Transcript
BSX
TM
Self-Regulating Heating Cable
Product Specifications
Application . . .
1
Freeze Protection or Process Temperature Maintenance
BSX self-regulating heating cables are designed to provide
freeze protection or process temperature maintenance to
metallic and nonmetallic piping, tanks and equipment.
2
3
The heat output of BSX cable varies in response to the
surrounding conditions along the entire length of a circuit.
Whenever the heat loss of the insulated pipe, tank or
equipment increases (as ambient temperature drops), the
heat output of the cable increases. Conversely, when the
heat loss decreases (as the ambient temperature rises or
product flows), the cable reacts by reducing its heat output.
This self-regulating feature allows BSX to be overlapped
without temperature upset damage to the cable.
4
5, 6
BSX cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.
Construction . . .
Ratings . . .
Available Watt densities .............. 9, 15, 25, 32 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac
Maximum maintenance temperature ............................. 65°C
Maximum continuous exposure temperature
Power-off .................................................................. 85°C
Minimum installation temperature .... -40°C (OJ); -51°C (FOJ)
Minimum bend radius ................................................ 32 mm
T-rating 2
9, 15, 25 W/m .................................................... T6 85°C
32 W/m ............................................................. T5 100°C
Based on stabilised design 3 ................................ T6 85°C
Basic Accessories 4 . . .
1 Nickel-Plated Copper Bus Wires (1.3 mm2)
2 Radiation Cross-Linked Semiconductive
Heating Matrix
3 Radiation Cross-Linked Dielectric Insulation
4 Tinned Copper Braid
5 Polyolefin overjacket provides additional
protection where exposure to aqueous
inorganic chemicals is expected.
Options . . .
6 FOJ Fluoropolymer overjacket provides
additional protection where exposure
to organic chemicals or corrosives is
expected.
Power Connection: All BSX cables require a TBX-3L power
boot for terminating the circuit before connecting to power..
End-of-Circuit Termination: All BSX cables require the use
of the ET-6 end cap and ET-60 overcap for terminating at
the end of the circuit.
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
2. T-rating per internationally recognised testing agency guidelines.
3. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without limiting thermostats. The T-rating may be determined using CompuTrace® Electric Heat
Tracing Design Software or contact Thermon for design assistance.
4. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
BSX
TM
Self-Regulating Heating Cable
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type1 . . .
The power outputs shown apply to overjacketed cable
installed on insulated metallic pipe at the service voltage
stated below.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and
earth-fault protection should be based on applicable local
codes. For information on design and performance on
other voltages, contact Thermon.
Product Type
230 Vac Nominal
Power Output at 10°C
W/m
BSX 3-2
9
BSX 5-2
15
BSX 8-2
25
BSX 10-2
32
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
Type B Circuit Breakers
230 Vac Service Voltage
Product
Type
BSX at 230 Vac
40
35
BSX 3-2
BSX 10-2
Watts per Metre
30
BSX 5-2
25
BSX 8-2
20
BSX 8-2
15
BSX 5-2
10
BSX 3-2
5
BSX 10-2
0
0
10
20
30
40
60 65
50
Pipe Temperature °C
Product
Type
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
BSX 3-2
02 ATEX 0132424
BSX 5-2
Factory Mutual Research
Hazardous (Classified) Locations
BSX 8-2
Underwriters Laboratories Inc.
Hazardous (Classified) Locations
BSX has additional hazardous area approvals including:
BSX 10-2
• DNV • Lloyd’s • SAA • JIS • CCE/CMRS
Contact Thermon for additional approvals and specific
information.
Max. Circuit Length3 vs. Breaker Size
Metres
16 A
191
191
156
127
117
117
98
80
93
93
74
61
67
58
45
37
25 A
226
226
226
199
184
184
153
125
146
146
116
95
105
91
71
58
32 A
226
226
226
226
184
184
184
160
146
146
146
122
120
117
91
75
Type C Circuit Breakers
230 Vac Service Voltage
Certifications/Approvals . . .
II 2 G/D EEx e II T5 or T6
Start-Up
Temperature2
°C
10
0
-20
-40
10
0
-20
-40
10
0
-20
-40
10
0
-20
-40
Start-Up
Temperature2
°C
10
0
-20
-40
10
0
-20
-40
10
0
-20
-40
10
0
-20
-40
Max. Circuit Length3 vs. Breaker Size
Metres
16 A
191
191
156
127
117
117
98
80
93
93
78
64
77
75
59
48
25 A
226
226
226
199
184
184
153
125
146
146
122
100
120
117
92
75
32 A
226
226
226
226
184
184
184
160
146
146
146
128
120
120
118
96
Note . . .
