UPS5000-A-(30 kVA–120 kVA)
V100R002
Product Description
Issue
Draft B
Date
2013-09-22
HUAWEI TECHNOLOGIES CO., LTD.
Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Trademarks and Permissions
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Technologies Co., Ltd.
Address:
Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China
Website:
http://www.huawei.com
Email:
[email protected]
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
i
UPS5000-A-(30 kVA–120 kVA)
Product Description
About This Document
About This Document
Purpose
This document describes the high-frequency tower-mounted UPS5000-A-(30 kVA–120 kVA)
in terms of models, positioning, benefits, application scenarios, configurations, composition,
and technical specifications. UPS is short for uninterruptible power system. Unless otherwise
specified, UPS refers to all the models described in this document.
The UPS5000-A described in this document provides an output capacity of 30 kVA, 40 kVA,
60 kVA, 80 kVA, or 120 kVA.
Intended Audience
This document is intended for:

Sales engineers

System engineers

Technical support engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates a hazard with a high level or medium level of risk
which, if not avoided, could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation that, if not avoided,
could result in equipment damage, data loss, performance
deterioration, or unanticipated results.
Provides a tip that may help you solve a problem or save time.
Provides additional information to emphasize or supplement
important points in the main text.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
ii
UPS5000-A-(30 kVA–120 kVA)
Product Description
About This Document
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue Draft B (2013-09-22)
Added the description of UPS5000-A-(60 kVA–120 kVA).
Issue Draft A (2013-07-08)
This issue is used for first office application (FOA).
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
iii
UPS5000-A-(30 kVA–120 kVA)
Product Description
Contents
Contents
About This Document .................................................................................................................... ii
1 Model Description ........................................................................................................................ 1
2 Overview......................................................................................................................................... 3
2.1 Positioning .................................................................................................................................................................... 3
2.2 Highlights ..................................................................................................................................................................... 3
2.3 Features ......................................................................................................................................................................... 4
3 Application Scenarios and Configurations .............................................................................. 5
3.1 Typical Applications ..................................................................................................................................................... 5
3.2 Typical Configurations.................................................................................................................................................. 6
4 Composition ................................................................................................................................... 8
4.1 Overview ...................................................................................................................................................................... 8
4.2 UPS Appearance ........................................................................................................................................................... 8
4.2.1 UPS5000-A-30 kVA/40 kVA ..................................................................................................................................... 8
4.2.2 UPS5000-A-60 kVA/80 kVA/120 kVA ...................................................................................................................... 9
4.3 MDU ............................................................................................................................................................................. 9
4.4 Functional Components .............................................................................................................................................. 12
4.4.1 UPS5000-A-30 kVA/40 kVA Functional Components ............................................................................................ 12
4.4.2 UPS5000-A-60 kVA/80 kVA/120 kVA Functional Components ............................................................................. 16
5 Optional Components ................................................................................................................ 19
5.1 Overview .................................................................................................................................................................... 19
5.2 Dry Contact Card ........................................................................................................................................................ 20
5.3 BCB box ..................................................................................................................................................................... 21
5.4 Battery Switch Box ..................................................................................................................................................... 22
5.5 Ambient Temperature and Humidity Sensor ............................................................................................................... 24
5.6 Short-Distance Battery Temperature Sensor ............................................................................................................... 25
6 Technical Specifications ............................................................................................................ 27
6.1 Physical Specifications ............................................................................................................................................... 27
6.2 Environmental Specifications ..................................................................................................................................... 27
6.3 Safety Regulations and EMC ...................................................................................................................................... 28
6.4 Mains Input Electrical Specifications ......................................................................................................................... 28
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
iv
UPS5000-A-(30 kVA–120 kVA)
Product Description
Contents
6.5 Bypass Input Electrical Specifications ........................................................................................................................ 29
6.6 Battery Specifications ................................................................................................................................................. 29
6.7 Output Electrical Specifications ................................................................................................................................. 29
6.8 System Electrical Specifications ................................................................................................................................. 30
A Acronyms and Abbreviations .................................................................................................. 31
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
v
UPS5000-A-(30 kVA–120 kVA)
Product Description
1 Model Description
1
Model Description
This document describes the following UPS models:

