* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Tech W Shop 1998 5kv
		                    
		                    
								Survey							
                            
		                
		                
                            
                            
								Document related concepts							
                        
                        
                    
						
						
							Transcript						
					
					Diagnostic Insulation Testing       Predictive Maintenance issues Basis of Insulation Tests Spot Tests & Polarisation Index Dielectric Discharge Test Power factor testing AVO Range Maintenance Regimes  Corrective maintenance Preventive (Periodic) Maintenance Predictive Maintenance (Record & trend data to determine next action - variable maintenance periods)  Appropriate regime varies   Test Techniques - DC Testing  Total Current has 3 components  Capacitive Current - Charging  Absorbtion Current -Polarisation  Leakage Current   TIME DEPENDENT Temperature Dependent Insulation Test Currents I/uA 100 Charging Total 10 Leakage Absorption 1 0,1 1 10 T Insulation Equivalent Circuit Leakage Capacitance Absorption Diagnosis from Insulation Tests  Record & Trend  Spot Tests - Record conditions as well (Temp, RH) Time resistance tests - Polarisation Index Test (PI) Step Voltage Test (SV) Dielectric Discharge Tests (DD)    Insulation Test as a Go/NoGo Test    Spot Test carried out for given time (1 minute) Commissioning National /Manufacturer’s Standards Time Resistance Tests    Independent of equipment size and temperature Some information without past results Options;  Curves  Time - Resistance Ratios Time ResistanceTest R Absorbtion current not seen t1 t2 Time Time Resistance Tests Polarisation Index (10 min/1 min ratio) <1 Insulation Condition unsatisfactory 1,0 - 2,0 dubious 2,0 - 4,0 good >4,0 very good Time Resistance Tests Dielectric Absorption Ratio (60 s/30 s) <1 Insulation Condition unsatisfactory 1.0 - 1.4 dubious 1.4 - 1.6 good >1.6 very good Step Voltage Test   Test voltage is increased in 5 steps Lower insulation resistance values at higher voltage indicate presence of cracks/holes Step Voltage Test 5000 V Resistance 2000 V 1000 V Voltage Dielectric Discharge Test  Test is run until currents stabilise  Measurements made on discharge DD = Current after 1 min Voltage x Capacitance Dielectric Discharge Test + - - - + + + + - - - + + ++ - - + + - + - + + - + - + - + - - + + Dielectric Discharge Test DD Value >4 2.0 - 4.0 <2.0 Insulation Condition unsatisfactory dubious good Tan Delta Testing    Polarisation and capacitive current dominate Aging (moisture/dirt) sensitive Low voltages can be used Perfect Insulation I (capacitive) ITOTAL IR = 0 V (applied) Facts about Insulation  In a “REAL insulation system” there is also a loss current flowing inphase with the voltage IC // IR = ITOTAL REAL Insulation I (capacitive) IC ITOTAL IR V (applied) Facts about Insulation    In practice NO insulation is perfect Resistive loss current is always present Total current leads the voltage by a phase angle  and lags capacitive current by angle  REAL Insulation I (capacitive) IC ITOTAL   IR V (applied) What is Tan Delta?   Tan Delta is the ratio of in-phase (resistive) current to the 90-degree (capacitive) current Tan Delta equals Dissipation Factor What is Power Factor?  Power factor is the ratio in-phase (resistive) current to the total current. Tan Delta Testing I(capacitive) Tan  = IC ITOTAL  Power Factor =  IR V(applied) IR IC IR ITOTAL Tan Delta v. Power Factor  Both values are similar up to 20% power factor and tan delta; beyond 20% they diverge. Tan Delta 3 Terminal Test Low voltage (L) High voltage (H) CHL CLG CHG Ground Connection (G) Tan Delta 3 Terminal Test Configuration Measures GST L-GND CHL + CHG GST L-Guard CHG UST CHL GST H-Guard CLG GST H-GND CHL + CLG Why perform the Tan Delta Test?     Normal insulation resistance testing limited to 5kV dc Tan Delta is up to 12kV ac Most test specimens normally operate with AC voltage Much closer resemblance to the normal operating condition of the insulation Tan Delta Testing     Comparison with name -plate values Very sensitive to small changes a.c. test at rated voltage Larger, heavier test equipment Insulation Test Diagnosis Test Type Main Failure Mode “Spot” Insulation Test Go/no go Polarisation Index Moisture/dirt Step Voltage Cracks/holes Dielectric Discharge Absorbed moisture/dirt Loss measurement Tan-delta Tests Performed On        Transformers Circuit Breakers Rotating Machinery Insulating Liquids High Voltage Bushings Surge Arrestors High Voltage Coils MEGGER BM11D     Portable, IP54 , large PbAcid battery Readings to 500 GOhm Display is large, clear & Easy to Use Safety features  Automatic discharge, locking test leads, Hazard display  Integral Timer MEGGER BM21 All BM11D features plus;  Readings up to 5TOhm  Selectable Test Voltage  Selectable Test Time  Checks Capacitance at test End  Can show current as well as resistance  Burn mode MEGGER BM25 As BM21 features plus;  Automated tests  Polarisation Index  Step Voltage  Dielectric Discharge   RS232 download results every 5 s Download software & lead MEGGER S1-5005 As BM25 with 5 mA test current. BM25 has 2 mA test current. MEGGER S1-5010      Heavy Duty - Mains & Battery Automated Tests Results Storage RS 232 communications Graphical Display MEGGER S1-5010 MEGGER S1-5010   Memory for 75 sets of results Windows PC software  remote operation  results storage    