1. Maximum circuit lengths shown are based on an instantaneous trip current characteristic per IEC 60898 at the referenced start-up temperature and a 10°C maintenance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
2. While a heat tracing system is generally designed to keep the contents of a pipe at
the desired maintain temperature, the cable may be energized at lower temperatures.
For design data with lower start-up temperatures than represented above contact
Thermon for design assistance.
3. The maximum circuit length is for one continuous length of cable, not the sum of
segments of cable. Refer to CompuTrace® design software or contact Thermon for
current loading of segments.
Form TEP0067U-0403 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
RSX 15-2
TM
Self-Regulating Heating Cable
Product Specifications
Application . . .
Freeze Protection or Process Temperature Maintenance
RSX 15-2 self-regulating heating cable is designed for
applications where the Watt density requirements preclude
the use of the standard range of winterization cables. The
cable is ideally suited for freeze protection or process
temperature maintenance applications that have higher heat
losses but are not exposed to high temperatures (such as
steam cleaning).
1
2
3
The ends of RSX 15-2 must be properly terminated prior to
connecting the cable to power. Refer to the “Self-Regulating
Cables Systems Accessories” product specification sheet
(Form TEP0010U).
4
RSX 15-2 is approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.
5, 6
Ratings . . .
Available Watt density ................................. 48 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac
Maximum maintenance temperature ............................. 65°C
Maximum continuous exposure temperature
Power-off .................................................................. 85°C
Minimum installation temperature .... -40°C (OJ); -51°C (FOJ)
Minimum bend radius ................................................ 32 mm
T-rating2 .................................................................. T5 100°C
Construction . . .
1 Nickel-Plated Copper Bus Wires (2.1 mm2)
2 Radiation Cross-Linked Semiconductive
Heating Matrix
3 Radiation Cross-Linked Dielectric Insulation
4 Tinned Copper Braid (BC)
Options . . .
5 OJ Polyolefin Overjacket
6 FOJ Fluoropolymer Overjacket
Power Output Curve . . .
60
Circuit Breaker Sizing . . .
55
Max. Circuit Length
vs. Breaker Size
Start-Up
Product
M
e
t
r
es (C-Type Breakers)
Temperature
Type
16 A 25 A 32 A 40 A
°C
10
35
56
74
98
RSX 15-2
0
33
53
71
93
-20
30
48
63
82
230 Vac Service Voltage
50
Watts per Metre
45
40
35
RSX 15-2
30
Certifications/Approvals . . .
25
Factory Mutual Research
Hazardous (Classified) Locations
20
15
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
10
0
10
20
30
40
Pipe Temperature °C
50
60 65
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
2. T-rating per internationally recognised testing agency guidelines.
Contact Thermon for additional approvals and
specific information.
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
RSX 15-2 has additional hazardous area
approvals including:
• DNV
• Lloyd’s
• SAA
• JIS
• CCE/CMRS
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
Form TEP0048U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
KSX
TM
Self-Regulating Heating Cable
Product Specifications
Application . . .
Process Temperature Maintenance or Freeze Protection
High performance KSX self-regulating heating cables are
designed specifically for high heat loss freeze protection
applications or process temperature maintenance where
steam cleaning is not required.
1
2
The heat output of KSX cable varies in response to the
surrounding temperature by reducing its thermal output
with increasing temperature.
3
KSX cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.
4
Ratings . . .
Available watt densities ......................... 48, 64 W/m @ 10°C
Nominal supply voltages1 .......................................... 230 Vac
Max. maintenance or exposure temperature
Continuous power-on ............................................. 121°C
Minimum installation temperature ............................... -60°C
Minimum bend radius ................................................ 32 mm
T-rating2 ................................................................. T3 200°C
Based on stabilised design3 ................................. T4 to T6
Basic Accessories4 . . .
Power Connection: All KSX cables require a TBX-4L power
connection boot for terminating the circuit before connecting to power.
End-of-Circuit Termination: KSX cables require the ET-8
end cap and ET-80 overcap for terminating at the end of the
circuit.
Construction . . .
1 Nickel-Plated Copper Bus Wires (1.3 mm2)
2 Semiconductive Heating Matrix and
Fluoropolymer Dielectric Insulation
3 Tinned Copper Braid
4 Fluoropolymer overjacket provides
additional protection to cable and braid
where exposure to chemicals or corrosives
is expected.
Product Features . . .
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
2. T-rating per internationally recognised testing agency guidelines.
3. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without
limiting thermostats. The T-rating may be determined using CompuTrace® Electric
Heat Tracing Design Software or contact Thermon for design assistance.
4. Information on additional accessories to complete a heater circuit installation and to
comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).
• Withstands continuous flamibility testing
according to IEC 60332-1: 1993
• Allows cable to be installed at temperatures
to -60°C
• Termination for system tested for ozone
stability, UV stability and flammability testing
according to ISO/IEC requirements
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
KSX
TM
Self-Regulating Heating Cable
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type1 . . .