UPS5000-A-30KTTL

UPS5000-A-40KTTL

UPS5000-A-60KTTL

UPS5000-A-80KTTL

UPS5000-A-120KTTL
Figure 1-1 shows a UPS model number.
Figure 1-1 Model number
Table 1-1 describes the model number.
Table 1-1 Model number details
No.
Item
Description
(1)
Product category
UPS
(2)
Product family
5000: medium-capacity UPS
(3)
UPS subcategory
A series
(4)
Output capacity
30K: 30 kVA/kW
40K: 40 kVA/kW
60K: 60 kVA/kW
80K: 80 kVA/kW
120K: 120 kVA/kW
(5)
Issue Draft B (2013-09-22)
UPS type
TT: tower-mounted
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
1
UPS5000-A-(30 kVA–120 kVA)
Product Description
1 Model Description
No.
Item
Description
(6)
Battery pack type
L: external large-capacity battery pack
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
2
UPS5000-A-(30 kVA–120 kVA)
Product Description
2 Overview
2
Overview
2.1 Positioning
The UPS5000-A is an online, double-conversion, and tower-mounted UPS that Huawei has
launched. It uses the digital signal processing (DSP) technology and features high reliability,
efficiency, availability, and intelligence.
The UPS5000-A provides reliable, economical, intelligent, and convenient solutions. It
supplies reliable and high-quality AC power to:

Server rooms

Small- and medium-sized data centers

Telecom and Internet switch rooms of small- and medium-sized enterprises

Local area networks (LANs) and communications equipment rooms

Equipment rooms of branch offices in sectors such as finance

Infrastructures, such as control equipment rooms, wireless systems, houses, and offices
2.2 Highlights
High Reliability
The auxiliary power supply and fans use redundancy design. If the auxiliary power supply or
fans are faulty, the UPS5000-A continues working reliably.
High Availability
The UPS5000-A can be tower-mounted or mounted on a 19-inch rack. The flexible
installation reduces installation space.
High Loading Capability
The UPS5000-A has an output power factor (PF) of 1, suitable for inductive and capacitive
loads with PFs greater than 0.5. This ensures the capacity to carry more loads and reduces
customer investments.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
3
UPS5000-A-(30 kVA–120 kVA)
Product Description
2 Overview
Easy Management
The UPS5000-A supports web monitoring, offers Simple Network Management Protocol
(SNMP) functionality, and provides communications ports such as the RS485 port to facilitate
networking and reduce investment costs.
2.3 Features
High Stability and Reliability

The UPS5000-A is recommended for poor power grids because it supports a wide range
of input voltages and frequencies. (The UPS works at full load when the line voltage is
305–485 V AC and is linearly derated to 40% when the line voltage is 138–305 V AC.)

The UPS5000-A has 5 kA lightning protection, higher than the industry level 2 kA.

The UPS5000-A has a high inverter overload capability.
105% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
High Efficiency and Energy Saving

The input PF is 0.99, and the total distortion of the input current waveform (THDi) is
less than 3%. This greatly reduces the pollution on power grids and the expense on
cables and circuit breakers.

The UPS5000-A has an efficiency of more than 99% in energy control operation (ECO)
mode. The short transfer time ensures reliability.

The UPS5000-A has a self-load test function. Startup and commissioning are easy,
allowing the UPS5000-A to be put into operation quickly.
Easy Maintenance

The UPS5000-A provides a maintenance switch and supports power-unit-level
maintenance to facilitate installation and maintenance.

