Function Guide for the GOLD, Xzone
1. General
2. Material Specification
The Xzone function is designed for controlling one extra
temperature zone via the ventilation system.
Sometimes it is necessary to control a part of the ventilation system with different temperature prerequisites.
This may be due to proximity to the perimeter wall of the
building facing north or south; workshop, office or other
conditions that give rise to different temperature loads in
various parts of a building.
The Xzone function can control one extra temperature
zone, max.
Xzone can be used for all types of GOLD air handling unit
with program version 5.00 or later, and both postheating
and cooling can be controlled in the extra zone.
When Xzone is activated, several menus appear in the
hand-held micro terminal under user level for setting and
reading the extra zone parameters.
The type of temperature control for the extra zone must
be selected separately, and can be of another type than
that used in the main zone.
If extract air temperature control is selected, the temperature sensors must be positioned so that they will not
be influenced by the temperature in the other zone. This
means that the internal extract air sensor (inside the air
handling unit) must not be used for control for the main
zone. The room sensor or extra extract air sensor should
be used, (see TBLZ-1-30 or TBLZ-1-24 in section Material
Specification).
The air heater and air cooler for the main and extra zone
must be sized on the basis of separate computerized
calculations. Always take into account that the duct system where the air heater and air cooler are fitted, does
not have the same dimensions as the connection spigots/
frames of the air handling unit.
We reserve the right to alter specifications.
Air handling unit: GOLD RX/PX/CX/SD
Xzone Control box TBLZ-1-50-a-b-cc
Consists of:IQnomic Plus, TBIQ-2-1, heating
IQnomic Plus, TBIQ-2-1, cooling
Comm. cable BC1-1 (L=250mm)
Code:a 0 = Without freeze protection monitor sensor
1 = With freeze protection monitor sensor
b 1= With supply air temperature sensor
2 = With supply air and extract air temperature sensor
3 = With supply air and room air temperature sensor
cc 01 = With 1 metre long communication cable
03 = With 3 metre long communication cable
05 = With 5 metre long communication cable
10 = With 10 metre long communication cable
15 = With 15 metre long communication cable
Supply air temperature sensor, set (TBLZ-1-30), according
to selection above consists of the following:
Duct temperature sensor 32106304
Jack for wall mounting 019611
Extract air temperature sensor, set (TBLZ-1-30), according
to selection above consists of the following:
Duct temperature sensor 32106304
Jack for wall mounting 019611
Room temperature sensor (TBLZ-1-24), according to selection above.
When the heater is electric of type Swegon standard incl.
control cable:
Adaptor modular/terminal
TBLZ-1-55
www.swegon.com
1
GB.XZONE.120522
3. Operation
The Xzone function requires två IQnomic Plus modules
for wiring temperature sensors as well as an air heater for
postheating and an air cooler. The wiring of temperature
sensors to the IQnomic Plus requires the presence of both
modules in the system even if there is only one air heater
or one air cooler in the zone.
Connect a cable for 0-10 V DC control of valve actuator - heating and cables for control of the pump for the
reheater (if any), supply air temperature and freeze protection monitor sensors to the IQnomic Plus module
A (function selector switch = A). If an electric air heater
is used, connect the overheating protection alarm signal
cable to the input of the freeze protection monitor sensor.
Connect a cable for 0-10 V DC control of the valve actuator cooling or air cooler for cooling in 1 - 3 steps or cooling pump control and extract air/room air sensors to the
IQnomic Plus module B (function selector switch = B).
The Xzone for heating and Xzone for cooling must each
be activated separately. The type of control signal for the
heating and cooling function respectively must be selected
individually.
Temperature control for the Xzone operates completely
separated from the temperature control of the main zone.
If an air heater for postheating with freeze protection
monitor is selected for the extra zone, the heat retaining
function operates completely separately. The heat retaining and alarm limit values preset at service level are applicable to both the extra zone and the main zone.
2
www.swegon.com
The cooling min. flow function applies to the flow from
the air handling unit, not the flow for each zone.
When the total flow reaches below the preset value, cooling will be blocked in both zones.
If intermittent night-time operation is activated, the conditions in the main zone are controlled according to the
settings of the function. When the air handling uit starts
up, the extra zone is controlled according to ordinary temperature control settings.
