ELB Series
15W, 30W
Emergency Lighting Units
Type: ________________
103/8"
(263 mm)
47/8"
(123 mm)
105/8"
(270 mm)
5"
(127 mm)
10"
(254 mm)
Side Mount Heads: Length 211/4", Height 51/2", Depth 4 7/8"
Attractive and conventional, the ELB
series is designed to be aesthetically
pleasing and unobtrusive in its
surroundings. Available in two sizes,
the ELB series is ideal for
applications where economy,
appearance and the use of a
conventionally designed unit is a
prime concern.
Standard Features
Model Numbers
• 6 volt, maintenance-free, lead-acid battery
• Dual voltage – 120/277VAC
ELB2
ELB4
• Automatic low voltage disconnect
Options (Add suffix to catalog number)
• Injection molded high impact, UV stabilized
thermoplastic
CVS
-BL
-EV2
-EAM2
-ECS
-NB
-T
-NH
• Standard white housing, optional black available
• Optional
self-testing electronics
• Thermally compensated charger
• Regulated charge voltage
• Reverse polarity protection
• Filtered charger output
• Short circuit and brownout protection
• AC lockout
• Test switch and AC-On light
• Capable of powering remote lampheads
• T-5 incandescent lamps
• Temperature range: 20°C to 30°C (68°F to 86°F)
• UL924 Listed
(6V, 15W)
(6V, 30W)
Continuous Verification System(1)(4)
Black housing
Voltmeter(3)
Ammeter(3)
Auxiliary 2-conductor AC line cord (120VAC)
NiCad battery(4)
Halogen lamp option(2)
No lampheads(5)
(1) Add "CVS" self-test option suffix immediately after base model number.
Example: ELB4CVS
(2) Specify voltage and wattage when ordering. See "Optional Lamps" below.
(3) Choice of EV2 or EAM2, not both.
(4) CVS not available with NiCad battery option.
(5) Not available on ELB2 model.
Accessories (Order Separately)
41G
40G
PELH
PELHD
Wire guard (side mounted lampheads)
Wire guard (top mounted lampheads)
Matching remote head - single(6)
Matching remote head - twin(6)
(6) Supplied with mounting plate.
Specify voltage and wattage when ordering.
Example: PELHD0612
See Remote Fixtures data sheet 0601888.
ELB Series
Emergency Lighting Unit
Housing
Compact size. Molded from high impact mar-resistant
thermoplastic. The unit has a textured white finish. Tamperresistant screws are standard. A universal mounting pattern
and keyhole slots are provided on the backplate to make
installation simple. Knockouts on the top and side are
provided for conduit feed.
Light Source
The ELB series is furnished standard with two 6 volt, 7.2
watt T-5 incandescent lamps. Fully directional, injection
molded lampheads will remain in place once they are aimed
in desired direction.
6 Volt, 7.2 Watt, T-5 Lamp
Horizontal Distribution
10
Feet
Left
LAMP
AXIS
0
IFC
0.5
0.2
0.3
0.1
10
10
20
30
40
50
60
Limited Warranty
Unit
Full
3
3
5
Description
ELB Series
with NiCad battery option
with CVS option
Warranty In Years
Battery
Full
Pro-Rata
1
5
1
9
2
4
Batteries must be placed in service or recharged within nine
(9) months from factory shipment date. This warranty only
applies when the product is used as intended. Any abuse or
misuse contrary to normal installation or operation shall void
this warranty.
Feet
Right
0
Transfer to emergency operation is completely automatic
upon failure of utility AC voltage. A brownout circuit is
provided and a low voltage disconnect circuit prevents deep
discharge damage to the unit battery during prolonged power
outages. An AC lock-out prevents battery discharge before
the unit is energized with AC power. Full battery recharge
occurs in compliance with UL 924 specifications. A universal
120/277VAC, 60Hz input transformer, test switch and long
life AC pilot light are all provided standard.
70
Feet From Lamp (measured on axis)
Optional Lamps
To order non-standard lamps, suffix catalog number.
Example: ELB4-T0612
Battery
A 6 volt maintenance free lead-acid battery is provided. The
battery is completely sealed and it is never necessary to add
water.
Electronics
A solid-state charger is standard. Charger voltage is
regulated to ±1% of nominal system voltage. The charger is
current limited, temperature compensated, and protected
against short circuit and reverse polarity conditions.
Suggested Specifications
Self contained emergency lighting unit shall be Prescolite
Life Safety Products model(ELB2)(ELB4). The unit shall
supply the rated load for a minimum of 11/2 hours to not
less than 871/2% of rated battery voltage. The unit shall be
rated 120/277VAC, 60 Hz and be listed with Underwriters
Laboratories to Standard 924. The emergency power source
shall be a fully rechargeable maintenance-free 6 volt leadacid battery. The housing shall be constructed of high impact
thermoplastic. Electronics shall include a solid state charger
with regulated charge voltage, current limitation, temperature
compensation and short circuit protection. A low voltage
disconnect and AC lock-out will also be included in the
electronics. Illumination shall be provided by two 7.2 watt T-5
incandescent lamps housed in fully directional, high impact
thermoplastic lamphead assemblies.
Product Selector Guide
Electrical
†
Base
Catalog
Number
Output
Volts
Output Watts
1.5
2
3
4
Hours Hours Hours Hours
ELB2
6
15
11
8
6
ELB4
6
30
22
15
12
AC Input†
Volts
Amps
Watts
120
.070 (.078)
8.4 (9.36)
277
120
.032 (.039)
.070 (.114)
8.8 (10.8)
8.4 (13.68)
277
.032 (.051)
8.8 (14.1)
Standard Remote
Lamp Capability
7.2W
No
7.2W
Yes
AC input rating with parentheses ( ) are for NiCad units.
60 Fieldstone Court • Cheshire, CT • U.S.A. • Phone (203) 699-2000 • Fax (203) 699-2060
A Hubbell Lighting, Inc. brand with representatives’ offices in principal cities throughout North America.
©
Copyright Prescolite Life Safety Products, All Rights Reserved • Specifications subject to change without notice. • Printed in U.S.A.
0601880
7/03