Download Series 2300 Room Units for TALON Controllers

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rectiverter wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Installation Instructions
Document No. 129-479
November 13, 2012
Series 2300 Room Units
for TALON® Controllers
Product Description
These room units measure temperature in the
occupied space in which they are installed. Models
with display allow users to view the measured
temperature value. A version with temperature
setpoint adjustment is also offered.
These devices are intended for use with appropriate
signal input on a TALON Controller. The effective
sensing and setpoint range is 55°F to 95°F (13°C to
35°C).
These room units can be mounted on electrical
boxes, stud-type mounting brackets, or drywall.
Obtain the necessary mounting hardware and follow
the appropriate mounting procedures for the type of
installation required.
Product Numbers
Expected Installation Time
20 minutes
Required Tools
•
Sizes 1 and 2 Phillips screwdrivers
•
Small and medium flat-blade screwdrivers
•
1/16-inch hex key
•
Medium-duty electric drill
•
3/16-inch (4.8 mm) drill bit
•
One-inch (25 mm) hole saw
•
Small level
•
Tape measure
•
Marker or pencil
Prerequisites
QAA2312.xWxN
•
Review these instructions before beginning.
QAA2330.xWxx
•
Installed: appropriate field wiring within the
maximum wiring run length for the individual
equipment controller. The maximum
recommended length is 100 feet (30 m).
•
All wiring must comply with National Electric
Code (NEC) and local regulations.
QAA23SS.xWxN
QAA23SS.xWxx
Accessories
AQA2200-INTL Room Unit Back Plate (10-pack)
AQA2200-2X4 Room Unit Back Plate (Single)
NOTE: If installing the Back Plate, discard the
metric screws provided with the Back Plate
and utilize the Room Unit mounting screws.
Caution Notations
CAUTION
Figure 1. QAA23xx.EWTN, and QAA23xx.FWTN
Room Units.
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Item Number 129-479, Rev. HA
Page 1 of 6
Document No. 129-479
Installation Instructions
November 13, 2012
Mounting Information
Always mount the room unit vertically.
d. Cut the cable, leaving about three inches
(75 mm) on the room unit side of the
drywall. Ensure that pin Number 1 connects
to the same wire at each end of the cable.
Locate the room unit:
•
according to design specifications and local
regulations.
•
where the air circulates around it freely (not
in recessed areas or behind doors).
•
allowing a minimum of 4 inches (10 cm) free
space above and below for proper airflow,
the front cover removal tool, and the
computer communication cable.
•
away from drafts caused by doors, windows,
outside walls, air registers, pipes, return air
plenums, etc.
•
away from heat sources such as strong
lights, fireplaces, direct sunlight, etc.
•
on an inside wall (preferably), about 5 feet
(1.5 m) above the finished floor.
Drywall Mounting (No Rough-in),
Typical
Base Plate Mounting and Wiring
1. Mark the center (cable) hole and the mounting
hole locations, using the room unit base plate as
a template. See Figure 2.
2. Drill two 3/16-inch (4.8 mm) mounting holes and
mount the two plastic wall anchors flush to
below the wall surface for stable mounting of the
device.
Figure 2. Drywall Mounting (No Rough-in), Typical.
7. Terminate the wires to the termination blocks on
the room unit's base plate. (See Figure 5.)
8. Feed the extra cable back through the hole.
Sensor Set-up
R64 Resistor
(°F/°C Selector)
Jumper
3. Cut a 1-inch (25 mm) center hole with a hole
saw.
4. Pull about three inches (75 mm) of the cable
through the hole in the base plate.
5V
10V
Voltage/Current
Selector Switch
5. Mount the room unit base plate on the wall,
noting the UP arrow:
If required, position the Back Plate
behind the Room Unit Base, aligning
the top and bottom mounting holes,
prior to mounting to the wall:
a. Install the two mounting screws provided,
but do not tighten.
V
I
SEN0589R1
NOTE:
Figure 3. Circuit Board
(Located inside Room Unit Cover.
b. Level the room unit base plate for
appearance.
c.
Tighten the two mounting screws to the
room unit base plate.
Page 2 of 6
Siemens Industry, Inc.
Document No. 129-479
Installation Instructions
November 13, 2012
1.
If the device has a switch, determine if voltage
or current output is needed.
•
For current, set the switch in the down
position (I).
Electrical Box and Rough-in
Mounting, Typical
1.