The power outputs shown apply to overjacketed cable
installed on insulated metallic pipe at the service voltage
stated below.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and earthfault protection should be based on applicable local codes.
For information on design and performance on other
voltages, contact Thermon.
Product Type
230 Vac
Nominal
Power Output
at 10°C
W/m
KSX 15-2
48
KSX 20-2
64
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
Type B Circuit Breakers
230 Vac Service Voltage
KSX at 230 Vac
Product
Type
70
60
KSX 15-2
KSX 20-2
Watts per Meter
50
40
KSX 20-2
KSX 15-2
30
Start-Up
Temperature2
°C
10
0
-20
-40
10
0
-20
-40
Max. Circuit Length3 vs. Breaker Size
Metres
16 A
46
44
39
35
27
25
23
21
25 A
76
72
63
56
43
40
36
33
32 A
94
94
83
73
56
53
47
42
Type C Circuit Breakers
230 Vac Service Voltage
20
Product
Type
10
0
0
30
60
90
Pipe Temperature °C
KSX 15-2
KSX 20-2
Certifications/Approvals . . .
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
II 2 G/D EEx e II T3
120
02 ATEX 0148864
Factory Mutual Research
Hazardous (Classified) Locations
Underwriters Laboratories Inc.
Hazardous (Classified) Locations
Start-Up
Temperature2
°C
10
0
-20
-40
10
0
-20
-40
Max. Circuit Length3 vs. Breaker Size
Metres
16 A
46
46
46
43
36
36
36
35
25 A
76
76
76
71
59
59
59
56
32 A
94
94
94
94
78
78
78
74
Note . . .
1. Maximum circuit lengths shown are based on an instantaneous trip current
characteristic per IEC 60898 at the referenced start-up temperature and a 10°C
maintenance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
2. While a heat tracing system is generally designed to keep the contents of a pipe at
the desired maintain temperature, the cable may be energized at lower temperatures.
For design data with lower start-up temperatures than represented above contact
Thermon for design assistance.
3. The maximum circuit length is for one continuous length of cable, not the sum of
segments of cable. Refer to CompuTrace® design software or contact Thermon for
current loading of segments.
KSX has additional hazardous area approvals including:
• DNV • Lloyd’s • SAA • JIS • CCE/CMRS • GGTN
Contact Thermon for additional approvals and specific
information.
Form TEP0072U-0104
© Thermon Manufacturing Co.
Printed in U.S.A.
TSX
TM
Self-Regulating Heating Cable
Product Specifications
Application . . .
Process Temperature Maintenance or Freeze Protection
TSX self-regulating heating cables are designed specifically
for process temperature maintenance or freeze protection
where elevated cold-start currents are unacceptable. TSX
withstands the temperature exposures associated with
steam purging.
1
2
3
The heat output of TSX cable varies in response to the
surrounding temperature. Variations in the ambient temperature or heat lost through the thermal insulation are
compensated for automatically along the entire length of a
heat-traced pipe. This self-regulating feature allows TSX to
be overlapped without temperature upset damage to the
cable.
4
5
TSX cables are approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.
Ratings . . .
Available Watt densities .............. 9, 18, 27, 37 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac
Maximum maintenance temperature ........................... 121°C
Maximum continuous exposure temperature
Power-off ................................................................ 190°C
Minimum installation temperature ................................ -51°C
Minimum bend radius ................................................ 32 mm
T-rating2 .................................................................. T3 200°C
Basic Accessories3 . . .
Power Connection: All TSX cables require a TBX-3L power
boot for terminating the circuit before connecting to power..
End-of-Circuit Termination: TSX cables with the metallic
braid require the use of the ET-8 end cap for terminating at
the end of the circuit.
Construction . . .
1
2
3
4
Nickel-Plated Copper Bus Wires (1.3 mm2)
Semiconductive Heating Matrix
Fluoropolymer Dielectric Insulation
Nickel-Plated Copper Braid (BN)
Options . . .
5 OJ Fluoropolymer overjacket over nickelplated copper braid provides additional
protection to cable and braid where
exposure to chemicals or corrosives is
expected.
Certifications/Approvals . . .
TSX cables with the overjacket option require the ET-6 end
cap for terminating at the end of the circuit.
Factory Mutual Research
Hazardous (Classified) Locations
Notes . . .
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
1. Cable may be energised at other voltages; contact Thermon for design assistance.
2. T-rating per internationally recognised testing agency guidelines.
3. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).
TSX has additional hazardous area approvals
including:
• DNV
• Lloyd’s
• SAA
• JIS
• CCE/CMRS
Contact Thermon for additional approvals and
specific information.