The UPS5000-A supports self-diagnosis and allows you to replace power units onsite,
which improves maintenance efficiency.
Flexible Battery Configuration
The battery string can be shared depending on site requirements. You can configure thirty to
forty 12 V batteries.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4
UPS5000-A-(30 kVA–120 kVA)
Product Description
3
3 Application Scenarios and Configurations
Application Scenarios and Configurations
3.1 Typical Applications
The UPS5000-A is suitable for power systems in various indoor scenarios, including smalland medium-sized data centers or communications centers, equipment rooms of small- and
medium-sized enterprises, equipment rooms of financial systems, industrial automated
equipment, and scheduling centers.
Figure 3-1 and Figure 3-2 show typical applications.
Figure 3-1 Typical application of a single UPS5000-A
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5
UPS5000-A-(30 kVA–120 kVA)
Product Description
3 Application Scenarios and Configurations
Figure 3-2 Typical application of a parallel system
NOTE
In the preceding figures, only the UPSs are developed and sold by Huawei.
3.2 Typical Configurations
The applications vary depending on UPS configurations, as listed in Table 3-1.
Table 3-1 UPS configurations
Configuration
Application Scenario
Single UPS
Supplies power to common loads.
Provides an average availability.
N+X parallel system
(N represents the number of
requisite UPSs connected in
parallel, and X represents the
number of redundant UPSs.)
Issue Draft B (2013-09-22)
Supplies power to important loads in small- and
medium-sized data centers.
Provides a high reliability and transient overload capacity.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6
UPS5000-A-(30 kVA–120 kVA)
Product Description
3 Application Scenarios and Configurations
Configuration
Application Scenario
Dual-bus system
Supplies power to important loads in large- and
medium-sized data centers and Internet data centers
(IDCs), where very high availability is required.
Provides an outstanding availability, complex
configuration, and freedom from bottlenecks in addition to
parallel system merits.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
7
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
4
Composition
4.1 Overview
The tower-mounted UPS5000-A consists of the UPS chassis and support bases. Optional
components include the dry contact card, antiseismic kit, parallel cable, and bus
synchronization controller (BSC) cable.
4.2 UPS Appearance
4.2.1 UPS5000-A-30 kVA/40 kVA
Figure 4-1 shows the UPS5000-A-30 kVA/40 kVA.
Figure 4-1 UPS5000-A-30 kVA/40 kVA
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
1. Chassis
2. Support base
3. Monitor display unit (MDU)
4. Front panel
4.2.2 UPS5000-A-60 kVA/80 kVA/120 kVA
Figure 4-2 shows the UPS5000-A-60 kVA/80 kVA/120 kVA.
Figure 4-2 UPS5000-A-60 kVA/80 kVA/120 kVA
1. Front panel 1
4. Leveling foot
2. MDU
5. Chassis
3. Front panel 2
6. Castor
4.3 MDU
Appearance
The MDU, located on the front panel of the UPS, allows you to control UPS running, set
parameters, and view running status and alarms. Figure 4-3 shows the MDU panel and its
support.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
Figure 4-3 MDU panel and its support
1. Liquid crystal display (LCD)
5. Startup/Enter/Mute button
2. Back/Shutdown button
6. Mains indicator
3. Up button
7. Battery
indicator
4. Down button
8. Bypass indicator
9. Fault indicator/INFO button
NOTE
The MDU is installed on a separate support. It is not moved when you install or remove the front panel
of the UPS.
Indicators
Table 4-1 describes the indicators on the MDU.
Table 4-1 Indicator description
Indicator
Color
Status
Meaning
Mains indicator
Green
On
The UPS is in normal mode.
Off
The UPS is not in normal mode.
On
The UPS is in battery mode.
Off
The UPS is not in battery mode.
Blinking
The remaining battery capacity is less
than the threshold.
On
The UPS is in bypass mode.
Off
The UPS is not in bypass mode.
Red
On
The UPS is faulty.
Red
Blinking
The UPS generates an alarm.
Green
On
The UPS is running properly.
Battery indicator
Bypass indicator
Fault indicator/INFO
button
Issue Draft B (2013-09-22)
Yellow
Yellow
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
10
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
NOTE

The UPS is in mains ECO mode when the mains indicator and bypass indicator are both on.