Connect the cable of the air heater for main zone postheating to the ordinary heating output on the GOLD
air handling unit control unit. Connect the main zone’s
cooling control cables to the ordinary cooling outputs on
the GOLD air handling unit control unit. Connect the air
heater of the extra zone to the screw connection terminals
of the IQnomic Plus module. The heating output cannot
have modular connection and if standard coils for GOLD
with modular connection are used for the extra zone, the
cable will have to be cut.
Important!
The function with output power reduction (for an electric
air heater), activated in the event of low airflows for protecting the heater elements from overheating, is blocked
when the Xzone is selected. Since the control system
cannot measure the flow in the different zones, the function is blocked both for the extra zone and the main zone.
We reserve the right to alter specifications.
GB.XZONE.120522
4. Electrical connections
Jack for wall mounting, 019611
IQnomic Plus module
Valve actuator, cooling
or air cooler 0-10 V
Air heater for hot water
1)
Temp. sensor**
supply air
Temp. sensor**
extract air/room
1)
Jack for wall mounting, 019611
Freeze protection monitor sensor**
R1
RD
T1
GR
R1
RD
T1
GR
Data GND
Valve actuator, heating
G G0 Y
24 V AC*
IQnomic Plus
module A
24 V AC*
–
S
Brown
White
G G0 Y
– S – S
– S – S
13 14 15 16 17 18 19 20 21 22 23 24
13 14 15 16 17 18 19 20 21 22 23 24
F 012
L1
L2
BCDE
1 2 3 4 5 6 7 8 9 10 11 12
Control of pump
for heating
Control of cooling step 1
or pump in cooling circuit
IQnomic Plus
module B
Function selector
switch in position B
34 5 6
7 89A
7 89A
F 012
34 5 6
BCDE
Function selector
switch in position A
Communication cable to the
control unit of the air handling unit, where it must be
connected to one of the connections for Internal EIA-485.
Room sensor
* The 24 V AC powersupply conductors can
1 2 3 4 5 6 7 8 9 10 11 12
be connected to Terminals 60 (G) and 61 (G0)
in the control unit of
the air handling unit.
** Digital temperature
sensors require correct polarity. Be careful
Communication cable
when you wire the
between modules.
conductors.
L1
L2
Control of cooling step 2
1 2 3 4 5 6 7
Pump controls
Supply voltage to 1-phase pump, max 1.5 A, can be obtained by wiring
to the following terminals inside the GOLD air handling unit:
Terminal 101 (L), terminal 102 (N).
PE N L
We reserve the right to alter specifications.
www.swegon.com
3
GB.XZONE.120522
Electric air heater
Swegon Standard with control cable
Jack for wall mounting, 8-pole
BL
OR
BK
RD
Temp. sensor,**
supply air
WH
BR
YL
GR
Overheating
protection
0-10 V
– S – S
13 14 15 16 17 18 19 20 21 22 23 24
F 012
L1
L2
L1
L2
1 2 3 4 5 6 7 8 9 10 11 12
BCDE
Control of cooling step 2
www.swegon.com
Function selector
switch in Position B
34 5 6
Control of cooling step 1
or pump in cooling circuit
4
IQnomic Plus
Module B
7 89A
7 89A
F 012
34 5 6
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7
Room sensor
24 VAC*
– S – S
Function selector
switch in Position A
T1
GR
G G0 Y
13 14 15 16 17 18 19 20 21 22 23 24
PE N L
R1
RD
GR
Data GND
IQnomic Plus
Module A
Communication cable to the
control unit of the air handling unit, where it should be
connected to one of the connections for Internal EIA-485.
Jack för väggmontage, 019611
Valve actuator,
cooling or cooT1 ling 0–10 V
R1
RD
24 VAC***
G0
Temp. sensor,** extract air
BCDE
Electric air
heater Swegon Standard
with control
cable, 0–10 V,
pause/pulse
Jack for wall mounting, 019611
Pump controls
Supply voltage to 1-phase pump, max 1.5 A,
can be obtained by wiring to the following
terminals inside the GOLD air handling unit:
Terminal 101 (L), terminal 102 (N).
Communication cable between modules.