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
TSX
TM
Self-Regulating Heating Cable
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type . . .
The power outputs shown apply to overjacketed cable
installed on insulated metallic pipe at the service voltage
stated below.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and
earth-fault protection should be based on applicable local
codes. TSX heating cables do not exhibit significant elevated
cold-start currents; therefore, it is not necessary to adjust
the circuit length based on expected minimum ambient
start-up temperatures to -40° C. For information on design
and performance on other voltages, contact Thermon.
Product Type
230 Vac Nominal
Power Output at 10° C
W/m
TSX 3-2
9
TSX 6-2
18
TSX 9-2
27
TSX 12-2
37
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
TSX at 230 Vac
50
230 Vac Service Voltage
Product Type
Watts per Metre
40
TSX 12-2
30
TSX 9-2
20
Max. Circuit Length vs. Breaker Size
Metres (C-Type Breakers)
16 A
25 A
TSX 3-2
171
217
TSX 6-2
111
153
TSX 9-2
82
125
TSX 12-2
64
107
TSX 6-2
10
TSX 3-2
0
-25
0
25
50
75
Pipe Temperature °C
100
125
Form TEP0006U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
HTSX 15 and 20
TM
Self-Regulating Heating Cable
Product Specifications
Application . . .
Process Temperature Maintenance or Freeze Protection
HTSX self-regulating heating cables are designed specifically
for process temperature maintenance or freeze protection
where high temperature exposure capability is required.
HTSX withstands the temperature exposures associated with
steam purging.
1
2
The heat output of HTSX cable varies in response to the
surrounding temperature. Variations in the ambient temperature or heat lost through the thermal insulation are compensated for automatically along the entire length of a heattraced pipe.
3
HTSX cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.
4
Ratings . . .
Available watt densities ........................ 48, 64 W/m @ 10°C
Nominal supply voltages1 .......................................... 230 Vac
Max. maintenance temperature ................................... 121°C
Max. exposure temperature
Intermittent power-on ............................................ 191°C
Continuous power-off ............................................ 191°C
Minimum installation temperature ............................... -60°C
Minimum bend radius ................................................ 32 mm
T-rating2 ................................................................. T3 200°C
Based on stabilised design3 ................................. T4 to T6
Basic Accessories4 . . .
Power Connection: All HTSX cables require a TBX-4L power
connection boot for terminating the circuit before connecting to power.
End-of-Circuit Termination: HTSX cables require the ET-8
end cap and ET-80 overcap for terminating at the end of the
circuit.
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
Construction . . .
1 Nickel-Plated Copper Bus Wires (1.3 mm2)
2 Semiconductive Heating Matrix and
Fluoropolymer Dielectric Insulation
3 Tinned Copper Braid
4 Fluoropolymer overjacket provides
additional protection to cable and braid
where exposure to chemicals or corrosives
is expected.
Product Features . . .
• Withstands continuous flamibility testing
according to IEC 60332-1: 1993
• Allows cable to be installed at temperatures
to -60°C
• Termination for system tested for ozone
stability, UV stability and flammability testing
according to ISO/IEC requirements
2. T-rating per internationally recognised testing agency guidelines.
3. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without limiting thermostats. The T-rating may be determined using CompuTrace® Electric Heat
Tracing Design Software or contact Thermon for design assistance.
4. Information on additional accessories to complete a heater circuit installation and to
comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
HTSX 15 and 20
TM
Self-Regulating Heating Cable
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type1 . . .
The power outputs shown apply to overjacketed cable
installed on insulated metallic pipe at the service voltage
stated below.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and earthfault protection should be based on applicable local codes.
For information on design and performance on other
voltages, contact Thermon.
Product Type
230 Vac
Nominal
Power Output
at 10°C
W/m
HTSX 15-2
48
HTSX 20-2
64
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
Type B Circuit Breakers
230 Vac Service Voltage
Start-Up
Product
Temperature2
Type
°C
10
0
HTSX 15-2
-20
-40
10
0
HTSX 20-2
-20
-40
HTSX at 230 Vac
70
HTSX 20-2
60
Watts per Meter
50
HTSX 15-2
40
30
Max. Circuit Length3 vs. Breaker Size
Metres
16 A
46
44
39
35
27
25
23
21
25 A
76
72
63
56
43
40
36
33
32 A
94
94
83
73
56
53
47
42
Type C Circuit Breakers
230 Vac Service Voltage
20
10
0
0
30
60
90
Pipe Temperature °C
Certifications/Approvals . . .
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
II 2 G/D EEx e II T3
02 ATEX 0120790
120
Start-Up
Product
Temperature2
Type
°C
10
0
HTSX 15-2
-20
-40
10
0
HTSX 20-2
-20
-40
Max. Circuit Length3 vs. Breaker Size
Metres
16 A
46
46
46
43
36
36
36
35
25 A
76
76
76
71
59
59
59
56
32 A
94
94
94
94
78
78
78
74
Note . . .