The UPS is in battery ECO mode when the battery indicator and bypass indicator are both on.
Functions
The MDU displays the UPS running data and alarm information in real time and allows you
to set parameters and control UPS running on the LCD. The backlight turns off if you do not
press any button within 30s.
Table 4-2 describes the buttons on the MDU.
Table 4-2 Button description
Button
Meaning
Description
ESC
Back/Shutdown
On any screen other than the default screen, press ESC to
return to the upper-level menu (the default screen is the
upper-level screen for the main menu screen).
On the default screen, press ESC for more than 5s.
Release the button when you hear a beep sound. The
shutdown screen is displayed. Press
shuts down.
. The inverter
▲
Up
Press ▲ or ▼ to scroll upward or downward.
▼
Down
Set parameters by using the list or step increase or
decrease.
Startup/Enter/Mute
On the default screen, hold down
for more than 5s.
Release the button when you hear a beep sound. The
startup screen is displayed. Press
On the default screen, press
displayed.
. The UPS starts.
. The main menu is
On any screen, press
. The lower-level menu is
displayed. If the menu is the last level, an information
screen is displayed.
When the buzzer buzzes, hold down
for more than
2s to mute it. The mute function cannot mute the sound
generated due to low battery capacity.
Fault indicator/INFO
button
When an alarm is generated, press
active alarm information.
to view the
When no alarm is generated, press
default screen.
to return to the
When the buzzer buzzes, hold down
to mute it.
The mute function cannot mute the sound generated due
to low battery capacity.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
11
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
NOTE
If you do not press any button within 60s, the default screen is displayed. After login, if you do not press
any button within 60s, you are logged out.
4.4 Functional Components
The functional components include power input and output terminals, communication slots,
dry contacts, and the monitoring bus that controls the addition of optional components and
monitors UPSs.
4.4.1 UPS5000-A-30 kVA/40 kVA Functional Components
Figure 4-4 and Figure 4-5 show the functional components on the front and at the rear of the
UPS5000-A-30 kVA/40 kVA. In Figure 4-4, the front panel and MDU are removed.
Figure 4-4 Functional components on the front of the UPS5000-A-30 kVA/40 kVA
1. Power unit
indicators
5. MDU reset
button
2. Power unit ready switch
3. Bypass unit indicators
4. Bypass unit ready switch
6. Dual in-line package (DIP)
switch
7. MDU port
8. Cold-start button
Indicators
Both the power unit and bypass unit provide the Run indicator, Alarm indicator, and Fault
indicator (from top down).
MDU Reset Button
If the MDU does not work properly, use this button to reset the MDU, without affecting
power supply.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
DIP Switch
Typically, three toggle switches are reserved for function settings. Table 4-3 describes the DIP
switch status.
Table 4-3 DIP switch status
DIP
Switch
DIP1
DIP2
DIP3
LCD
Operation
Function
Remarks
Status 1
OFF
OFF
OFF
N/A
Not defined
N/A
Status 2
ON
ON
OFF
Settings >
Restore
Default
Settings
Restores factory
defaults.
After clearing system
parameters, battery
parameters, monitoring
parameters, and logs
(operation logs, upgrade
logs, and battery test and
statistics logs), the MDU
does not start
automatically.
Status 3
ON
OFF
ON
Hold down the
Up and Down
buttons at the
same time for
5s.
Restores the
user name and
password.
After restoring the preset
user name and password,
the MDU restarts
automatically, without
affecting power supply.
Status 4
ON
OFF
OFF
Control >
Clear historical
alarms
Clears historical
alarm records.
After clearing historical
alarm records, the MDU
restarts automatically.
Status 5
OFF
ON
ON
Control >
Clear operation
logs
Clears
operation logs.
After clearing operation
logs, the MDU restarts
automatically.
Status 6
OFF
ON
OFF
Settings >
Advanced
Param. > Work
mode >
Self-load mode
Sets self-load
mode.
After entering self-load
mode subsequent to
inverter startup, the MDU
does not restart
automatically.
Status 7
OFF
OFF
ON
N/A
Not defined
N/A
Status 8
ON
ON
ON
N/A
Not defined
N/A
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
13
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
Figure 4-5 Functional components at the rear of the UPS5000-A-30 kVA/40 kVA
1. Ventilation
panel on the rear
panel
2. Dry contacts
3. Battery temperature
sensor port
6. BSC port
7. Maintenance
bypass switch
8. Parallel ports
11. Battery
wiring terminals
(under the cover)
12. UPS bypass
input terminals
(under the cover)
13. UPS mains input
terminals (under the
cover)
4. Ambient
temperature
and humidity
sensor port
9. Optional
card slot
5. Fast Ethernet
(FE) port (upper)
and RS485 port
(lower)
10. UPS output
terminals (under
the cover)
Dry contacts
Table 4-4 describes the dry contacts.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
14
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
Table 4-4 Dry contacts
Silk Screen
Description
Status
BFP_NO
Triggers bypass backfeed
protection.
Normally, the COM and NC dry
contacts are closed. If bypass
backfeed occurs, the COM and NO
dry contacts are closed, opening the
bypass input circuit breaker.
/
Reserved
N/A
BTG
Detects battery grounding
failures.
Status:

