Crucial Power Products Series 300 UPS GUIDE SPECIFICATIONS for a 10 - 125 kVA Three-Phase Uninterruptible Power System CSI 16610 Uninterruptible Power Supply Systems 1.0 GENERAL 1.1 SUMMARY This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase, solid-state, uninterruptible power supply (UPS) system. The UPS shall provide high-quality AC power for sensitive electronic equipment loads. 1.2 STANDARDS The UPS shall be designed in accordance with the applicable sections of the current revision of the following documents. Where a conflict arises between these documents and statements made herein, the statements in this specification shall govern. • • • • • • • • • ANSI C62.41 (IEEE 587) ASME CSA 22.2, No. 107.1 FCC Part 15, Class A ISO 9001 National Electrical Code (NFPA-70) NEMA PE-1 OSHA UL Standard 1778 The UPS shall be UL listed per UL Standard 1778, and shall be CSA certified. 1.3 SYSTEM DESCRIPTION 1.3.1 Design Requirements - UPS Module A. Voltage. Input/output voltage specifications of the UPS shall be: Input: ( ) volts, three-phase, 3-wire-plus-ground. Output: ( ) volts, three-phase, 4-wire-plus-ground. B. Output Load Capacity. Specified output load capacity of the UPS shall be ( ) kVA at 0.8 lagging power factor. C. Field-Installable Power Upgrade. Selected systems shall be able to accept a field-installed power upgrade to the next highest power rating without an increase in cabinet size, as follows: 10 kVA UPS modules can be field upgraded to 15 kVA S300 Specifications Crucial Power Products 20 kVA UPS modules can be field upgraded to 30 kVA 40 kVA UPS modules can be field upgraded to 50 kVA 65 kVA UPS modules can be field upgraded to 75 kVA 100 kVA UPS modules can be field upgraded to 125 kVA 1.3.2 Design Requirements - Matching Battery Cabinet A. Battery Cells: Sealed, lead-acid, valve-regulated. B. Reserve Time: ( ) minutes at full load, 0.8 power factor, with ambient temperature between 20 and 30캜. C. Recharge Time: to 95% capacity within ten (10) times discharge time. 1.3.3 Modes of Operation The UPS shall be designed to operate as an on-line reverse transfer system in the following modes: A. Normal - The critical AC load is continuously supplied by the UPS inverter. The rectifier/charger derives power from a utility AC source and supplies DC power to the inverter while simultaneously float-charging a power reserve battery. B. Emergency - Upon failure of utility AC power, the critical AC load is supplied by the inverter, which without any switching, obtains power from the battery. There shall be no interruption in power to the critical load upon failure or restoration of the utility AC source. C. Recharge - Upon restoration of utility AC power, after a utility AC power outage, the rectifier/charger shall automatically restart, walk-in, and gradually assume the inverter and battery recharge loads. D. Bypass - If the UPS must be taken out of service for maintenance or repair, or should the inverter overload capacity be exceeded, the static transfer switch shall perform a reverse transfer of the load from the inverter to the bypass source with no interruption in power to the critical AC load. 1.3.4 Performance Requirements 1. AC Input to UPS A. Voltage Configuration for Standard Units: three-phase, 4-wire plus ground. B. Voltage Range: + 10%, -25% of nominal. C. Frequency: Nominal frequency +/- 5%. D. Power Factor: 0.90 lagging minimum at nominal input voltage and full rated UPS output load. S300 Specifications Crucial Power Products E. Inrush current: 800% of full load current maximum. F. Current Limit: 125% of nominal AC input current maximum. 100% of nominal for optional generator operation. G. Input Current Walk-In: 20 seconds to full rated input current maximum. Field selectable 5 or 20 seconds. H. Current Distortion: 30% THD maximum at full load. An optional input filter shall be available to reduce input current distortion to 10% THD maximum at full load. I. Surge Protection: Sustains input surges without damage per criteria listed in ANSI C62.41-1980. 