1. Maximum circuit lengths shown are based on an instantaneous trip current
characteristic per IEC 60898 at the referenced start-up temperature and a 10°C
maintenance temperature. For maximum circuit lengths with other trip current
characteristics contact Thermon.
Factory Mutual Research
Hazardous (Classified) Locations
2. While a heat tracing system is generally designed to keep the contents of a pipe at
the desired maintain temperature, the cable may be energized at lower temperatures.
For design data with lower start-up temperatures than represented above contact
Thermon for design assistance.
Underwriters Laboratories Inc.
Hazardous (Classified) Locations
3. The maximum circuit length is for one continuous length of cable, not the sum of
segments of cable. Refer to CompuTrace® design software or contact Thermon for
current loading of segments.
HTSX 15 and 20 has additional hazardous area approvals
including:
• DNV • Lloyd’s • SAA • JIS • CCE/CMRS • GGTN
Contact Thermon for additional approvals and specific
information.
Form TEP0074U-0104
© Thermon Manufacturing Co.
Printed in U.S.A.
VSX
TM
Self-Regulating Heating Cable
Product Specifications
Application . . .
Process Temperature Maintenance or Freeze Protection
High performance VSX self-regulating heating cables are
designed specifically for process temperature maintenance
or freeze protection where high maintain temperatures or
high temperature exposure is required. VSX withstands the
temperature exposures associated with steam purging.
1
2
3
The heat output of VSX cable varies in response to the
surrounding temperature by reducing its thermal output
with increasing temperature and can be overlapped without
temperature upset damage to the cable. With its high selfregulating characteristic, VSX can be installed in hazardous
areas requiring a T3 temperature class rating.
4
VSX cables are approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.
Ratings . . .
Available Watt densities ........... 15, 32, 48, 64 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac
Maximum maintenance temperature ........................... 149°C
Maximum continuous exposure temperature
Continuous power-off ............................................ 204°C
Intermittent power-on ............................................ 232°C
Minimum installation temperature ................................ -51°C
Minimum bend radius ................................................ 32 mm
T-rating2 .................................................................. T3 200°C
Construction . . .
1 Nickel-Plated Copper Bus Wires (2.1 mm2)
2 Semiconductive Heating Matrix and
Fluoropolymer Dielectric Insulation
3 Nickel-Plated Copper Braid
4 Fluoropolymer Overjacket
Certifications/Approvals . . .
Basic Accessories3 . . .
Factory Mutual Research
Hazardous (Classified) Locations
Power Connection: All VSX cables require a TBX-3L power
boot for terminating the circuit before connecting to power..
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
End-of-Circuit Termination: All VSX cables require the use
of the ET-6 end cap for terminating at the end of the circuit.
Notes . . .
1. Cable may be energised at other voltages; contact Thermon for design assistance.
2. T-rating per internationally recognised testing agency guidelines. VSX 20 has a T2
(300°C) temperature rating per CENELEC.
3. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Self-Regulating Cables
Systems Accessories” product specification sheet (Form TEP0010U).
VSX has additional hazardous area approvals
including:
• DNV
• Lloyd’s
• SAA
• JIS
• CCE/CMRS
Contact Thermon for additional approvals and
specific information.
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
VSX
TM
Self-Regulating Heating Cable
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type . . .
The power outputs shown apply to overjacketed cable
installed on insulated metallic pipe at the service voltage
stated below.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and
earth-fault protection should be based on applicable local
codes. For information on design and performance on
other voltages, contact Thermon.
Product Type
230 Vac Nominal
Power Output at 10° C
W/m
VSX 5-2
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
15
VSX 10-2
32
VSX 15-2
48
VSX 20-2
64
230 Vac Service Voltage
Product
Type
VSX at 230 Vac
70
VSX 5-2
60
Watts per Metre
50
VSX 10-2
VSX 20-2
40
VSX 15-2
VSX 15-2
30
20
VSX 20-2
VSX 10-2
10
Start-Up
Temperature
°C
10
0
-20
10
0
-20
10
0
-20
10
0
-20
Max. Circuit Length vs. Breaker Size
Metres (C-Type Breakers)
16 A
98
98
98
64
64
59
47
47
41
35
33
30
25 A
168
168
168
105
105
99
77
76
67
56
53
48
32 A
201
201
201
145
145
137
104
103
89
74
71
63
40 A
201
201
201
163
163
163
142
141
121
98
93
82
VSX 5-2
0
10
30
50
90
110
70
Pipe Temperature °C
130
150
Form TEP0008U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
HPT
TM
Power-Limiting Heating Cable
Product Specifications
Application . . .
