Download Room Controller Network Node

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Switched-mode power supply wikipedia , lookup

Computer network wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Alternating current wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Mains electricity wikipedia , lookup

Voltage optimisation wikipedia , lookup

Buck converter wikipedia , lookup

Network analysis (electrical circuits) wikipedia , lookup

Opto-isolator wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
Greengate
Application Note
Room Controller – Network Node Upgrade
SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
●
Installation should be performed by a qualified electrician
●
Installation shall be in accordance with all applicable local and NEC codes
●
Turn the power off at circuit breakers before wiring
●
RC3DE models may contain circuits from more than one power source
●
Designed for indoor installation and use only
●
All new wiring must be fully verified before applying power
●
Servicing of equipment should be performed by qualified service personnel
SAVE THESE INSTRUCTIONS
System Overview
Normal Power
(Line In & Load Out)
SPRC-R-20-120
(20A Receptacle Control)
Line Voltage
to J-Box
Room Controller
(Above Entry Door)
Line Voltage
to Receptacles
(Low Voltage, Class 2)
Emergency Power
(Line In & Load Out)
RC3DE Model only
OCC-RJ45
0-10V Dimmer Wiring
(Dimming Models Only)
DSRC-FMOIR
(Multi-zone
Daylight Sensor)
(Any Greengate
Occupancy Sensor)
Wallstation
(Entry)
Wallstation
(Additional)
RS-485 to other Room Controllers
and ControlKeepers
Network Node Installation
Room Controller Firmware
1.
Insert Netork Node (Part# RCNN)
2.
Install Cover
3.
Secure cover in place with two screws
The Room Controller must be updated to the latest
firmware version for the Network Node to work. Contact
Eaton Lighting systems technical support for information on
updating Room Controller Firmware.
4.
Install electrical connectors
Room Controller Networking
This section applies to the RC3-PL-N, RC3D-PL-N and
RC3DE-PL-N Room Controller models.
3
Room Controller Network Node
The diagram below
calls out some of the various
Network Node
components of the network node.
2
RS-485 Connection
1
Terminating Jumper
Communication
Status LEDs
Reset Button
Address DIP Switch
Network Wiring Notes
The Room Controller network is designed to communicate
with other Room Controller and ControlKeeper network
panels using a lighting control RS-485 network for
communications. This allows the panels to share information
and to be programmed from a central location using the
Keeper Enterprise Software.
Please refer to Table 1 for information on recommended
network cables.
4
Acceptable
Network Wiring
Suggested Cable
Eaton CAT#
Standard RS485
Belden 9841 (Shield is not used)
GG9841
Plenum RS485
Belden 89841 (Shield is not used)
GG89841
Table 1. Network Wiring Recommendations
For best network performance, one of the suggested
cables should be used. If the specified cable is not
used and communications problems occur that require
troubleshooting assistance, additional charges for support
may be assessed.
2
www.eaton.com/lightingsystems
1.
All low voltage wiring is Class 2.
To network Room Controllers together:
2.
All low voltage wiring must enter the cabinet from the
low voltage section of the enclosure.
1.
Select end panels to establish the beginning and end of
the network
3.
All low voltage wiring must be run in separate conduit
from line voltage wiring.Test all network wiring for
shorts to AC ground before connecting to the Room
Controller.
2.
The end panels will have the network termination
jumpers installed and the panels in between will have
them removed.
4.
If using Belden 9841 or 89841, ensure shields are
taped back and not connected to any metal surfaces.
3.
Wire the panels together per the diagram below. For
clarity the network node is seen below.
5.
Panels and devices on the RS-485 lighting network
should be daisy-chained. Do not create a Star or
T-Tapped configuration.
End Panel
Jumper installed
Middle
Panel(s)
Jumper Removed
6.
Total network length should not exceed 4000 feet.
Network Wiring Detail
The diagram below illustrates the networking of the Room
Controllers. Pull the twisted pair wiring in conduit along the
planned route, making certain that it is separated from any
line voltage wiring.
End Panel
Jumper installed
Room Controller Network Topology
QuickConnect Coupler
(GGRC-COUPLER)
Adjustable Skylights
Adjustable Skylights
QuickConnect Cables
Sensors
