* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download R4076E LFAA
Resistive opto-isolator wikipedia , lookup
Radio transmitter design wikipedia , lookup
Power electronics wikipedia , lookup
Surge protector wikipedia , lookup
Flexible electronics wikipedia , lookup
Wien bridge oscillator wikipedia , lookup
Transistor–transistor logic wikipedia , lookup
Integrated circuit wikipedia , lookup
Index of electronics articles wikipedia , lookup
Interferometric synthetic-aperture radar wikipedia , lookup
Integrating ADC wikipedia , lookup
Operational amplifier wikipedia , lookup
Regenerative circuit wikipedia , lookup
Valve RF amplifier wikipedia , lookup
Two-port network wikipedia , lookup
Telecommunications relay service wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Phase-locked loop wikipedia , lookup
Schmitt trigger wikipedia , lookup
RLC circuit wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Midos Types LFAA 101, 102 Auto-Reclose Relay Figure 1: LFAA relay with hinged front cover open to show the modular construction Features Models Available Benefits ● Selectable single and/or three phase auto-reclosing LFAA 101 ● Wide choice of scheme logic options ● Suitable for feeders controlled by one or two circuit breakers ● Number of reclosures can be selected ● Dead times, close pulse and reclaim time are independently adjustable ● Scheme logic options can be selected ● User friendly inbuilt keypad and menu system ● Built-in test facilities ● Automatic scheme documentation via ladder diagram 2 for application to feeders switched by a single circuit breaker LFAA 102 ● Suitable for all transmission feeder protection schemes for application to feeders switched by two circuit breakers ● Simplified commissioning via inbuilt test feature ● Greater setting flexibility ● Comprehensive analysis of auto reclose attempts Signals from external plant DC auxiliary + supply VX1 – Opto-isolators Auxiliary relay outputs Micro-processor +6.5V +19.5V –19.5V +24V 0V. H13 DC/DC converter H14 LED indications Serial & parallel I/O ports LCD Keypad Signals to external plant Operator interface Figure 2: LFAA relay block diagram phase auto-reclose if protection re-operates during the reclaim time after the first reclose Application The LFAA auto-reclose relay provides facilities for single or two-shot reclosures of one or two circuit breakers following their tripping for a fault on an overhead line. The reclosures can be selected to be either high speed single-phase, or high speed or delayed three-phase. When three-phase reclosure is desired the equipment will convert any single or two-phase tripping into three-phase tripping before initiating the reclosure. For schemes with two circuit breakers the reclosure of the second circuit breaker can be either simultaneous with the first circuit breaker or it can be sequential. In the latter case the reclosure of the second circuit breaker must naturally be a delayed three phase reclosure. Different operating cycles can be selected using the keypad on the relay front-plate. These allow the relay to perform various combinations of the following cycles: One breaker schemes (LFAA 101) ● ● Single shot scheme: - single phase auto-reclose - single phase or three phase - auto reclose, depending on type of fault - three phase auto-reclose for all types of fault Two shot scheme: any of the above cycles for the first shot, followed by delayed three- Two breaker schemes (LFAA 102) ● Combinations of single and three phase auto-reclose as above ● Circuit breakers can be closed simultaneously or sequentially on the first shot A block diagram is shown in Figure 2. Description - Scheme Scheme initiation enabling conditions An auto-reclose cycle is initiated by protection operation. Auto-reclose of a specific circuit breaker is enabled provided that, immediately prior to the protection operation: - the circuit breaker is closed - The ‘Energy’ input from that circuit breaker indicates sufficient stored energy to perform an auto-reclose cycle - auto-reclose for that circuit breaker is not switched out of service and is not locked out Scheme initiation Single phase auto-reclose LFAA 101 and LFAA 102 For single phase auto-relose, a phaseto-earth fault on any one phase will initiate single