Process Temperature Maintenance or Freeze Protection
High performance HPT power-limiting heating cables are
designed specifically for process temperature maintenance
or freeze protection where high maintain temperatures or
high temperature exposure is required. HPT withstands the
temperature exposures associated with steam purging.
1
2
A coiled resistor alloy heating element (patent pending)
provides the power-limiting feature of HPT. This PTC
(Positive Temperature Coefficient) characteristic decreases
the cable’s power output as the heat-traced product
temperature increases and allows the cable to be overlapped during installation. The composite construction of
the heating element and fibre substrate, plus an additional
fibre cushion layer, provides an exceptionally durable high
performance heating cable.
5
6
7
HPT cables are approved for use in ordinary (nonclassified)
areas and Zone 1 and 2 classified areas.
Ratings . . .
Construction . . .
Available Watt densities ............ 14, 28, 42, 57 W/m at 10°C
Nominal supply voltage1 ........................................... 230 Vac
Maximum maintenance temperature ........................... 149°C
Maximum continuous exposure temperature
Power-off ................................................................ 260°C
Minimum installation temperature ................................ -51°C
Minimum bend radius ................................................ 32 mm
1
2
3
4
5
6
7
Basic Accessories2 . . .
Certifications/Approvals . . .
Nickel-Plated Copper Bus Wires (3.3 mm2)
Composite Metal Alloy/Fibre
Heater Bus Connection (not shown)
Fibreglass Braid (not shown)
Fluoropolymer Dielectric Insulation
Nickel-Plated Copper Braid
Fluoropolymer Overjacket
Power Connection: All HPT cables require a TBX-4L power
boot for terminating the circuit before connecting to power..
End-of-Circuit Termination: HPT cables with exposure
temperatures below 200°C require the use of the ET-8 end
cap and TT-6 fluoropolymer tape strip for terminating at the
end of the circuit.
HPT cables with exposure temperatures between 200°C
and 260°C require the HPEK-OJ end cap for terminating at
the end of the circuit.
Notes . . .
1. Higher maintenance temperatures and operating voltages may be possible; contact
Thermon for design assistance.
Factory Mutual Research
Hazardous (Classified) Locations
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
HPT has additional hazardous area approvals
including:
• DNV
• Lloyd’s
• SAA
• JIS
• CCE/CMRS
Contact Thermon for additional approvals and
specific information.
2. Information on additional accessories to complete a heater circuit installation and
to comply with approval requirements can be found in the “Power-Limiting Cables
Systems Accessories” product specification sheet (Form TEP0018U).
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
HPT
TM
Power-Limiting Heating Cable
Product Specifications
Power Output Curves . . .
Circuit Breaker Sizing and Type . . .
The power outputs shown apply to overjacketed cable
installed on insulated metallic pipe at the service voltage
stated below.
Maximum circuit lengths for various circuit breaker
amperages are shown below. Circuit breaker sizing and
earth-fault protection should be based on applicable local
codes. For information on design and performance on
other voltages, contact Thermon.
Product Type
230 Vac Nominal
Zone Length
cm
Power Output at 10ºC
W/m
H PT 5-2
76
14
H PT 10-2
61
28
H PT 15-2
61
42
H PT 20-2
61
57
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
230 Vac Service Voltage
Product
Type
HPT at 230 Vac
60
H PT 5-2
50
Watts per Metre
HPT 20-2
40
H PT 10-2
HPT 15-2
30
H PT 15-2
20
HPT 10-2
10
H PT 20-2
HPT 5-2
0
10
30
50
70
90
110
130
Start-Up
Temperature
°C
10
0
-20
10
0
-20
10
0
-20
10
0
-20
Max. Circuit Length vs. Breaker Size
Metres (C-Type Breakers)
16 A
257
248
230
124
120
112
82
79
74
61
59
55
25 A
281
281
281
199
199
182
132
127
118
98
94
88
32 A
281
281
281
199
199
199
162
162
156
128
124
114
40 A
281
281
281
199
199
199
162
162
161
133
128
118
150
Pipe Temperature °C
Form TEP0011U-1200 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
MIK
TM
Mineral Insulated Heating Cable
Product Specifications
Application . . .
Process Temperature Maintenance or Freeze Protection
MIK high performance mineral insulated heating cables are
used extensively for high temperature maintenance, high
temperature exposure and/or high Watt density applications
which exceed the limitations of thermoplastic insulated
cables.
1
2
3
Thermon’s MIK mineral insulated cables are available in
three outer sheath materials to meet the temperature and
exposure requirements of the application.
MIK cables are approved for use in ordinary (nonclassified)
areas and are certified to the ATEX directive for use in
Category 2 and 3 (Zone 1 and 2) classified areas.
Ratings . . .