2. AC Output, UPS Inverter A. Voltage Configuration: three-phase, 4-wire plus ground. B. Voltage Regulation: +/- 1% three-phase RMS average for a balanced three-phase load for the combined variation effects of input voltage, connected load, battery voltage, ambient temperature, and load power factor. +/- 2% three-phase RMS average for a 50% unbalanced load for the combined variation effects of input voltage, connected load, battery voltage, ambient temperature, and load power factor. C. Frequency: Nominal frequency +/- 0.1%. D. Frequency Slew Rate: 1.0 Hertz per second maximum. Field selectable from 0.1 to 1.0 Hz per second. E. Phase Displacement: +/- 1 degree for balanced load. +/- 3 degrees for 50% unbalanced load. F. Bypass Line Sync Range: +/- 0.5 Hertz. Field selectable +/- 0.5, 1.0, 3.0, 5.0 Hz. G. Voltage Distortion: 5% total harmonic distortion (THD) for linear loads. 3% maximum for any single harmonic. H. Load Power Factor Range: 0.9 leading to 0.5 lagging. I. Output Power Rating: Rated kVA at 0.8 lagging power factor. S300 Specifications Crucial Power Products J. Overload Capability: 125% for 10 minutes (without bypass source). 150% for 30 seconds (without bypass source). K. Inverter Output Voltage Adjustment: +/- 5% manual adjustment. L. Voltage Transient Response: 20% load step +/- 4% 30% load step +/- 5% 50% load step +/- 8% loss or return of AC input power +/- 1% manual transfer of 100% load +/- 4%. M. Transient Recovery Time: to within 1% of output voltage within 50 milliseconds. N. Voltage Unbalance: balanced load to 20% unbalanced load +/- 1%, 50% unbalanced load +/-2%, 100% unbalanced load +/- 5%. O. Fault Clearing: Sub-cycle current of at least 300%. 1.4 ENVIRONMENTAL CONDITIONS The UPS shall be able to withstand the following environmental conditions without damage or degradation of operating characteristics: A. Operating Ambient Temperature: UPS Module: 32캟 to 105캟 (0캜 to 40캜). Battery: 77 +/- 9캟 (25 +/- 5캜). B. Storage/Transport Ambient Temperature: -4캟 to 158캟 (-20캜 to 70캜). C. Relative Humidity: 0 to 95%, non-condensing. D. Altitude: Operating: to 6600 ft. (2 000 meters) above Mean Sea Level. Derated for higher altitude applications. Storage/Transport: to 40,000 ft. (12 200 meters) above Mean Sea Level. S300 Specifications Crucial Power Products E. Audible Noise: Noise generated by the UPS under any condition of normal operation shall not exceed 65 dBA measured 1 meter from surface of the UPS. 1.5 SUBMITTALS 1.5.1 Proposal Submittals Submittals with the proposal shall include: a. System configuration with single-line diagrams. b. Functional relationship of equipment including weights, dimensions, and heat dissipation. c. Descriptions of equipment to be furnished, including deviations from these specifications. d. Size and weight of shipping units to be handled by installing contractor. e. Detailed layouts of customer power and control connections. f. Detailed installation drawings including all terminal locations. 1.5.2 UPS Delivery Submittals Submittals upon UPS delivery shall include: a. A complete set of submittal drawings. b. One (1) instruction manual that shall include a functional description of the equipment with block diagrams, safety precautions, instructions, step-by-step operating procedures and routine maintenance guidelines, including illustrations. 1.6 WARRANTY 1.6.1 UPS Module The UPS manufacturer shall warrant the UPS module against defects in materials and workmanship for 12 months after initial start-up or 18 months after ship date, whichever period expires first. 1.6.2 Battery The battery manufacturer뭩 standard warranty shall be passed through to the end user. 1.7 QUALITY ASSURANCE 1.7.1 Manufacturer Qualifications S300 Specifications Crucial Power Products A minimum of twenty year뭩 experience in the design, manufacture, and testing of solid-state UPS systems is required. The system shall be designed and manufactured according to world class quality standards. The manufacturer shall be ISO 9001 certified. 1.7.2 Factory Testing Before shipment, the manufacturer shall fully and completely test the system to assure compliance with the specification. These tests shall include operational discharge and recharge tests on at least a one-minute battery plant to assure guaranteed rated performance. 2.0 PRODUCT 2.1 FABRICATION 2.1.1 Materials All materials of the UPS shall be new, of current manufacture, high grade and free from all defects and shall not have been in prior service except as required during factory testing. The maximum working voltage, current, and di/dt of all solid-state power components and electronic devices shall not exceed 75% of the ratings established by their manufacturer. The operating temperature of solid-state component sub-assembly shall not be greater than 75% of their ratings. Electrolytic capacitors shall be computer grade and be operated at no more than 95% of their voltage rating at the maximum rectifier charging voltage. 