phase tripping and autoreclose of the faulty phase only. A fault involving two of more phases will result in three phase tripping. For this purpose the scheme will convert any two pole trip of the circuit breaker into a three pole trip. LFAA 102 Single phase auto-reclosures can be either of the simultaneous or sequential type depending on the programme selected. Whenever simultaneous reclosure is selected, both circuit breakers will trip single phase and reclose simultaneously after the single phase dead time. Whenever sequential reclosure is selected, the leader circuit breaker will trip single phase and reclose after the single phase dead time but the follower circuit breaker will grip three phase and reclose after the selected follower circuit breaker delay time has elapsed. Three phase auto-reclose Three phase auto-reclose can be initiated by single phase faults only, multi-phase faults only or any fault depending on the scheme selected and whether the auto-reclosure is first or second shot. In the case of faults which result in the tripping of one or two poles of the circuit breaker, the relay will convert the single or two pole trip into a three pole trip before initiating three phase reclosing. LFAA102: auto-reclose of follower circuit breaker The follower circuit breaker can be automatically switched to the autoreclose programme originally selected for the leader circuit breaker if any one of the initiation enabling 3 conditions for the leader circuit breaker is not satisfied. In the sequential single phase or single and three phase auto-reclose programme, one or two shot, the follower circuit breaker will be automatically switched to perform a single phase trip on scheme initiation if any one of the above conditions exists. Single phase reclosure of the follower circuit breaker will occur at the end of the single phase dead time. + DC auxilliary supply Vx2Switch in – B1 1 Switch out B3 2 'A' PH 'A/R initiate' signals from protection 'B' PH 'C' PH 3 PH B5 3 B7 4 B9 5 B11 6 Intertrip receive B13 'Block A/R' from protn. B15 Line voltage monitor B17 Timer test start B19 Developing faults (3) "Stop" B21 For single phase only auto-reclose programmes, the development of a fault on to a previously unaffected phase, if detected during the single pole dead time and before the circuit breaker reclosure, will result in a three phase trip and scheme lockout. (4) "Enable" B23 If any of the above conditions exist prior to initiation of a three phase auto-reclose, the follower circuit breaker will trip three phase followed by reclosure at the end of the three phase dead time. For single and three phase autoreclose programmes, the development of a fault on to a previously unaffected phase, if detected during the discrimination time and before the circuit breaker reclosure, will result in a three phase trip and conversion of reclosing from single phase to three phase. If the developing fault occurs after the discriminating time has elapsed the relay will trip in all three phases and lock out. Scheme reset Single breaker schemes (LFAA 101) The scheme will automatically reset if the reclaim time expires and the circuit breaker is closed. 7 8 9 10 11 12 B25 B27 (1) CB1 aux. switch B2 (2) CB1 healthy B4 Microprocessor 17 CB1 dead line charge/ sync. check CB1 separate sync. check 18 B6 19 B8 20 Reset CB1 lockout Reset CB1 maint. counter B10 (1) CB2 aux. switch B14 (2) CB2 healthy B16 21 B12 22 23 CB2 dead line charge/ sync. check CB2 separate sync. check 24 B18 25 B20 26 Reset CB2 lockout B22 Reset CB2 maint. counter B24 CB2 stop Two breaker schemes (LFAA 102) The auto-reclose of the breakers will automatically reset at the end of the reclaim time if both breakers are closed. If the auto-reclose of only one circuit breaker is in progress at the end of the reclaim time, the scheme will reset if this particular circuit breaker is in the closed position but lock out if it is in the open position. 13 Notes: 1. Each 'CB AUX SWITCH' should comprise either three normally open (52a) auxiliary switch contacts (one per pole), connected in series or three normally closed (52b) auxiliary switch contacts (one per pole), connected in parallel. 