Voltage Regulation E V reg V nl rated per unit regulation rated %regulation per unit 100% ECE 441 1 Voltage Regulation (continued) • Enl = no-load output voltage – Measure with a voltmeter when no load is connected to the transformer • Vrated = voltmeter reading at the output terminals when the transformer is supplying the rated apparent power • These voltages are all either High-side or Low-side voltages! ECE 441 2 Voltage Regulation (continued) • Measurements are not always easy to make, so use the equivalent circuit. ECE 441 3 When the breaker is open, no current flows in Req,LS , jXeq,LS , or ZLOAD,LS , therefore Vout = VLS = E’LS = Enl ECE 441 4 With rated load on the secondary, E’LS = ILSZeq,LS + VLS ILS = rated low-side current at a specified power factor VLS = rated low-side voltage Zeq,LS = equivalent impedance of the transformer referred to the low-side ECE 441 E’LS = no-load low-side voltage 5 Example 2.7 • The equivalent low-side parameters of a 250kVA, 4160 – 480V, 60 Hz transformer areReq,LS = 0.00920 Ω and Xeq,LS = 0.0433 Ω. The transformer is operated in the step-down mode and is delivering rated current at rated voltage to a 0.840 powerfactor lagging load. • Determine ECE 441 6 – the no-load voltage – The actual input voltage on the highside – The high-side current – The input impedance – The voltage regulation – The voltage regulation if the power factor of the load is 0.840 leading – Sketch the tip-to-tail phasor diagram of the secondary circuit for the 0.840 power factor lagging load. Show all voltage drops. ECE 441 7 250, 000kVA I LS 520.83 A 480V cos 1 (0.840) 32.86 32.86(lagging ) VLS 4800V I LS 520.83 32.86 A ECE 441 8 Low-Side Output ECE 441 9 ' ELS I LS Req , LS I LS jX eq , LS VLS ' ELS 520.83 32.86(0.0092) 520.83 32.86( j 0.0433) 4800 ' ELS 4.79 32.86 22.5557.14 4800 ' ELS 4.024 j 2.599 12.235 j18.94 480 j 0 ' ELS 496.531.886V ECE 441 10 ' HS ' LS E a E VT E ' HS VHS 4160 8.667 VLS 480 aE 8.667(496.531.886) ' LS VT 4303.41.886V ECE 441 11 The high-side current I HS I HS I LS 520.83 32.86 a 8.667 60.09 32.86 A The input impedance VT 4304.41.886 Z I HS 60.09 32.86 ' in Zin' 71.6234.74 ECE 441 12 The voltage regulation Enl Vrated 496.53 480 reg 0.0344 3.44% Vrated 480 ECE 441 13 Voltage Regulation if the power factor is 0.840 leading I LS 520.83 32.86 ............. ' ELS 472.282.61 Enl Vrated 472.28 480 reg 0.0161 1.61% Vrated 480 Regulation is negative because of a voltage rise in the transformer due to resonant effects. ECE 441 14 The “tip-to-tail” phasor diagram for the 0.840 power factor lagging load. I LS Req , LS 520.83 32.86(0.0092) 4.79 32.86V I LS X eq , LS 520.83 32.86( j 0.0433) 22.657.14V ECE 441 15 Component Phasors ECE 441 16 Tip-to-Tail Addition ECE 441 17