33mm)
1.30”
(33mm)
4.20”
(106.6mm)
4.20”
(106.6mm)
3.28”
(83.3mm)
3.28”
(83.3mm)
1.26”
(32mm)
1.26”
(32mm)
Figure 3. TRSGFH15 Line art with dimensions
Figure 4. TRSGFH20 Line art with dimensions
Certifications & compliances
Catalog no.
426
SGFH15
SGFH15F
TRSGFH15
TRSGFH15F
SGFH20
SGFH20F
TRSGFH20
TRSGFH20F
KEY:
cULus
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
426
NOM
Arrowlink
Build-To-Spec
Build-To-Spec Customizable Devices
Compliances, specifications and availability are subject to change without notice.
Electrical Sector
203 Cooper Circle
Peachtree City, GA 30269
United States
Eaton.com
Cooperwiringdevices.com
Electrical Sector
Canada Operations
5925 McLaughlin Road
Mississauga, Ontario, L5R 1B8
Canada
EatonCanada.ca
Cooperwiringdevices.com
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. TD610006EN
June 2015
Electrical Sector
Mexico Operations
Carr. Tlalnepantla Cuautitlán Km 17.8 s/n
Col. Villa Jardín esq.
Cerrada 8 de Mayo
Cuautitlán, México CP 54800
México
Eaton.mx
Cooperwiringdevices.com
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.