2. Each 'CB HEALTHY' contact is a contact on the circuit breaker which operates when the CB is ready to perform an auto-reclose cycle (for example, closing spring fully charged or gas pressure high). The contact can be either normally open or normally closed. 27 28 B26 B28 29 3. If two relays are main and backup autoreclose on the same feeder, terminal B21 on each relay can be energised by an 'Autoreclose in Progress' signal from the other relay, to provide mutual interlocking. 4. If auto-reclose is permitted only under specified conditions, eg parallel circuit in operation, B23 can be controlled by a contact which operates when the specified conditions are satisfied. Figure 3: LFAA 101 and 102: External connections to opto-isolator inputs 4 PS-1 H3 H4 PS-2 H5 H6 Note: Power supply failure alarm (see note) Module 1 Module 2 G3 G5 RL1 Under healthy operating conditions the power supply fail relay is held on. The following conditions will cause the relay to drop off: – loss of dc supply – loss of any internal dc rail voltage G1 G4 G6 RL2 G2 RL3 G11 G9 RL4-1 G15 G13 RL4-2 G19 G17 RL5-1 G12 G10 RL5-2 G16 G14 CB1 A/R lockout indication RL17 RL7 RL8 RL12 RL13 RL14 G20 G18 G24 G22 G28 G26 G8 G7 G23 G21 G27 G25 F1 F9 F11 CB1 'phases not together' protn. inhibit RL19 RL18 Trip CB1 3 phase F2 F10 F12 Close CB1 F8 F16 F18 'CB1 close' indication RL22 F14 F22 F24 Bridge CB1 trip circuits RL23 F20 RL24 F28 F26 Initiate sync. voltage selection CB1 F15 F17 RL28 F13 RL29 F27 F25 Not used CB1 maintenance alarm F21 F23 CB1 maintenance lockout RL30 E3 E5 'Auto-reclose in Progress' indication F7 F4 F6 RL21 RL6 Module 3 (LFAA 102 only) F3 F5 F19 Directional earth fault protection inhibit inhibit power swing blocking RL33 E1 E4 E6 Not used 'Auto-reclose in service' indication CB2 'phases not together' protn. inhibit RL34 E2 RL35 E11 E9 RL36-1 E15 E13 RL36-2 E19 E17 RL37-1 E12 E10 RL37-2 E16 E14 RL38 E20 E18 RL39 E24 E22 RL40 E28 E26 RL44 E8 E7 RL45 E23 E21 CB2 maintenance alarm RL46 E27 E25 CB2 maintenance lockout Inhibit zone 1 extension Not used CB2 A/R lockout indication Timer test Not used Trip CB2 3 phase Close CB2 'CB2 close' indication Bridge CB2 trip circuits Initiate sync. voltage selection CB2. CB2 control See input 29 description Figure 4: LFAA 101 and 102: External output contacts wiring Scheme lockout ● at the end of the three phase dead time the correct voltage monitor or check synchronism conditions are not satisfied within the pre-closing check time ● if the closing pulse ends without interruption and the circuit breaker is in the open position ● auto-reclose blocking is initiated ● for certain conditions after an interruption of dc supply Single breaker schemes (LFAA 101) Scheme lockout will block scheme initiation and operation, preventing automatic reclosure. It occurs for any of the following conditions: ● ● the circuit breaker is in the open position at the end of the reclaim time the protection operates during the reclaim time following the final shot ● if the protection relay has not reset or the circuit breaker has not tripped within the trip fail time 5 Two breaker schemes (LFAA 102) Circuit breaker lockout will block scheme initiation and operation of the relevant breaker, preventing automatic reclosure; it occurs for any of the following conditions: ● ● ● ● ● 6 ALARMS 1 AUTO RECLOSE OUT OF SERVICE if the auto-reclose of both breakers is successfully initiated, the autoreclose of the affected CB will lock out at the end of the reclaim time if either one or both breakers are in the open position if the auto-reclose of only one circuit breaker is in progress at the end of the reclaim time, the scheme will reset if this particular circuit breaker is in the closed position but lock out if it is in the open position if the relay is initiated during the reclaim time of a single shot programme or during the reclaim time following the final shot of a two shot programme, the relay will initiate three phase tripping and lock out both breakers will be locked out if the correct voltage monitor/synchronism check conditions have not occurred within the pre-closing check time. If the leader circuit breaker has successfully reclosed and the correct conditions have not occurred within the pre-closing check time after the expiry of the follower circuit breaker time, the follower circuit breaker will