Download B320-97036

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Ground (electricity) wikipedia , lookup

Electronic engineering wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric power system wikipedia , lookup

Islanding wikipedia , lookup

Power engineering wikipedia , lookup

Electrical substation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Mains electricity wikipedia , lookup

Distribution management system wikipedia , lookup

Alternating current wikipedia , lookup

Power over Ethernet wikipedia , lookup

Last mile wikipedia , lookup

Earthing system wikipedia , lookup

Rectiverter wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Fault tolerance wikipedia , lookup

Transcript
Locate Faulted Sections of Overhead Cable
Systems Efficiently using S.T.A.R.™ Electrostatic
Reset Type Faulted Circuit Indicators
Cooper Power Systems manufactures a line of S.T.A.R. — Superior, Tough And
Reliable — faulted circuit indicators to fit your application.
S.T.A.R. Electrostatic Reset Type Faulted Circuit Indicator
Cooper Power Systems S.T.A.R.™ Electrostatic Reset (ER)
type faulted circuit indicators (FCI) can be used on bare overhead cable and unshielded insulated cable, such as tree wire.
They are powered from the voltage gradient between the line
and the ground plane. Load levels do not affect the reset circuit. The unit automatically resets to the normal position when
circuit voltage is restored.
The S.T.A.R. Electrostatic Reset type FCI is designed with
a clamping mechanism that’s “a snap” to connect to an
energized system for a wide range of cable diameters.
Installation is quick and easy, with a single clampstick.
The unique FISHEYE™ display, with a highly reflective orange
target, provides enhanced 180 degree visual indication. The
display is black under normal conditions.
To select trip rating, simply choose the “HI” trip rating for
applications close in to the substation where available fault
currents tend to be greater than 800 A, and select a “LO” trip
rating for areas further out on the system where available fault
currents tend to be less than 800 A. This approach to trip
selection means that one indicator fits all cable diameters from
0.25” through 2.0”.
With this simplified approach to rating selection:
■ Ordering is easier and faster.
■ Inventory is reduced, eliminating the need to stock multiple
designs.
■ Pre-installation load surveys are not needed.
■ FCI changeouts are not necessary as systems grow.
■ Misapplication due to trip selection errors is eliminated.
One Cooper | www.cooperpower.com | Online
One Cooper | www.cooperpower.com | Online
S.T.A.R. electrostatic reset type faulted circuit indicator
features include:
■ Inrush Restraint: Eliminates false tripping due to recloser
operations
■ Low Pass Filter: Prevents tripping on capacitive cable
discharge and high frequency transients
■ Temperature Compensation Circuitry: Assures accurate,
reliable performance over a wide temperature range
■ Reliable Open Core CT Design: Eliminates tripping due to
adjacent magnetic fields
■ Quick Response Time: Coordinates with current-limiting
fuses
■ Tough, Durable Construction: Corrosion-proof, damageresistant, robust mechanical display for long life
■ Exceeds IEEE Std 495™-1986 standard
■ Quick and Easy Installation: A single clampstick is
required
Optional features:
■ LED Display: LED will blink for up to four (4) hours
providing high intensity output of fault indication from longer
distances than FISHEYE display alone
S.T.A.R.
Electrostatic Reset
Faulted Circuit Indicator
Description
Characteristics and Ordering Information
Ratings and Characteristics
Power Requirements
Minimum 6.9 kV L-G
Reset Time
8 Minutes Maximum at 6.9 kV
Trip Current
Factory Preset (High and Low)
Trip Accuracy
+/- 10%
Trip Response Speed
Response Curve, see Catalog Section 320-60
Fault Withstand Capability
25 kA for 10 Cycles per IEEE Std 495™-1986 standard
Temperature Range
-40 °C to + 85 °C
Materials
Corrosion-resistant and submersible per IEEE Std 495™-1986 standard
Weight
13.6 ounces (0.39 kg)
Cable Size
0.25” (6.4 mm) through 2.0” (51 mm)
FRONT VIEW
SIDE VIEW
4.57”
(116 mm)
6.65”
(168.8 mm)
3.65”
(93 mm)
Standard
Options
Digits: 1 2 3
S E H
4
I
Ordering
Information
5
6
7
Options
S.T.A.R. FCI Line
Digits
FCI Type
5
Trip Rating
Digit
2
Type
E
Electrostatic
Reset
L
Digits
3
4
Trip Rating
L
O
Low
H
I
High
6
7
Description
LED Light Indication
(max 4-hour blinking)
Notes:
1. The S.T.A.R. FCI catalog number may vary in length from 4 digits to 7 digits.
2. The standard S.T.A.R. FCI catalog number may be truncated after entering digits 1-4. options may be selected be
adding the appropriate design code to digits 5, 6 and/or 7.
Contact your Cooper Power Systems Representative for more information or refer to Catalog Section 320-60.
Cooper Power Systems
2300 Badger Drive
Waukesha, WI 53188
P: 877.CPS.INFO