Download 280-76

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Portable appliance testing wikipedia , lookup

Electronic musical instrument wikipedia , lookup

Peak programme meter wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Electronic engineering wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Automation wikipedia , lookup

Fire-control system wikipedia , lookup

Distribution management system wikipedia , lookup

Control theory wikipedia , lookup

Wassim Michael Haddad wikipedia , lookup

Distributed control system wikipedia , lookup

Hendrik Wade Bode wikipedia , lookup

Metadyne wikipedia , lookup

Control system wikipedia , lookup

Resilient control systems wikipedia , lookup

Transcript
Technical Data 280-76
Effective July 2014
Supersedes August 1996
MET electronic recloser control tester
Description
The MET electronic recloser control tester from
Eaton's Cooper Power Systems is designed
specifically for testing Type ME Form 2, Form
3, Form 3A, Form 4A, Form 4C, Form 5, Types
FX, FXA, and FXB controls. The tester has the
capability to check the following:
•
Battery voltage (load and no load)
•
Battery charge and discharge rates
•
Minimum-trip current (phase- and ground-trip)
•
Operating sequence
•
Control response time (phase- and ground trip)
•
Reclosing time
•
Reset time
•
Electrical operation of recloser
•
Functioning of various accessories through
simulation of the conditions under which they
operate
The self-contained unit, compactly packaged in a
handy carrying case with a detachable front cover,
includes the following:
•
Multi-scale dc meter with associated switches
for checking the battery and battery-charging
circuits
•
Multi-scale ac meter and adjustable current
source to duplicate the output of the sensing
bushing current transformers of the recloser
•
Solid-state digital clock to measure time of the
test
•
Simulator circuit to simulate recloser operation
and duplicate recloser mechanism response
times to trip and close signals
•
Switches and associated circuitry for performing
the various tests
•
Cables for connecting the control, recloser, and
control battery to the tester
•
Internal buzzer sounds if a mis-match between
grounds on the ME control and MET tester
exists
Technical Data 280-76
MET electronic recloser control tester
Effective July 2014
Ordering information
Table 1. Specifications
Input
120 Vac; 60 Hz; single-phase (fused for 2 amps)
Output
0–3000 mA continuously adjustable from front panel
of tester
Instrumentation
The tester is supplied as a complete unit and includes all necessary
interconnecting cables. To order, specify tester by description and
catalog number.
MET electronic recloser control tester: Catalog No. KMET
DC meter
Edgewise panel meter with 2-in. horizontal scale; accuracy ± 5% of full scale
Recloser simulator
Panelswitched
ranges
0–4/40 mA; 0–40 volts
AC meter*
Edgewise panel meter with 2-in. horizontal scale; accuracy ± 5% of full scale
Panel-switched
ranges
0–30/100/300/1000/3000 mA
Timer
Digital clock timer 0–999.999 seconds in 0.001-second increments;
with manual reset
No external equipment or accessories are required when using
this tester. The tester can check the operation of the electronic
control and the recloser (provided reclosing power is available at
the recloser). However, the control cannot operate the recloser
through the tester. Recloser operation is simulated with red and
green indicating lights on the tester panel. A built-in time delay is
also provided to simulate the response time of the solenoid-closing
recloser mechanisms to a trip signal (2-½ cycles) and a closing signal
(30 cycles) from the control.
* Jacks are provided on the panel for connecting external ammeter if different ranges, greater
accuracy, or calibration of panel meter is required.
Table 2. Interconnecting Cables*
15-ft. cable for connecting electronic control to tester.
15-ft. extender cable for connecting end of recloser
cable to tester.
15-ft. cable for directly connecting control battery terminals to tester.
* Connector terminations on all cables are polarized to assure proper interconnection.
Carrying case
The unit is packaged in a sturdy Formica®-covered carrying case
with removable front cover and provision for storing interconnecting
cables, spare fuses, and bulbs.
Dimensions (overall)
9-½ in. high; 21 in. wide; 13-¼ in. deep.
Weight (approximate)
Net: 33 lbs; shipping: 37 lbs.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Power Systems Business
2300 Badger Drive
Waukesha, WI 53188
United States
Cooperpower.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. 280-76
Eaton and Cooper Power Systems are valuable
trademarks of Eaton in the U.S. and other
countries. You are not permitted to use the
these trademarks without the prior written
consent of Eaton.
Formica® is a registered trademark of The
Diller Corporation.
For Eaton's Cooper Power
Systems MET recloser control
tester product information call
1-877-277-4636 or visit: www.