Download Implementing Emergency Circuits in Greengate Centralized Lighting Control Panels

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Switched-mode power supply wikipedia , lookup

Distributed control system wikipedia , lookup

War of the currents wikipedia , lookup

Electric power system wikipedia , lookup

Resilient control systems wikipedia , lookup

Mains electricity wikipedia , lookup

Electrification wikipedia , lookup

Alternating current wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switch wikipedia , lookup

Distribution management system wikipedia , lookup

Control system wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Light switch wikipedia , lookup

Relay wikipedia , lookup

Protective relay wikipedia , lookup

Transcript
Application
Note
Implementing Emergency Circuits in
Greengate Centralized Lighting Control Panels
Overview
North America Headquarters
203 Cooper Circle
Peachtree City, GA 30269
P: 800-553-3879
F: 800-954-7016
Service & Support Center
6 Green Tree Drive
South Burlington, VT 05403
P: 800-553-3879
F: 800-954-7016
International Headquarters
20 Greenhill Crescent
Watford Business Park
Watford, Herts, WD18 8XG. UK
P: +44 (0)1923 495495
F: +44 (0)1923 228796
Many lighting control applications require support for emergency lighting of some type. These
emergency lighting circuits typically provide minimum illumination levels for egress and safety as
required by NFPA 101 Life Safety Code or other local building codes and standards. Designers
may meet these requirements with dedicated emergency lighting fixtures. These fixtures would be
fed directly from emergency branch circuits or from internal power sources (rechargeable battery
packs are typical) when grid power has failed. A disadvantage to these approaches is that these
dedicated luminaires often go largely unused as they provide lighting only when normal power has
failed. An alternative is to utilize the same fixtures for both normal and emergency lighting needs.
Greengate lighting control panels for energy management from Cooper Controls have been designed to
accommodate this approach.
Technical Details
Greengate ControlKeeper and LiteKeeper 16, 32
and 48 circuit lighting control panels for centralized
applications have built-in provisions for initiating a
hardware override of all lighting loads in the event
of an emergency. In ControlKeeper systems the
relay cards communicate through a Relay Stack
Controller (RSC) to the panel logic board. The logic
board would normally command the relay cards to
switch lighting loads based on system programming
that may incorporate time schedules or responses
to system inputs such as switches or photosensors.
The panel override switch allows an operator to force all
relays to an on or off state
A LiteKeeper logic board commands its relays
through a Standard Override Card (SOC). The RSC
and SOC provide similar functionality in that they both possess the ability to override the state of all
relays independent of the system logic board. This override may be initiated by an operator via a three
position override switch. The switch allows the operator to command all relays to the off state (OFF),
the on state (ON) or to states determined by the logic board (AUTO).
If the on or off state is selected the relays will assume that state regardless of system programming. In
fact, on and off commands can be issued by an RSC or SOC even if no logic board is installed in the
system. This feature is often used during the construction phase to allow illumination of the job site
before the system is programmed.
The RSC and SOC also include dry contact inputs that can be used to force an override condition.
Forcing an override condition by providing a contact closure to the RSC or SOC is similar to creating
an override condition via the override switch. The significant
difference between these two override methods is that the dry
contact inputs take precedence over the override switch. If, for
example, the relays were forced on by a contact closure there
would be no method to turn those relays off short of removing
panel power.
Page 1 of 2
The Relay Interface Module is a UL924
listed accessory for Greengate lighting
control panels.
The Greengate Relay Interface Module (RIM) is a UL924
listed device that is designed to operate in conjunction with a
ControlKeeper or LiteKeeper panel to provide emergency lighting.
The RIM senses normal power and provides a contact closure to
the RSC or SOC when normal power is lost. This contact closure
forces all relays in the lighting control panel to an on state.
Upon restoration of normal power the RIM will remove the contact closure and the relays will assume
their proper state based on system programming. Relays states will correctly reflect any time
schedules or changes to system inputs that may have occurred during the override condition.
Application
Note
Relays feeding emergency lighting fixtures should be fed by emergency branch circuits that are
switched from normal to emergency power by an upstream UL1008 listed transfer switch. The lighting
control panel power transformer must also be fed from the emergency power source in order for the
relays to operate. If normal and emergency circuits are present in the same lighting control panel, they
should be separated by a high voltage barrier. Barriers are available to separate loads by individual
relay cards.
North America Headquarters
203 Cooper Circle
Peachtree City, GA 30269
P: 800-553-3879
F: 800-954-7016
Service & Support Center
6 Green Tree Drive
South Burlington, VT 05403
P: 800-553-3879
F: 800-954-7016
International Headquarters
20 Greenhill Crescent
Watford Business Park
Watford, Herts, WD18 8XG. UK
P: +44 (0)1923 495495
F: +44 (0)1923 228796
Typical emergency lighting application
The panel power transformer is located in the lower portion of the class 1 section of the lighting control
panel enclosure. In panels with mixed normal and emergency circuits, relays in the lower portion of the
enclosure should be allocated to emergency circuits to facilitate the use of barriers for separation.
Proper operation of the system can be verified by removing the normal power feed to the Relay Interface Module. This should force an on override condition as indicated by the green ON override indicator located next to the override switch and also by the closure of all relays in the lighting control panel.
An on override condition is indicated by illumination of the green
LED located adjacent to the override switch
Conclusion
Page 2 of 2
With a properly designed and configured lighting control system it is possible to utilize the same lighting
fixtures for both normal and emergency applications. Greengate lighting control panels for centralized
applications are designed to facilitate this approach when used in conjunction with the UL924 listed
Relay Interface Module accessory. High voltage barriers are available from Cooper Controls, which
may be employed to accommodate normal and emergency circuits within the same lighting control
panel enclosure.