Closed: battery grounding failure
Secondary side ground

Open: no battery grounding
failure
BFP_COM
BFP_NC
0V
The initial status is Open.
GEN
0V
Detects diesel generator
(D.G.) mode.
Status:

Closed: D.G. mode
Secondary side ground

Open: non-D.G. mode
The initial status is Open.
Detects the battery circuit
breaker (BCB) box.
BCB_OL
Status:

Grounded: BCB box connected

Floated: BCB box not connected
The initial status is Grounded.
Monitors the battery circuit
breaker.
BCB_STA
Status:

Closed: battery circuit breaker ON

Open: battery circuit breaker OFF
The initial status is Open.
BCB_0V
Secondary side ground
N/A
BCB_DRV
Controls the trip of the battery
switch in the BCB box.
Voltage:

0 V: battery switch not tripped

12 V: battery switch tripped
The initial port voltage is 0 V.
SWITCH
STATUS_OUT
Monitors the UPS output
circuit breaker on the output
power distribution cabinet
(PDC).
Status:

Open: circuit breaker OFF

Closed: circuit breaker ON
The initial status is Closed.
SWITCH
STATUS_0V
Secondary side ground
N/A
SWITCH
STATUS_MT
Monitors the maintenance
circuit breaker on the output
PDC.
Status:
Issue Draft B (2013-09-22)

Open: circuit breaker OFF

Closed: circuit breaker ON
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
15
UPS5000-A-(30 kVA–120 kVA)
Product Description
Silk Screen
4 Composition
Description
Status
The initial status is Open.
SWITCH
STATUS_0V
Secondary side ground
N/A
SWITCH
STATUS_BP
Monitors the bypass input
circuit breaker on the input
PDC.
Status:

Open: circuit breaker OFF

Closed: circuit breaker ON
The initial status is Closed.
SWITCH
STATUS_0V
Secondary side ground
N/A
EPO_12V
12 V power supply
N/A
EPO_NO
Triggers emergency power-off
(EPO).
The initial status is Open. EPO is
triggered if the dry contact is closed.
4.4.2 UPS5000-A-60 kVA/80 kVA/120 kVA Functional
Components
Figure 4-6 and Figure 4-7 show the functional components on the front and at the rear of the
UPS5000-A-60 kVA/80 kVA/120 kVA. In Figure 4-6, the front panel and MDU are removed.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
16
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
Figure 4-6 Functional components on the front of the UPS5000-A-60 kVA/80 kVA/120 kVA
1. Bypass unit
indicators
6. Power unit
indicators
Issue Draft B (2013-09-22)
2. MDU port
7. Power unit
ready switch
3. Bypass unit
ready switch
8. Maintenance
bypass switch
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
4. MDU reset
button
9. Cold-start
button
5. DIP
switch
17
UPS5000-A-(30 kVA–120 kVA)
Product Description
4 Composition
Figure 4-7 Functional components at the rear of the UPS5000-A-60 kVA/80 kVA/120 kVA
1. Dry contacts
5. BSC port
2. Battery
temperature
sensor port
6. Parallel ports
3. Ambient temperature
and humidity sensor port
4. FE port (upper) and
RS485 port (lower)
7. Optional card slot
8. Power distribution
unit (PDU)
The functions of UPS5000-A-60 kVA/80 kVA/120 kVA functional components are the same as those of
UPS5000-A-30 kVA/40 kVA functional components. For details, see section 4.4.1 "UPS5000-A-30
kVA/40 kVA Functional Components."
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
18
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
5
Optional Components
5.1 Overview
The UPS5000-A provides a variety of optional components to address various customer
requirements. Table 5-1 describes the optional components.
Table 5-1 Optional components
Component
Model
Function
Battery switch
box
PDC-0630DC0384BBA
Controls the connection between
battery strings and the UPS when
multiple battery strings are
connected in parallel.
BCB-BOX

PDC-0250DC0384BXA


PDC-0400DC0384BXA

PDC-0630DC0384BXA
Controls the connection
between battery strings and
the UPS.

