APOLLO SOLAR CHARGE CONTROLLERS
USE OF SHUNT, SHUNT BOARD, AND ASNET CONNECTIVITY KIT
BASIC OVERVIEW
The basics are simple: The T80 and T100 TurboCharger products include the hardware and
software to measure and display the State of Charge (SOC) of the Battery. The method used
is considerably more practical and accurate than simply measuring battery voltage because
the battery voltage in typical systems will read very high when the battery is being charged
and read very low when the battery is simply being used by the load. (The only way to
depend on the voltage is to disconnect the battery from both loads and charging devices, let it
settle for 20 minutes and then take accurate readings and adjust for temperature.) Since this
is impractical in real systems, Apollo Solar uses a method which continually measures the
current going into the battery from all charging devices and the current going out of the battery
to all loads.
USE OF THE SHUNT AND SHUNT BOARD
The Charge Controller determines when the battery is completely charged as it goes into Float
mode and resets the SOC accumulator. Then the SHUNT measures the current going out of
or into the battery on a continuous basis. The results are displayed on the LCD of the T80
TurboCharger and on the Remote Display when used. The Shunt is wired in series with the
negative lead of the battery. See diagram below:
SHUNT WIRING DETAIL
_
FROM THE
+ T80 TurboCharger
BATTERY TERMINALS
MODULAR CABLE WITH6 PIN RJ-11
AT BOTH ENDS PLUGS INTO THE
CONTROL PC BOARD IN THE T80.
OUTPUT TO DC
LOAD BREAKER
+
This diagram shows a
pair of 12 volt batteries.
The T80 works with 12,
24 or 48 volt battery
systems.
APOLLO
SHUNT
BOARD
_
+Bat
FUSE
-Bat
SHUNT 50mV
500AMP
Temperature
TEMPERATURE SENSOR
(Stick between batteries below
top of the electrolyte level .)
BATTERY VOLTAGE
SENSE WIRES WITH FUSE
(Must be connected across
the full battery voltage .)
NOTE: The Shunt must
be the only item wired
directly to the battery
negative terminal .
Please see the User Manual of the Apollo Solar T80 TurboCharger for detailed instructions.
_______________________________________________________________________
23 F. J. Clarke Circle
Apollo Solar, Inc.
Phone (203) 790-6400
Bethel, CT 06801
www.ApolloSolar.com
fax (203) 792-0300
Page 2 of 3
APOLLO SOLAR: USE OF SHUNT, SHUNT BOARD, AND ASNET
PARALLEL CHARGE CONTROLLERS
Since all the battery current must pass through a single SHUNT, there will only be one shunt
in any system. When the system uses multiple T80 TurboChargers connected in parallel, the
ASNET Option Cards (T80 Network Option Cards) are used to tie them together. Only ONE
SHUNT with ONE SHUNT Board is used to measure the total accumulated current.
The figure immediately below is a simplified wiring diagram of the CAT 5 (Ethernet type) cable
used to connect the T80 TurboChargers together in parallel using the ASNET Option Cards.
The figure also shows the connection of multiple T80s to a single Shunt.
UP TO 15 SLAVE T80s CAN
BE WIRED TO 1 MASTER
NETWORK
MASTER
SLAVE 1
SLAVE 2
T80
TURBO
CHARGER
T80
TURBO
CHARGER
T80
TURBO
CHARGER
CAT 5 CABLE WIRED AS
DAISY CHAIN FROM
MASTER TO SLAVE.
SHUNT CABLE
PLUGGED IN
MAKES THIS T80
THE MASTER
A REMOTE DISPLAY MAY
BE WIRED TO EITHER END
OF THE CHAIN.
CAT 5
CABLE
3 PAIR CABLE
TO APOLLO
SHUNT BOARD
APOLLO T80
NETWORK
OPTION CARD
CAT 5
CABLE
CAT 5
CABLE
REMOTE
DISPLAY
BREAKER
TO INVERTERS,
BREAKERS AND
LOADS
APOLLO
SHUNT
BOARD
Please see the Apollo Solar T80 TurboCharger Installation Manual that comes with the
ASNET Option Card for detailed instructions of set up and programming for parallel operation.
__________________________________________________________________________
23 F. J. Clarke Circle
Apollo Solar, Inc.
Phone (203) 790-6400
Bethel, CT 06801
www.ApolloSolar.com
fax (203) 792-0300
Page 3 of 3
APOLLO SOLAR: USE OF SHUNT, SHUNT BOARD, AND ASNET
The figure below is the complete wiring diagram showing all the connections to the Apollo
Solar T80 TurboChargers in parallel operation.
MULTIPLE INDEPENDENT
MPPT INPUTS
GFDI
GFDI
80A
DC
80A
DC
80A
DC
NETWORK
MASTER
SLAVE 1
SLAVE 2
APOLLO
TURBO
CHARGER
APOLLO
TURBO
CHARGER
APOLLO
TURBO
CHARGER
APOLLO
NETWORK
OPTION CARD
SHUNT CABLE
PLUGGED IN
MAKES THIS
TURBOCHARGER
THE MASTER
CAT 5 CABLE WIRED AS
DAISY CHAIN FROM
MASTER TO SLAVE.
CAT 5
CABLE
CAT 5
CABLE
BREAKER
CAT 5
CABLE
BREAKER
A REMOTE DISPLAY MAY
BE WIRED TO EITHER END
OF THE CHAIN.
BREAKER
3 PAIR CABLE
TO APOLLO
SHUNT BOARD
UP TO 15 SLAVE
TURBOCHARGERs CAN BE
WIRED TO 1 MASTER
POS
BUS
REMOTE
DISPLAY
BREAKER
TO INVERTERS,
BREAKERS AND
LOADS
APOLLO
SHUNT
BOARD
BATT VOLTAGE
SENSE WIRES
(REQUIRED)
NEG BUS
BATTERIES
12V, 24V or 48V
500A
SHUNT
BATT TEMP
SENSOR
FUSE
__________________________________________________________________________
23 F. J. Clarke Circle
Apollo Solar, Inc.
Phone (203) 790-6400
Bethel, CT 06801
www.ApolloSolar.com
fax (203) 792-0300