External output for HV “ON” indicator Switchable digital filter for noise rejection IP54 weatherproofing S1-5010 and S1-S1 software S1-5010 S1-S1 software      Duplicates the S1-5010 on your PC screen. Control the S1-5010 from your PC via an RS232 link. Download tests to your PC  in real time.  as a batch at the end of testing. Annotate the tests results with details of the test. Recreate graphs etc. in other software. BIDDLE Delta 2000      500 V - 12 kV power factor tester Automatic bridge operation High noise immunity Menu driven display Measures voltage, current, power (loss), power factor/tan-delta and capacitance BIDDLE Delta 2000     Results storage Printer for on-site results Downloading test data Accessories Oil test cell  Bushing connectors  Bar code wand  BIDDLE Delta 2000 BIDDLE 2.5 & 12 kV semiautomatic units    2.5 kV single unit construction 12 kV control unit and Measure capacitance, dissipation factor and Watts CB-100 Low Voltage Bridge      28 V test voltage Safe Compact Low cost Often used on bushings & transformers Testing with Safety – How – does the electrical risk appears ? - When an electrical line or conductor is unexpectedly still live - When current sources are not properly isolated - When power generators are connected to the network - When there are atmospheric phenomenons such as lightning - Through induced currents Testing with Safety  However, it has also been observed that the most common causes of unexpected presence of voltage on electrical lines or installations were due to: - A mistake in operating a switch - A mistake in identifying the work to perform - A "faulty" switch (one of the links for example remaining partially engaged) Testing with Safety  How does the electrical risk disappear ? – 1. By observing Simple Electrical Safety Rules directed by common Sense (even if Working Practices vary from a country to another, GOLDEN RULES always apply). 2. By using Simple, Light and Reliable Electrical Safety Equipment. Testing with Safety  1. SEPARATE THE WORK AREA FROM ALL POSSIBLE SOURCES OF POWER SUPPLY by opening circuit-breakers, switches… AND LOCK THE LINKS IN THE OPEN POSITION Testing with Safety   2. CHECK THE ABSENCE OF VOLTAGE at source and on site, on each conductor and apparatus involved. 3. APPLY APPROPRIATE SHORTCIRCUIT AND EARTHING SYSTEMS in sufficient numbers on the conductors of your network where operation is taking place. Testing with Safety  4. SHOWN, WARN OTHERS AND LIMIT THE WORK AREA even during the most simple temporary maintenance operation Testing with Safety    Discharge Sticks Slowly discharge capacitive items (cables, capacitors….) Discharge to a safe level in 5 - 10 times RC (time constant) Discharge Sticks Voltage 35 kV 50 kV 75 kV 100 kV 150 kV Length 50 cm 136 cm 156 cm 176 cm 208 cm Resistance 10 kOhm 100 kOhm 150 kOhm 200 kOhm 300 kOhm Max. cap. 6 uF 6 uF 4 uF 3 uF 2 uF Oil Testing MEGGER Foster Oil Electric Strength Testers Why test switchgear oil? Prevent Transformer failure Principle problems are:  humidity  oxygen  temperature  Oil Testing Methods Water content  Acidity  Colour  Flash point  Gas content  Oil provides HV insulation Electric strength is the most important test  Test Voltage Breakdown Testing 60 40 20 0 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Time Electric Strength Test Results   Average over six tests Scatter can be large  Standard  deviation calculated Report breakdown values, date, temperature New Specification EN60156     Replaces IEC156 (1963) Optional stirring Current limited breakdown for silicone oils Gives guidance on scatter of results Withstand Testing    Test voltage held at preset level for 1 minute Quick test of level of contamination Increase to breakdown to find headroom? Withstand Testing Test Voltage 60 50 40 30 20 10 0 0 10 20 30 40 50 Time 60 70 80 90 MEGGER Foster OTSAF/2       Fully automatic, unattended operation Wide range of tests including five custom Results include standard deviation, time, date Results printed or download via RS232 Stirring options for magnetic or propellor 60 kV, 80 kV and 100 kV versions MEGGER Foster OTSAF/2 MEGGER Foster OTS60PB         Portable oil test set for on site measurement Battery powered for two days continuous use Fully automatic, unattended operation Pass/fail levels for go/no go testing Small and lightweight (19 kg = 42 lb) Complete with battery charger Variety of electrodes RS232 interface plus optional printer MEGGER Foster OTS60SX        Low cost, Semi automatic set 60 kV maximum output, 0,1 kV resolution Simple START, STOP & PAUSE control Weighs only 17,5 kg Optional vessels for all specifications Auto 60 second timer for withstand testing Operates from 110/230 V power supply MEGGER KF2000 Karl Fischer moisture in oil test set  Simple to use  Quick results  Low cost  Battery powered, portable MEGGER KF2000 AVO INTERNATIONAL Bringing Reliability to Amps Volts Ohms
 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
									 
                                             
                                             
                                             
                                             
                                             
                                             
                                             
                                             
                                             
                                             
                                            