PDU8000-0125DCV8-BXA001


PDU8000-0250DCV8-BXA001
Provides overload protection,
short-circuit protection, and
remote trip control.

PDU8000-0400DCV8-BXA001

PDU8000-0630DCV8-BXA001

PDU8000-0800DCV8-BXA001
Antiseismic kit
N/A
Reinforces the cabinet so that the
cabinet meets the requirements
of 9 degree seismic fortification
intensity.
Dry
card
RMS-SNMP01A
Provides output dry contacts.
N/A
Monitors
the
ambient
temperature and humidity.
contact
Ambient
temperature
and humidity
sensor
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
19
UPS5000-A-(30 kVA–120 kVA)
Product Description
Component
5 Optional Components
Model
Function
Short-distance
battery
temperature
sensor
N/A
Internal battery temperature
sensor. The required distance is
within 2 m.
Long-distance
battery
temperature
sensor
N/A
External battery temperature
sensor. The required distance is
within 50 m.
Parallel cable
5 m/10 m/15 m
Connects UPSs in parallel.
BSC cable
5 m/10 m/15 m
Transmits bus synchronization
signals in a dual-bus system.
5.2 Dry Contact Card
Appearance
Figure 5-1 shows a dry contact card.
Figure 5-1 Dry contact card
1. Input and output dry contacts
Functions
The dry contact card RMS-RELAY01A is installed in the optional card slot on the UPS and
supports hot swap. The card provides six alarm dry contact outputs (normal mode, battery
mode, bypass mode, low battery voltage, bypass backfeed, and UPS faults).
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
20
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
NOTE
For details about the dry contact card, see the RMS-RELAY01A User Manual. When the dry contact card
is used on the UPS, only output dry contacts are available.
5.3 BCB box
Appearance
Figure 5-2 shows the BCB box PDU8000-0250DCV8-BXA001.
Figure 5-2 BCB box
Functions
The BCB box controls the connection between battery strings and the UPS5000-A and
provides overload protection, short-circuit protection, and remote trip control.
Specifications
Table 5-2 lists the technical specifications of the BCB box.
Table 5-2 Technical specifications of the BCB box
Item
Rated
(A)
Issue Draft B (2013-09-22)
current
PDU80000125DCV8
-BXA001
PDU80000250DCV8
-BXA001
PDU80000400DCV8
-BXA001
PDU80000630DCV8
-BXA001
PDU80000800DCV8
-BXA001
125
250
400
630
800
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
21
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
Item
PDU80000125DCV8
-BXA001
PDU80000250DCV8
-BXA001
PDU80000400DCV8
-BXA001
PDU80000630DCV8
-BXA001
PDU80000800DCV8
-BXA001
Rated voltage
(V DC)
750
750
750
750
750
Breaking
capacity (kA)
16
16
16
20
36
IP level
20
20
20
20
20
5.4 Battery Switch Box
Appearance
Figure 5-3 shows a battery switch box.
Figure 5-3 Battery switch box
Figure 5-4 shows the position for installing the battery switch box.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
22
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
Figure 5-4 Battery switch box installed on the battery rack
Functions
The battery switch box controls the connection between battery strings and the UPS5000-A
when the UPS5000-A is equipped with a single or multiple battery strings connected in
parallel.
Specifications

Maximum current: 630 A

Maximum voltage: 384 V DC

Short-term durability: 20 kA (≤ 1000 V 1s)