be locked out. the auto-reclose of the relevant circuit breaker will be locked out if that particular circuit breaker is in the open position when the closing pulse expires without interruption. If the auto-reclose of the leader circuit breaker locks out in this way, the follower circuit breaker will inherit the pre-closing check conditions originally selected for the leader circuit breaker. After the follower circuit breaker delay time, if the pre-closing check conditions are satisfied, the follower circuit breaker reclose pulse will be initiated. For subsequent scheme initiation with the leader circuit breaker in the lockout state, the follower circuit breaker will adopt the auto-reclose programme originally selected for the leader circuit breaker ALARMS 2 RELAY HEALTHY SET PARALLEL SELECT/RESET ACCEPT/READ SERIAL Figure 5: Operator interface ● both breakers will be locked out if auto-reclose blocking is initiated ● both breakers will be locked out if the protection relay has not reset or the circuit breakers have not tripped within the set ‘Trip Fail’ time after scheme initiation. The lock out condition is one of the conditions indicated by the ALARMS 1 indication on the front of the relay. Block auto-reclose This is an input which initiates blocking, causing three phase tripping and lock out. Manual closing of the circuit breaker – status alarms 1, indicated by the red led being stably lit This group includes the lock-out alarms – compound alarms, indicated by the red led flashing This group includes the maintenance lock-out alarm – status alarms 2, indicated by the amber led being stably lit This group includes the auto-reclose in progress alarm – change alarms, indicated by the amber led flashing This group includes the maintenance (pre-lockout warning) alarm If the circuit breaker is closed manually on to a fault, the autoreclose must be inhibited. An ‘initiation inhibit’ condition is activated when either of the circuit breakers moves from open to closed when there is no auto-reclose cycle in progress (ie, closed by manual control). The inhibit is removed when the circuit breaker has remained closed for the set manual close time. The alarms are enabled when the appropriate condition occurs in the ladder logic, and can then be read without removing the relay front cover, by a combination of keystrokes on the ACCEPT/READ and SELECT/RESET keys on the relay front panel. Switching auto-reclose relay in/out of service The fourth led (green) is the relay healthy indication. The LFAA relay can be switched in or out of service from a remote point. When out of service, the relay OUT OF SERVICE amber indicator lights on the front of the relay. Indications and alarms The relay has four light emitting diodes (led’s) on the front panel for indications and alarms. The top two (red and amber) are for alarms, which are in four groups: The third led (amber) is the out of service indication. Test facilities The LFAA relay provides the customer with the facility to test the following parameters: – to read the state (ie, on or off) of each input to, and output of, the relay – to monitor the operation of all timers via a dedicated input and output – with the front cover removed and the relay out of service, the state of each relay can be changed Relay inputs Input connections are shown in Figure 3. Input functions are as follows: 1. TERMINAL B1: When this input is energised, either momentarily or permanently, the autoreclose scheme is switched in to service, provided input terminal B3 is not also energised. 2. TERMINAL B3: When this input is energised, either momentarily or permanently, the autoreclose scheme is switched out of service. 3. TERMINAL B5: 4. TERMINAL B7: 5. TERMINAL B9: 6. TERMINAL B11: These inputs are energised by single phase or three phase trip repeat (A/R initiation) contacts on the protective relays. If the protection does not have a separate ‘3PH trip’ output, input 6 to terminal B11 is not required. 7. TERMINAL B13: This input may be energised by a contact on an intertrip receive repeat relay if a direct intertripping scheme is in use. If this input is energised, the auto-reclose relay will treat it as a three phase fault. 