If a locator is attached to the rough-in device,
remove the locator by removing the two screws
and lightly rocking the locator to pull it free.
2.
Untie the twist tie and pull about three inches
(75 mm) of the room unit cable through the hole
in the base plate.
•
For voltage, set the switch in the up position
(V).
NOTE:
The output setting applies to all
outputs (temperature, and setpoint).
2. If selecting voltage, set the jumper:
•
Use the top and middle pins for 0-5V.
• Use the bottom and middle pins for 0-10V.
NOTE:
If the jumper is missing or removed,
the output voltage will default to
0-10V.
NOTE:
The factory default for displayed
temperature units is °F. To change the
display to °C, snip the wire jumper (0 Ohm
resistor R64) on the back of the PCA.
°
F
°
C
3. Mount the room unit base plate on the wall,
noting the UP arrow:
NOTE:
If required, position the Back Plate
behind the Room Unit Base, aligning
the top and bottom mounting holes,
prior to mounting to the wall:
a. Install the two room unit mounting screws
provided, but do not tighten.
b.
Level the room unit base plate for
appearance only.
c.
Tighten the two mounting screws to the
room unit base plate.
CAUTION:
Over-tightening may cause the room unit
base plate to crack or bend.
4. Continue with Drywall Mounting (No Rough-in),
Typical, Steps 6 through 8, and Sensor Set-up.
CAUTION:
To prevent equipment damage, do the
following:
SEN0588R1
If room unit is powered by AC (See Figure
9):
Figure 4. Changing Display to °C.
9. Snap the room unit cover to the room unit base
plate by first hooking the room unit front to the
top latches, and then rotating the cover
downward until it latches.
10. Loosen the safety set screw at the bottom of the
base one or two revolutions to lock the cover to
the base. Be careful not to loosen too far as the
screw can be completely removed from the
base.
• AC Supply must be type NEC Class 2 and
earth grounded at the secondary neutral.
• Room Unit ACN (GND) must be
connected to the controller common.
• If the controller has a floating common,
that common must be connected to the
same earth ground point as the controller
AC supply.
If room unit is powered by isolated DC
(See Figure 8):
• Where power is current limited up to 300
mA, it is not required to earth ground the
controller isolated common.
• Room Unit DC-(GND) must be
connected to the controller common.
Siemens Industry, Inc.
Page 3 of 6
Document No. 129-479
Installation Instructions
November 13, 2012
CAUTION:
Follow manufacturer’s Installation
Instructions and Wiring Guidelines for
connecting the controller to the Room Unit.
•
TALON Controllers with common
already earth grounded are TXIO used
on TC Modular and TC Compact 36
Expansion. These do not require the
earth ground wire to be connected to
the controller as shown in Figure 9.
•
NOTE:
TALON Controllers with floating
common are TC Compact 16/24/36,
Raptor, Predator and PPM. These
require the earth ground wire to be
connected to the controller as shown in
Figure 9.
If active temperature (0-5V/0-10V/4-20 mA) (Pin
3) rather than passive/ resistive temperature is
used, Passive Temp Common (Pin 6) does not
need to be terminated.
NOTE: To use the override function with a Predator
Controller, a 500 ohm resistor must be wired in
series with the setpoint termination on the
Predator Controller and the Override termination
8 on the Room Sensor. See Figure 6 and Figure
7 for the complete wiring diagrams for the two
different style controllers.
The installation is now complete.
Pin No.
2
3
2
3
7
8
1
2
3
5*
6*
1
2
3
5*
6*
7
8
9
1
2
3
5*
6*
7
8
9
10
11
12
Function
QAA2312.EWTN
Temperature
Temp_Common
QAA2330.EWxC
Temperature
Temp_Common
LON1
LON2
QAA23SS.EWxN
DC+ or ACH
DC- or ACN (GND)
Temperature Output
Passive Temp
Passive Temp Common
QAA23xx.FWxN
DC + or ACH
DC - or ACN (GND)
Temperature Output
Passive Temp
Passive Temp Common
Setpoint Output
Override
Override Common
QAA2330.FWTC
DC + or ACH
DC - or ACN (GND)
Temperature Output
Passive Temp
Passive Temp Common
Setpoint Output
Override
Override Common
GND
LON1
LON2
* Not available on “SS” models.
1
2
3
4
5
6
SEN0485R1
7
8
9
10
11
12
Figure 5. Typical Wiring Base.
(All terminals may not be present.)
Page 4 of 6
Siemens Industry, Inc.