Protection level: IP20
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
5.5 Ambient Temperature and Humidity Sensor
Appearance
Figure 5-5 shows an ambient temperature and humidity sensor.
Figure 5-5 Ambient temperature and humidity sensor
Functions
The ambient temperature and humidity sensor monitors the ambient temperature and humidity
in the equipment room.
Before you use the ambient temperature and humidity sensor, set the DIP switch on it, as
shown in Figure 5-6. The DIP switch address ranges from 32 to 44. The DIP switch has six
binary toggle switches. The bit on the leftmost is the most significant bit, and the bit on the
rightmost is the least significant bit. Bit 1 indicates ON, and bit 0 indicates OFF. See Table
5-3.
Figure 5-6 DIP switch on the ambient temperature and humidity sensor
Table 5-3 DIP switch address mapping
Toggle
Switch
32
33
34
35
36
37
38
39
40
41
42
43
44
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
24
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
Toggle
Switch
32
33
34
35
36
37
38
39
40
41
42
43
44
2
0
0
0
0
0
0
0
0
0
0
0
0
0
3
0
0
0
0
0
0
0
0
1
1
1
1
1
4
0
0
0
0
1
1
1
1
0
0
0
0
1
5
0
0
1
1
0
0
1
1
0
0
1
1
0
6
0
1
0
1
0
1
0
1
0
1
0
1
0
NOTE
The long-range battery temperature sensor looks the same as the ambient temperature and humidity
sensor. The difference is that the former has a DIP switch address range of 16 to 28. Therefore, you can
use the sensor as an ambient temperature and humidity sensor or battery temperature sensor by setting
the DIP switch address.
5.6 Short-Distance Battery Temperature Sensor
Appearance
Figure 5-7 shows a short-distance battery temperature sensor.
Figure 5-7 Short-distance battery temperature sensor
D: 6±0.2 mm
L1: 30±0.5 mm drawing tube
L2: 2000±50 mm
L3: 20±5 mm (crimped with a
two-port terminal block on the
front. The distance between the
two ports is 2.54 mm.)
Functions
The short-distance battery temperature sensor monitors the ambient temperature near batteries.
Table 5-4 lists its performance specifications.
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
25
UPS5000-A-(30 kVA–120 kVA)
Product Description
5 Optional Components
Table 5-4 Performance specifications
Item
Specifications
Measured temperature
–40°C to +80°C
Nominal impedance (at 25°C)
10 kilohms (±1%)
B25/85 value
3435 K
B25/85 value tolerance (%)
±1
Rated power
50 mW
Storage temperature
–40°C to +85°C
Protection level
IP68 (in 1 m deep water)
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
26
UPS5000-A-(30 kVA–120 kVA)
Product Description
6 Technical Specifications
6
Technical Specifications
6.1 Physical Specifications
Item
30 kVA
40 kVA
60 kVA
80 kVA
120 kVA
Cabling mode
Cables are routed from the bottom.
Protection level
IP20
Dimensions (H x W
x D)
500 mm x 264 mm x 800
mm
Communication
Optional card slot, RS485 port, and FE port; SNMP and Modbus
Weight
70 kg
1020 mm x 440 mm x 850 mm
160 kg
200 kg
6.2 Environmental Specifications
Item
30 kVA
40 kVA
60 kVA
Operating temperature
0–40°C
Storage temperature
–40°C to +70°C
Humidity
0%–95% RH (non-condensing)
Altitude
0–1000 m
80 kVA
120 kVA
When the altitude is above 1000 m (maximum 4000 m), see
IEC62040-3 to check how the load power is derated.
Noise
At 25°C and atmospheric pressure:
100% load: 58 dBA (30/40 kVA); 64 dBA (60/80/120 kVA)
50% load: 51 dBA (30/40 kVA); 60 dBA (60/80/120 kVA)
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
27
UPS5000-A-(30 kVA–120 kVA)
Product Description
6 Technical Specifications
6.3 Safety Regulations and EMC
Item
30 kVA
40 kVA
Safety regulations
EN62040-1: 2008
60 kVA
80 kVA
120 kVA
IEC62040-1: 2008
EMC
EN62040-2
IEC62040-2
IEC61000-3-11
IEC61000-3-12
IEC61000-2-2
IEC61000-4-2
EN61000-4-3
EN61000-4-6
IEC61000-4-8
IEC61000-4-11
6.4 Mains Input Electrical Specifications
Item
30 kVA
40 kVA
60 kVA
80 kVA
Input system