8. TERMINAL B15: This input is energised by the Block A/R contact of the feeder main protection (eg, output 96 on Micromho, Quadramho or Optimho). If B15 is energised at any time during an auto-reclose cycle, the scheme locks out. 9. TERMINAL B17: This input can be energised by a normally open or normally closed contact on a line voltage monitor relay, to provide a line voltage interlock. Please refer to publication R4085 or R4094 for full details. 10. TERMINAL B19: This input is used to start a timer test. Please refer to Service Manual R5920 or R5930 for full details. 11. TERMINAL B21: This is used when two relays operate in a main/backup arrangement. See Figure 3, Note 3. 21. TERMINAL B10: If this input is momentarily energised when CB1 auto-reclosing is locked out CB1 A/R will immediately reset, provided the condition which caused the lockout has been cleared. 22. TERMINAL B12: If this input is momentarily energised, the CB1 maintenance counter fault trips registers are reset to zero. 12. TERMINAL B2: INPUTS 23 TO 29 ARE USED ONLY ON LFAA 102: See Figure 3, Note 4. 23. TERMINAL B14: 17. TERMINAL B2: This input is energised by a normally open (52a) or normally closed (52b) auxiliary switch contact on the circuit breaker CB1. For circuit breakers with three separate single pole mechanisms, input 17 should be energised either by three 52a contacts (one from each pole) connected in series, or by three 52b contacts connected in parallel. Software function FNCT 14 should be set ON if 52a contacts are used, or OFF if 52b contacts are used. 24. TERMINAL B16: 18. TERMINAL B4: This input may be energised by a normally open or normally closed contact which indicates that the circuit breaker CB1 has sufficient stored energy (eg, oil or gas pressure, or spring fully charged) to perform a complete trip/auto-reclose cycle. Software function FNCT 15 should be set ON or OFF depending on the operating mode of the energy contact. If no such contact is available on the circuit breaker, this input may be left de-energised, and FNCT 15 set ON. 25. TERMINAL B18: 26. TERMINAL B20: 27. TERMINAL B22: 28. TERMINAL B24: Similar to corresponding inputs 17 to 22 but for CB2. 29. TERMINAL B26: When two adjacent circuits in the same bay of a one and a half switch S/S are each controlled by an LFAA 102 relay, the ‘CB2 CONTROL’ output (E7 - E8) on each relay should be connected to energise input 29 (B26) on the adjacent relay. This ensures that in the event of concurrent auto-reclose cycles on both circuits, the middle CB (CB2) can reclose only when the required conditions are satisfied for both LFAA relays. 19. TERMINAL B6: This input in energised by a normally open output contact on a voltage monitor (dead line charge, dead bus charge or synchronism check) relay, and must be live at the end of a three phase dead time (optional for first shot - see FNCT 11) before the CB close output can be given for CB1. 20. TERMINAL B8: This input may be energised by a normally open output contact on a separate synchronism check relay, if fast synchronising is required for CB1 - see publication R4085 or R4094 for full details. 7 Description - Hardware User Interface Description - Software The relay is housed in a 4U (178mm) high case suitable for either rack or panel mounting. The relay uses plug-in modules which are individually tested and calibrated in the factory. If necessary, modules can be exchanged without any need to recalibrate the relay. The front panel operator interface, shown in Figure 5, consists of a 2 row 16 character alphanumeric liquid crystal display (lcd) together with a seven push-button keypad. With the relay cover in position only the SELECT/RESET and ACCEPT/READ keys are accessible. Using just these two keys, it is possible to view system details, view (and clear) alarms, view counters, view settings, view the status of all opto-inputs and output relays and perform a timer test. A menu approach has been adopted such that the operator, using the lcd, can easily and efficiently access a whole range of useful information. The relay software is divided into three main groups: the system software, the logic controller software, and the scheme logic. A power supply module converts power from a dc supply to internal voltage rails. A power failure monitoring circuit with alarm output contact is