Document No. 129-479
Installation Instructions
November 13, 2012
Bypass \ Overdrive
Orange
500 ohm
White/Orange
Pin No.
SETPT
TEMP
Service
LCD/SRV
White/Blue
COM
2
3
Green
White/Green
Setpoint
2
3
7
8
LON
Tranceiver
Vin
DI Src
1
2
3
5*
6*
10K
Com
DC + or ACH
DC - or ACN
1
2
3
4
5
6
1
2
3
5*
6*
7
8
9
SEN0641R1
7
8
9
10
11
12
Figure 6. Predator Actuator (587-104) Wiring.
NOTE:
Wire color code shown in diagrams is for the
588-100X family of cables.
NOTE:
If powering the sensor from the same 24VAC
as the Predator Controllers, ACN for the
controller must connect to pin 2 (DC – or ACN)
of the sensor.
* Not available on “SS” models.
The installation is now complete.
500 ohm
7
8
9
10
11
12
1
2
3
4
5
6
1
2
3
5*
6*
7
8
9
10
11
12
Function
QAA2312.EWTN
Temperature
Temp_Common
QAA2330.EWxC
Temperature
Temp_Common
LON1
LON2
QAA23SS.EWxN
DC+ or ACH
DC- or ACN (GND)
Temperature Output
Passive Temp
Passive Temp Common
QAA23xx.FWxN
DC + or ACH
DC - or ACN (GND)
Temperature Output
Passive Temp
Passive Temp Common
Setpoint Output
Override
Override Common
QAA2330.FWTC
DC + or ACH
DC - or ACN (GND)
Temperature Output
Passive Temp
Passive Temp Common
Setpoint Output
Override
Override Common
GND
LON1
LON2
Pin
Color
Wire
1 = LonNetwork
Green
Twisted
Pair
2 = LonNetwork
White/Green
3 = Service Pin/LCD Power
Blue
4 = Common
White/Blue
5 = SetPoint/Bypass
Orange
6 = Room Temp
White/Orange
DC + or ACH
+
DC - or ACN
Twisted
Pair
Twisted
Pair
I
P
9
SEN0644R1
11
Figure 7.
Siemens Industry, Inc.
Page 5 of 6
Document No. 129-479
Installation Instructions
November 13, 2012
See Controller
Installation Instructions
For Power Input
Requirements
Powered By
Controller
CONTROLLER
2300
DC+ ACH
DC- ACN (GND)
Signal Out
NOTE:
Externally DC powered
2300 Room Units
require isolated DC
supply with all
commons connected
and may be used on
the same controller
with other Room Units
powered by internal
sensor supply.
Sensor Power DC
Common
Signal In
Common
Signal In
Isolated DC
Supply 300 MA Max.
Powered By
Isolated DC
SEN0652R1
2300
DC+
DC-
DC+ ACH
DC- ACN (GND)
Signal Out
I
I
I
I
I
AC
IN
Figure 8. Externally DC Powered 2300 Room Units.
With Class 2 (100 VA) Output
Isolated AC Supply
(See Controller
Installation Instructions)
Powered By
Controller
2300
DC+ ACH
DC- ACN (GND)
Signal Out
CONTROLLER
Sensor Power DC
Common
Signal In
Common
Signal In
Common
Signal In
Common
Powered By
Class 2 (100VA)
Isolated AC
SEN0651R1
DC+ ACH
DC- ACN (GND)
Signal Out
ACH
ACN
I
I
I
I
I
Powered By
Class 2 (100VA)
Isolated AC
Common
Signal In
2300
Class 2
Isolated AC Supply
100 VA Max.
2300
L N E
I
ACH I
ACN I
100 VA
ACH I
ACN I
DC+ ACH
DC- ACN (GND)
Signal Out
L
N
NOTE:
Externally AC powered
2300 Room Units require
controller common and all
AC secondary neutral ACN
to be earth grounded and
may be used on the same
controller with other room
units powered by internal
sensor supply.
E
Note: See Caution
Figure 9. Externally AC Powered 2300 Room Units.
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. TALON and Predator are registered trademarks of Siemens Industry, Inc. Other product or company names
mentioned herein may be the trademarks of their respective owners. © 2012 Siemens Industry, Inc.
Siemens Industry, Inc.
Building Technologies Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089
USA
+ 1 847-215-1000
Your feedback is important to us. If you have
comments about this document, please send them to
[email protected]
Document No. 129-479
Printed in the USA
Page 6 of 6