Rated voltages1 .......................................... 300 and 500 Vac
Maximum maintenance temperature2 ......................... 600°C
Maximum continuous exposure temperature
Power-off ................................................................ 650°C
Maximum Watt density2 ......................................... 200 W/m
Minimum installation temperature ................................ -20°C
Minimum bend radius .................................... 6 x cable O.D.
T-Rating5 ................................................................................................................... T1 to T6
(Using the principles of stabilized design or limiters)6
Construction . . .
1 Solid Alloy or Copper Conductor
2 Compacted Magnesium Oxide Insulation
3 Metallic Sheath
Certification/Approval . . .
Available MIK Sheaths . . .
Metal Sheath Material
Maximum Exposure
Temperature4
Copper
280°C
MIN
Cupro Nickel
350°C
M IS
Stainless Steel
650°C
Product Type
M IC3
MIK Heater Sets . . .
Thermon MIK cable sets are available in various factoryfabricated configurations designed for the cable type and
number of conductors. Information regarding cable
terminations is available from Thermon as part of a system
design.
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
II 2 G EEx e II T1 to T6
II 2 G EEx ed IIB or IIC T1 to T6
LCIE 01 ATEX 6025
MIK has additional hazardous area approvals
including:
• GGTN • Kazakhstan
Notes . . .
1. Specific voltage depends on circuit length and design conditions.
2. Watt density limitations are correlated to maintain temperatures.
3. Optional overjackets are available on MIC cables; contact Thermon.
4. When using cable terminations under the insulation the maximum allowable
temperature is lower; contact Thermon.
5. T-rating per internationally recognised testing agency guidelines.
6. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without
limiting thermostats. Contact Thermon for design assistance.
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
MIK
TM
Mineral Insulated Heating Cable
Product Specifications
Available Cables . . .
Circuit Breaker Sizing and Type . . .
300 and 500 Vac—One Conductor
1
Cable
Diameter
mm
Resistance
Ohm/m
at 20°C
M I N-M1-1600
3.2
1.600
2.5
M I N-M1-1000
3.4
1.000
2.5
M I N-M1-630
3.7
0.630
2.5
M I N-M1-400
4.0
0.400
2.5
M I N-M1-250
4.4
0.250
6.0
Product Reference Legend . . .
M I N-M1-160
M I N-M1-63
4.9
3.2
0.160
0.063
6.0
2.5
Example:
M I N-M1-40
M I N-M1-25
3.4
3.7
0.040
0.025
2.5
6.0
M I N-M1-17
4.6
0.017
6.0
M I N-M1-11
M I N-M1-7
4.9
5.3
0.011
0.007
6.0
10.0
M I N-M1-4
5.9
0.004
16.0
M IS-M1-10K
3.2
10.000
2.5
Product
Type
Cold Lead
Cable Size
mm2
Maximum circuit lengths for MIK heating cables will be a
function of cable resistance, circuit length and operating
voltage. Circuit length, breaker sizing and earth-fault
protection should be based on applicable local codes.
M IS-M1-6300
3.2
6.300
2.5
M IS-M1-4000
3.2
4.000
2.5
M IS-M1-2500
M IS-M1-1600
3.4
3.6
2.500
1.600
2.5
2.5
M IS-M1-1000
M IS-M1-630
3.9
4.3
1.000
0.630
2.5
2.5
M IS-M1-400
4.7
0.400
2.5
M IS-M1-250
5.3
0.250
6.0
M IS-M1-160
6.5
0.160
6.0
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
MIC-M1-800
Conductor Resistance
Sheath Material
Ω/km
2
C ....................... Copper
N .............. Cupro Nickel
S ............. Stainless Steel
Number of Conductors
Rated Voltage
L ....................... 300 Vac
M ...................... 500 Vac
Note . . .
1. All resistances shown are per length of cable at 20°C and are subject to a ±10%
manufacturing tolerance.
2. Copper sheath available on request; contact Thermon.
Form TEP0020U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.
TESH
TM
Series Constant Watt Heating Cable
Product Specifications
Application . . .
Long Line Temperature Maintenance or Freeze Protection
TESH series resistance constant Watt heating cables are
used where circuit lengths exceed the limitations of parallel
resistance heating cables. TESH withstands the temperature
exposures associated with steam purging.
1
2
3
The series circuitry of TESH provides consistent Watt-permetre power output along the entire length of the cable with
no voltage drop. A glassceramic tape layer adds additional
protection to the heating cable and a fluoropolymer
overjacket provides chemical resistance while maintaining
maximum flexibility. The construction of the cable meets the
7 Joule impact test per EN50019.
4
5
TESH cables are approved for use in ordinary (nonclassified) areas and Catagories 2 and 3 ATEX classified areas.
Ratings . . .