Three-phase, four-wire, and PE wire
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Input voltage
138–485 V AC
120 kVA
The load power is not derated at 305–485 V AC and is derated to
40% at 138–305 V AC.
Rated frequency
50 Hz/60 Hz
Input frequency
40–70 Hz
Input PF
> 0.99 (full load); > 0.98 (50% load)
THDi
< 3% (linear load)
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
28
UPS5000-A-(30 kVA–120 kVA)
Product Description
6 Technical Specifications
6.5 Bypass Input Electrical Specifications
Item
30 kVA
40 kVA
60 kVA
80 kVA
120 kVA
Input system
Three-phase, four-wire, and PE wire
Rated input voltage
380 V AC, 400 V AC, or 415 V AC (line voltage)
Rated frequency
50 Hz/60 Hz
Frequency range
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
Input mode
The mains input and bypass input use different power sources or
share a power source.
Bypass current
equalization
In a parallel system, control the cable length to equalize the current.
The current equalization must be less than 25%.
6.6 Battery Specifications
Item
30 kVA
40 kVA
60 kVA
80 kVA
Battery voltage
360–480 V DC (30–40 batteries, 32 by default)
120 kVA
The load power is derated by 6% when 30 batteries are configured.
Battery management
Intelligent battery management
One-button
cold-start
In the case of mains outage, batteries start the UPS, which supplies
power to loads.
Battery string
sharing
No battery string is shared by default.
Charge voltage
Equalized voltage: 2.35 V/cell; float voltage: 2.25 V/cell
Battery string sharing is supported in a parallel system.
6.7 Output Electrical Specifications
Item
30 kVA
Output system
Three-phase, four-wire, and PE wire
Voltage
380 V AC, 400 V AC, or 415 V AC (tolerance ±1%) (line voltage)
Frequency
In normal mode, the mains frequency is synchronous with the
bypass input frequency. The local frequency of the inverter is 50 Hz
or 60 Hz (tolerance ±0.25%).
Total harmonic
distortion of output
< 1% (full linear load)
Issue Draft B (2013-09-22)
40 kVA
60 kVA
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80 kVA
120 kVA
29
UPS5000-A-(30 kVA–120 kVA)
Product Description
6 Technical Specifications
Item
30 kVA
40 kVA
60 kVA
80 kVA
120 kVA
voltage (THDv)
Output PF
1
Transfer time
0 ms
Output voltage
unbalance
±3%
Overload capability
Inverter overload capability:
105% < load ≤ 110%: transfer to bypass mode after 60 min
110% < load ≤ 125%: transfer to bypass mode after 10±0.1 min
125% < load ≤ 150%: transfer to bypass mode after 1 min
Bypass overload capability:
Load ≤ 125%: continuous in bypass mode
Load = 1000%: 100 ms in bypass mode
6.8 System Electrical Specifications
Item
30 kVA
Number of UPSs
connected in parallel
2
Parallel system reliability
Auxiliary power supplies and parallel signals use
redundancy design.
Parallel system ECO
Supported
Issue Draft B (2013-09-22)
40 kVA
60 kVA
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80 kVA
120 kVA
30
UPS5000-A-(30 kVA–120 kVA)
Product Description
A Acronyms and Abbreviations
A
Acronyms and Abbreviations
B
BCB
battery circuit breaker
BSC
bus synchronization controller
D
D.G.
diesel generator
DIP
dual in-line package
DSP
digital signal processing
E
ECO
energy control operation
EPO
emergency power-off
F
FE
fast Ethernet
I
IDC
Internet data center
L
LAN
local area network
LCD
liquid crystal display
M
Issue Draft B (2013-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
31
UPS5000-A-(30 kVA–120 kVA)
Product Description
MDU
A Acronyms and Abbreviations
monitor display unit
P
PDC
power distribution cabinet
PE
protective earthing
PF
power factor
R
RS485
Recommend Standard 485
S
SNMP
Simple Network Management Protocol
T
THDi
total distortion of the input current waveform
THDv
total harmonic distortion of output voltage
U
UPS
Issue Draft B (2013-09-22)
uninterruptible power system
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
32