provided. A status input module receives external plant status and protection equipment status signals via optoisolated inputs. A 16 bit microprocessor is used for sequence control and timing functions. It interfaces with the opto-isolated inputs and output relays via an address/data bus. Input and output connections are shown in Figures 3 and 4 respectively. The microprocessor module also contains non-volatile read/write memory (EEPROM) for settings and relay status information, read/write memory (RAM) for temporary data, and read-only memory (ROM) for the system and application software. The system software resides in one pair of ROM devices, and the application software in another, separate pair. By appropriate programming of the application ROM, either standard or special auto-reclose requirements can be satisfied. Two output relay modules are provided in a basic single breaker application (LFAA 101), and three output modules are provided in a basic two breaker application (LFAA 102). The power supply module converts the auxiliary dc voltage into the regulated dc voltage rails required by the relay. High efficiency and isolation from the auxiliary supply are achieved by the use of a switching dc/dc converter. A power fail monitoring circuit with two alarm output contacts is included. 8 Security related commands, such as changing settings, resetting counters and testing output relays are only available when the cover is removed, and can be blocked under certain specific conditions. See the service manual and scheme description for details of the conditions under which the commands are blocked. Five pushbuttons, arranged in a cruciform pattern, become accessible when the front cover is removed; four of these act as cursor keys for selecting commands or altering parameters in an easy to follow menu approach. The SET key at the centre is used to confirm entry of new settings. The test sockets can be used to send information about the relay to either a serial or a parallel printer. The user selects whether to transmit the information to the serial or parallel port. In addition, test points within the relay can be monitored on the parallel socket. Remote communications All the options available on the menu are also available from a local or remote terminal via an RS232C serial communication port. Sockets are provided on the front of the relay for temporary connection and on the rear for permanent connection. The rear socket can also interface with a modem for communication over a suitable link, for instance a telephone line. The system software is independent of the application and is common to all multi-modular hardware applications. It consists of various diagnostic, debugging, input/output, and multitasking handling facilities. It provides a common software environment within which different application programmes can be developed and operated. The logic controller operating system interfaces between the system software and the scheme logic of the application programme. It processes the status input information, updates the relay outputs and controls the operator interface. The scheme logic is the application programme, defining how a relay performs; it is presented in the form of a ladder diagram. The ladder is an easy to follow application diagram consisting of contacts, timers, counters and output relays. This approach means that the user does not need to understand complex programming languages in order to understand the relay application. Each relay scheme is fully documented including a copy of the ladder diagram appropriate to that scheme. Further Information Full details of the selectable autoreclose cycles and scheme options are given in separate publications: LFAA 101 Scheme Description R4085 LFAA 102 Scheme Description R4094 Technical Data Auxiliary voltage rating Auxiliary voltage Vx (1)(dc) Nominal (V) Operative range(V) (Relay power supply) 24/27 30/34 48/54 110/125 220/250 19.0 - 32.0 24.0 - 40.0 37.5 - 65.0 87.5 - 150.0 175.0 - 300.0 Auxiliary voltage Vx(2)(dc) Nominal (V) Operative range (V) (Opto-isolator supply) 24/27 30/34 48/54 110/125 220/250 19.0 - 32.0 24.0 - 40.0 37.5 - 65.0 87.5 - 150.0 175.0 - 300.0 Note: Vx (2) May be different from Vx (1) Burdens (maximum) Vx(1) or Aux supply (W) Add to auxiliary supply burden (W) Vx(2) (Volts) (No output relays on) Each input 24 27 30 34 48 54 110 125 220 250 8 8 8 8 8.5 8.5 8.5 9 10.5 11.5 0.025 0.030 0.030 0.040 0.060 0.090 0.110 0.150 0.250 0.350 Each output RLO-RL7 RL8-RL13 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 Timers Timer name Limits of settings (s) Accuracy: greater of 0.01–2.0 ± 2% or –10 + 20ms high speed three phase reclosing 0.01–200 ± 2% or –10 + 20ms delayed second shot three phase reclosing 1.0–300 ± 2% or –10 + 20ms 0.01–2.0 ± 2% or –10 + 20ms Dead Time high speed single phase reclosing Discrimination time Pre-closing check 1.0–200 ± 2% or –10 + 20ms Trip fail timer (LFAA 101) (LFAA 102) 0.01–200 1.0–200 ± 2% or –10 + 20ms ± 2% or –10 + 20ms Reclose pulse 0.01–2.0 ± 2% or –10 + 20ms Reclaim time 1.0–300 ± 2% or –10 + 20ms Manual close time 1.0–200 ± 2% or –10 + 20ms Intertrip time 1.0–300 ± 2% or –10 + 20ms LFAA 102 only Follower circuit breaker delay time (2 breaker schemes) 0.01–300 ± 2% or –10 + 20ms 9 Contacts Make and carry for 0.2s 7500VA (30A or 300V ac or dc maxima) Carry continuously 5A ac or dc Break AC 250VA DC 50W resistive 25W inductive, L/R = 40ms (Subject to maxima of 5A or 300V) Durability Loaded contact Unloaded contact 10,000 operations, minimum 100,000 operations minimum High voltage withstand Dielectric withstand IEC 255-5:1977 2kV rms for 1 minute between all case terminals connected together and the case earth terminal. 2kV rms for 1 minute between all terminals of independent circuits, with terminals on each circuit connected together. 1kV rms for 1 minute across normally open contacts. High voltage impulse IEC 255-5:1977 Three positive and three negative impulses of 5kV peak, 1.2/50µs, 0.5J between all terminals and all terminals and case earth. Electrical environment High frequency disturbance IEC 255-22-1:1988 Class III 2.5 kV peak between independent circuits and independent circuits and case earth. 1.0 kV peak across terminals of the same circuit (except metallic contacts). Fast transient disturbance IEC 255-22-4:1992 Class III 2kV, 5kHz applied directly to auxiliary supply 2kV, 5kHz applied directly to all inputs Electrostatic discharge IEC 255-22-2:1989 Class III IEC 801-2:1991 Level 3 DC supply interruption IEC 255-11:1979 EMC compliance 89/336/EEC EN 50081-2:1994 EN 50082-2:1995 8.0kV - discharge in air with cover in place. 6.0kV - point contact discharge with cover removed. The unit will withstand a 10ms interruption in the auxiliary supply, under normal operating conditions, without de-energising. Compliance with the European Commission Directive on EMC is claimed via the Technical Construction File route. Generic standards were used to establish conformity. Product safety 10 72/23/EEC Compliance with European Commission Low Voltage Directive EN 61010-1:1993/A2:1995 EN 60950:1992/A3:1995 Compliance is demonstrated by reference to generic safety standards. Atmospheric environment Temperature IEC 255-6:1988 Storage and transit -25°C to +70°C Operating -25°C to +55°C IEC 68-2-1:1990 Cold IEC 68-2-2:1974 Dry Heat Humidity IEC 68-2-3:1969 Enclosure protection IEC 529:1989 56 days at 93% RH and 40°C IP50 (dust protected) Mechanical environment Vibration IEC 255-21-1:1988 Response Class 1 Seismic IEC 255-21-3:1993 Class 1 438 Rack Mounting 483mm (19”) rack details dimensions to IEC297 7 max 31,75 ±0,4 Removable cover 432 Hinged front panel 12,7 ±0,4 Push button projection 10mm max 450 MIN 10 177 U scale U=44,45 101,6 10 465 483 Front 37 252 465,1 ±1,6 7 Allow a minimum of 50 for terminal block & wiring Side 10,6 Fixing hole detail 438 Tolerance between any two holes within a distance of 1mm±0,4 Panel Mounting Panel cut out detail 400 200 Removable cover 432 Hinged front panel Push button projection 10mm max 180,5 191 10 201 177 10 443 Front 37 252 Side 440 Fixing Holes Ø 5,4 Allow a minimum of 50 for terminal block & wiring All dimensions in mm Terminal screws: M4 x 8 brass cheese head with lockwashers are provided Mounting screws are not provided Figure 6: Case outlines Cases Type LFAA are housed in multi-module MIDOS cases. (See Figure 6). Information Required with Order Type of relay LFAA 101 or LFAA 102 Auxiliary supply voltages Vx(1) and Vx(2) Case mounting Rack or panel 11