Maximum Watt density ............................................. 25 W/m
Maximum supply voltage .......................................... 750 Vac
Maximum continuous exposure temperature
Power-off ................................................................ 260°C
Minimum installation temperature ............................... -60°C
Minimum bend radius .................................... 5 x cable O.D.
T-rating1 .................................................................... T2 to T6
(using the principles of stabilized design or limiters)2
Stabilised Design . . .
Construction . . .
1
2
3
4
5
Heating Conductor
Fluoropolymer Dielectric Insulation
Glassceramic Tape
Nickel-Plated Copper Braid (BN)
Fluoropolymer Overjacket
Certification/Approval . . .
The Watt density limitation for TESH cables is directly
related to the desired maintain temperature. Thermon is
able to ensure the T-rating based on a stabilised design that
enables series constant Watt heating cables to operate in
hazardous areas without limiting thermostats. TESH cable
output and T-rating are dependent upon supply voltage,
cable resistance, temperature conditions as well as additional variables. Contact Thermon for design assistance.
European Organisation for Electrotechnical
Standardisation
Hazardous (Classified) Locations
II 2 G/D EEx e IIC T2 to T6 LCIE 00 ATEX 6014 X
TESH has additional hazardous area approvals
including:
• GGTN • Kazakhstan
Basic Accessories3 . . .
Power Connection: TESH cables typically require nonheating terminations at each end of the circuit before connecting to power. Contact Thermon for complete information.
Notes . . .
1. T-rating per internationally recognised testing agency guidelines.
2. Thermon heating cables are approved for the listed T-ratings using the stabilised
design method. This enables the cable to operate in hazardous areas without
limiting thermostats. The T-rating may be determined using CompuTrace® Electric
Heat Tracing Design Software or contact Thermon for design assistance.
Product Features . . .
• Withstands continuous flamibility testing
according to IEC 60332-1: 1993
• Allows cable to be installed at temperatures
to -60°C
THERMON . . . The Heat Tracing Specialists®
www.thermon.com
European Headquarters
Boezemweg 25
2641 KG Pijnacker
PO Box 205
2640 AE Pijnacker
The Netherlands
Phone: +31 (0) 15-36 15 370
Facsimile: +31 (0) 15-36 15 379
•
•
•
•
Corporate Headquarters
100 Thermon Dr.
PO Box 609
San Marcos, TX 78667-0609
U.S.A.
Phone: +1 512-396-5801
Facsimile: +1 512-396-3627
•
•
•
TESH
TM
Series Constant Watt Heating Cable
Product Specifications
Available Cables . . .
TESH 2.9
Resistance
Ohm/m
at 20°C
0.0029
Product Type
Circuit Breaker Sizing and Type . . .
Conductor Max. Cable Length1
Cable
Size
m (with 30 mA earth- Diameter
mm2
mm
fault protection)
6.00
1435
7.0
TESH 4.4
0.0044
4.00
1525
6.3
TE S H 7
0.0072
2.50
185
5.5
TESH 10
0.010
1.79
1775
5.1
TESH 11.7
0.0117
1.50
2025
4.9
TESH 15
0.015
1.20
2090
4.7
TESH 17.8
0.0178
1.00
2275
4.6
TESH 25
0.025
1.11
2525
4.6
TESH 31.5
0.0315
1.60
2400
4.9
TESH 50
0.050
1.02
2335
4.7
TESH 65
0.065
0.75
1890
4.4
TESH 80
0.080
1.21
2190
4.3
TESH 100
0.100
1.50
2025
4.9
TESH 150
0.150
1.02
2335
4.6
TESH 200
0.200
0.75
2605
4.4
TESH 320
0.320
0.92
2420
4.5
TESH 380
0.380
0.79
2555
4.4
TESH 480
0.480
0.64
2765
4.3
4.2
TESH 600
0.600
0.49
3010
TESH 700
0.700
0.43
3155
4.1
TESH 810
0.810
0.62
2780
4.3
TESH 1000
1.000
0.49
3010
4.2
TESH 1440
1.440
0.34
3395
4.1
TESH 1750
1.750
0.29
3615
4.1
TESH 2000
2.000
0.55
2900
4.2
TESH 3000
3.000
0.34
3395
4.1
TESH 8000
8.000
0.14
4455
3.8
Maximum circuit lengths for TESH heating cables will be a
function of cable resistance, circuit length and operating
voltage. Circuit length, breaker sizing and earth-fault
protection should be based on applicable local codes.
Earth-fault protection of equipment should be provided for
each branch circuit supplying electric heating equipment.
Note . . .
1. Longer circuit lengths are possible based on earth-fault protection with higher earthfault ratings; contact Thermon.
Form TEP0070U-0104 © Thermon Manufacturing Co. Printed in U.S.A. Information subject to change.