* The 24 V AC power-supply conductors can be
connected to Terminals 60 (G) and 61 (G0) in
the control unit of the air handling unit.
** Digital temperature sensors require correct
polarity. Be careful when you wire the conductors.
*** Electrical air heater above 36 kW 440 V
and above 27 kW 230 V (Norway) demand
supply voltage 24 VAC to internal control equipment. Supply voltage 24 VAC can be connected
on the AHU control unit, terminal block 60 (G)
and 61 (G0).
We reserve the right to alter specifications.
GB.XZONE.120522
5. Adjustment.
For basic particulars on how to handle the hand-held
micro terminal, see the Operation and Maintenance
Instructions for the GOLD unit.
INSTALLATION
FUNCTIONS
*FUNCTIONS*
TEMPERATURE
FLOW/PRESSURE
FILTER
The Xzone function must be manually activated, under
INSTALLATION – FUNCTIONS – IQNOMIC PLUS in the
hand-held terminal.
OPERATION
HEATING
COOLING
MOISTURE
ReCO2
IQNOMIC PLUS
If postheating is required in the extra zone, activate No. A
XZONE HEATING by selecting what type of air heater is to
be connected, under FUNCTION ON/OFF.
*IQNOMIC PLUS*
NO. 9 PREHEATING
NO. A XZONE HEATING
NO. B XZONE COOLING
*XZONE HEATING*
FUNCTION OFF/ON
DEACTIVATE
EL AIR HEATER, P/P
EL AIR HEATER, 0 - 10 V
WATER COIL WITH FP
WATER C. WITHOUT FP
If cooling is required in the extra zone, activate No. B
XZONE HEATING by selecting control function under
FUNCTION ON/OFF.
*IQNOMIC PLUS*
NO. 9 PREHEATING
NO. A XZONE HEATING
NO. B XZONE COOLING
*XZONE COOLING*
FUNCTION OFF/ON
SETTINGS
DEACTIVATE
STEPLESS 0 = 10 V
STEPLESS 10 = 0 V
ON/OFF, 1 STEP
ON/OFF, 2 STEPS
ON/OFF, 3 STEPS BINARY
The neutral zone required between the heating and cooling sequences must be set under SETTINGS.
We reserve the right to alter specifications.
*XZONE COOLING*
NEUTRAL ZONE
2.0°C.
www.swegon.com
5
GB.XZONE.120522
When one of the functions XZONE HEATING or XZONE
COOLING is activated, a new menu image is displayed in
the hand-held micro terminal: TEMP.CTRL.XZONE, under
INSTALLATION – FUNCTIONS - TEMPERATURE”.
*TEMPERATURE*
TEMPERATURE CTRL
TEMP.CTRL. Xzone
OUTD TEMP COMP.
The extra zone has the same settings as the ordinary menu
of the air handling unit for the setting temperature control
modes.
*TEMP.CTRL.XZONE*
ERS CONTROL 1
OTHERS?
ERS CONTROL
SUPPLY AIR CONTROL
EXTRACT AIR CONTROL
A new menu group XZONE is displayed between TEMPERATURE and FLOW/PRESSURE under SETTINGS at user
level. The selected temperature control function setpoint
settings required for for the extra zone can be set there.
XZONE
*XZONE*
READINGS
SETTING
6
www.swegon.com
We reserve the right to alter specifications.
GB.XZONE.120522
Performance checks
F 012
A flashing light-emitting diode L1 indicates correct communication with the GOLD unit’s control unit.
13 14 15 16 17 18 19 20 21 22 23 24
34 5 6
7 89A
IQnomic Plus module:
Light-emitting diode L2 lit with a steady glow indicates
that power is being supplied from the GOLD unit’s control
unit.
BCDE
6.
L1
L2
1 2 3 4 5 6 7 8 9 10 11 12
L1
L2
Temperature sensor:
Current temperatures can be read under INSTALLATION
– READINGS – IQNOMIC PLUS – XZONE HEATING/XZONE
COOLING. If the temperature readings are resonable,
wiring has been carried out correctly.
If the functions are activated but the accessories have not
been connected correctly, an alarm will be initiated. See
the Operation and Maintenance Instructions for the GOLD
unit for a description of each alarm.
We reserve the right to alter specifications.
www.swegon.com