Sensors
5
+
+
Alert
Mode
Time
Clock
Blue
Red
Black
4
Integration Controls
Slider
Station
Wallstations
+
-+
A/V
Mode
Demand
Response
Brown
3
OCC-RJ45
(Occupancy Coupler)
2
1
3
2
1
Not Used
4
Reset
Occ
Default 10%
Energy
Options
Occupancy
High End
Energy Options DIP Switch
Demand Response
Vac (default)
20%
40%
0-10V Dimming Outputs
+ + + Dimmer 2
Dimmer 1
Dimmer 3
+
-
Dimmer 2
+
-
Dimmer 1
-
+
0-10V Dimming
Half Lights
Full Lights
All Off
Blue - EM Line In
Dimmer 2
Dimmer 1
Dimmer 3
+
-
Dimmer 2
+
-
Adjustable Skylights
Adjustable Skylights
QuickConnect Cables
Sensors
5
-
Black
Brown
3
OCC-RJ45
(Occupancy Coupler)
2
1
Energy Options DIP Switch
1
20%
Occupancy
2
Not Used
3
4
Occ
Reset
Demand Response
Default 10%
Vac (default)
30%
40%
0-10V Dimming Outputs
+ + + Dimmer 3
Dimmer 2
Occupancy/
Vacancy Sensor
(OAWC-DT-120W)
Dimmer 1
+
0-10V Dimming
Blue
Red
4
Integration Controls
+
Dimmer 3
Dimmer 1
+
+
Status
Reset
0-10V Gain
Adjustment
Status
Low End
0-10V Dimming Outputs
+ + + Dimmer 3
Sensors
Wallstations
+
Time
Clock
0-10V Gain
Adjustment
4
Vac (default)
Receptacle
BMS/Out
Slider
Station
-
+
Alert
Mode
Energy
Options
Not Used
3
Occ
30%
40%
Green
A/V
Mode
Demand
Response
High End
Occupancy
2
Energy
Options
1
20%
Yellow - Load 1 Out
Red - Load 2 Out
Purple - Load 3 Out
Energy Options DIP Switch
Demand Response
Default 10%
Red
Black
Daylight sensor
(DSRC-FMOIR)
SPRC-R-20-120
20A Receptacle
Control
6
Low End
1
Occupancy/
Vacancy Sensor
(OAWC-DT-120W)
Blue - Load In
OCC-RJ45
(Occupancy Coupler)
2
Integration Controls
Black
Brown
3
White/Black - 120V N
White/Orange - 277V N
Blue
Red
4
Blue - EM Loads Out
+
Black - Line In
5
Integration Controls
+
Time
Clock
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Adjustable Skylights
QuickConnect Cables
Sensors
Wallstations
+
+
Alert
Mode
High End
Purple - Load 3 Out
Adjustable Skylights
Red - Load 2 Out
Blue - Load In
Receptacle
BMS/Out
Sensors
Slider
Station
-
A/V
Mode
Integration Controls
Yellow - Load 1 Out
White/Black - 120V N
White/Orange - 277V N
Black - Line In
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black
Green
Switchpack
White
Model: OCC-RJ45
Occupancy Sensor Coupler
Blue - EM Line In
Red
Demand
Response
Daylight sensor
(DSRC-FMOIR)
SPRC-R-20-120
20A Receptacle
Control
6
QuickConnect Coupler
(GGRC-COUPLER)
Model: OCC-RJ45
Occupancy Sensor Coupler
Blue - EM Loads Out
Switchpack
Slider Station
Wallstation
QuickConnect Coupler
(GGRC-COUPLER)
White
Occupancy/
Vacancy Sensor
(OAWC-DT-120W)
Status
Low End
30%
Dimmer 3
Daylight sensor
(DSRC-FMOIR)
SPRC-R-20-120
20A Receptacle
Control
6
0-10V Gain
Adjustment
Blue - EM Line In
Blue - EM Loads Out
The Ethernet Interface Module (EIM)
and Wireless Ethernet Interface
Module (WEIM) may be connected to
any Lighting Control Panel in the system
using the RS-232 cable included.
(Part #:52-018703-00)
Black
Green
Receptacle
BMS/Out
Integration Controls
Blue - Load In
Yellow - Load 1 Out
Black - Line In
White/Black - 120V N
White/Orange - 277V N
ControlKeeper
TouchScreen
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
120V Power
Receptacle Required
Switchpack
White
Red
Model: OCC-RJ45
Occupancy Sensor Coupler
Red - Load 2 Out
Purple - Load 3 Out
EIM
-
Dimmer 2
+
-
Dimmer 1
+
-
0-10V Dimming
Half Lights
Half Lights
Full Lights
Full Lights
All Off
Wallstation
All Off
Slider Station
Wallstation
Slider Station
www.eaton.com/lightingsystems
3
Network Address Switch Detail
After networking each panel an address will have to be
assigned to each using the network address DIP Switch.
The example below describes its use to address the room
controller. Each switch position (1–8) has a value associated
with it (1–128). Addresses 1 through 254 are valid for use
but 255 (all values added together) is reserved for system
use and should not be used.
1.
Add the value for each switch position that is On to
obtain the panel address.
Catalog Numbers
RC3
RC3D
RC3DE
RC3-PL
RC3D-PL
RC3DE-PL
RC3-PL-N
RC3D-PL-N
RC3DE-PL-N
Switch
Position
ON
OFF
Value
1
2.
+
4
=
5 (Panel Address)
Issue a soft
reset by pressing the reset button to assign
Network Node
the address to the panel.
RS-485 Connection
Terminating Jumper
Communication
Status LEDs
Reset Button
Address DIP Switch
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton
Lighting systems
203 Cooper Circle
Peachtree City, GA
www.eaton.com/lightingsystems
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. AP503003EN
June 1, 2015
Eaton is a registered trademark.
All trademarks are property
of their respective owners.