CAT. NO.
D -F-13203
FIRE ALARM PANEL
FAP232N-5L
FEATURES
● Conventional type
● Alarm verification type
(Alarm verification time : 60 seconds)
● Various test functions : fire indication test, line continuity
test, auxiliary power supply test, and alarm verification
time test.
● Durable LED indications
● Back-up power supply
(Ni-Cd battery, 24VDC)
● Easy maintenance
● Automatic self-checking system
DESCRIPTION
On receiving a fire signal from a fire detector or a manual
alarm box, the FAP232N-5L conventional fire alarm panel
gives visual alarms indicating the alarm point, as well as
an audible alarm, to alert the alarm panel operator. It also
produces alarms to alert the occupants of the building
premises.
The FAP232N-5L conventional fire alarm panel has
indication of the alarm points by individual zone lamps.
SPECIFICATIONS
Model no.
FAP232N- 5L
TYPE
Wall mounting type
POWER SUPPLY
220VAC 50/ 60Hz
AUX. POWER SUPPLY
CIRCUIT VOLTAGE
ALARM VERIFICATION TIME
POWER CONSUMPTION
MAX. NUMBER OF APPARATUS
TO BE CONNECTED
AMBIENT TEMPERATURE AND HUMIDITY
LOOP RESISTANCE OF ALARM INPUT CIRCUIT
END-OF -LINE RESISTOR
MATERIALS (ENCLOSURE)
24VDC Ni-Cd battery 0.225AH(Charging current : Approx. 4.7mA)
5,24,48VDC, 24VAC
Thermal detector : 10sec., Smoke detector : 60sec.
● Max. approx. : 14VA for monitoring
● Max. approx. : 31VA for alarming
● Spot type smoke detectors : 30/zone(Max. 50/panel)
● Local alarm bells : 10(24VDC, 10mA/bell)
● Location lamps : 5(30V, 2W/lamp) 14(24V, 24mA/lamp)
0 to 40℃ , 20 to 85%(RH)
Less than 50 Ω / Loop
10kΩ 1/2W
ABS resin with non-flammability to 94UL-V2
COLOR
Beige/yellow : Nearly to Munsell 2.5Y 9/1, semi-glare
WEIGHT
Approx. 2.7kg
●HEAD OFFICE:7-3, Kudan-Minami 4-chome, Chiyoda-ku, Tokyo 102-8277, Japan ●PHONE:
(81)3-3265-0231 ●FAX:
(81)3-3265-5348
FIRE ALARM PANEL FAP232N-5L
CAT. NO. D
-F-13203
TYPICAL WIRING DIAGRAM
End-of-line resistor
Manual fire alarm box
Detector line : 30 Smoke detectors per line(Max.50/panel)
No limit for contact type heat detectors.
Alarm signal lines (L)
Common line (C)
Fire alarm bell
Location lamp
Fire alarm bell
NUMBER of WIRES(BASIC)
5−Alarm signal lines (L)
1−Common line (C) for all zones
1−Response line (A)
2−Fire alarm bell lines (B)
2−Location lamp lines (PL)
External line resistance :
Less than 50Ω/Loop
Terminals :
for use withφ 0.5∼2.0mm wire
n+4 wires
220VAC
50/60Hz
Annunciator (*)
*Note : An optional unit is required for the fire alarm
panel when the annunciator is connected.
Fire alarm panel
DIMENSION
(WALL MOUNTING TYPE)
6
5
7
1
2
380
3
250
4
30
80
UNIT:mm
①CABINET PANEL ②CABINET BODY ③LOCK ④SWITCH COVER ⑤EQUIPMENT NAME PLATE
⑥ZONE LAMP ⑦ZONE NAMEPLATE
● These
instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in
connection with installation, operation and maintenance.
● Specifications are subject to change without notice. Contact Nohmi before relying on above specifications.
● Actual performance is based on proper application of the product by a qualified professional.
● Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser's purposes, the matter should
be referred to Nohmi or a distributer in your region.