2.1.2 Wiring Wiring practices, materials and coding shall be in accordance with the requirements of the National Electrical Code (NFPA 70). All bolted connections of bus bars, lugs, and cables shall be in accordance with requirements of the National Electrical Code and other applicable standards. All electrical power connections are to be torqued to the required value and marked with a visual indicator. Provision shall be made for power cables to enter or leave from the top or bottom of the UPS cabinet. 2.1.3 Construction and Mounting The UPS unit, comprised of input autotransformer, rectifier/charger with input filter, inverter, static transfer switch, and maintenance bypass switch, shall be housed in a single free-standing NEMA type 1 enclosure. Cabinet doors/covers shall require a tool for gaining access. Casters and leveling feet shall be provided for ease of installation. Front access only shall be required for expedient servicing, adjustments, and installation. The UPS cabinet shall be structurally adequate and have provisions for hoisting, jacking, and forklift handling. The UPS cabinet shall be cleaned, primed, and painted with the manufacturer뭩 standard color. The UPS shall be constructed of replaceable subassemblies. Printed circuit assemblies shall be plug-in. Like assemblies and like components shall be interchangeable. 2.1.4 Cooling Cooling of the UPS shall be by forced-air. Redundant fans shall be used. Low velocity fans shall be used to minimize audible noise output. Fan power shall be provided by the UPS output. S300 Specifications Crucial Power Products The thermal design, along with all thermal and ambient sensors, shall be coordinated with the protective devices before excessive component or internal cabinet temperatures are exceeded. 2.1.5 Grounding The AC output neutral shall be electrically isolated from the UPS chassis. The UPS chassis shall have an equipment ground terminal. Provisions for local bonding shall be provided. 2.2 COMPONENTS 2.2.1 Input Autotransformer An input autotransformer shall be included. The input autotransformer shall be factory installed inside the UPS module cabinet. 208/208 and 480/208 UPS module input/output voltage configurations shall be served by the same transformer through tap selection for additional system flexibility. 2.2.2 Rectifier/Charger A. General The term rectifier/charger shall denote the solid-state equipment and controls necessary to convert incoming AC power to regulated DC power for input to the inverter and for battery charging. The rectifier/charger shall be a phase-controlled, solid-state SCR type with constant voltage/current limiting control circuitry. B. AC Input Current Limiting The rectifier/charger unit shall be provided with AC input current limiting whereby the maximum input current shall be limited to 125% of the full input current rating. The rectifier/charger shall operate at a reduced current limit mode whenever the critical load is powered from the UPS static bypass circuit such that the maximum UPS input current will not exceed 125% of full load input current. In addition, the rectifier/charger input current limit shall be automatically reduced to 25% of full load input current whenever the critical load is powered from the UPS internal maintenance bypass circuit. An optional second circuit shall limit input current to 100% of rated full load current when activated by a customer supplied contact closure to signal a customer function such as generator operation. C. Input Current Walk-In The rectifier/charger shall contain a timed walk-in circuit that causes the unit to gradually assume the load over a 20-second time interval after input voltage is applied. Walk-in time shall be field selectable for 5 or 20 seconds. D. Fuse Failure Protection Power semiconductors in the rectifier/charger shall be fused with fast-acting fuses, so that loss of any one power semiconductor shall not cause cascading failures. E. DC Filter S300 Specifications Crucial Power Products The rectifier/charger shall have an output filter to minimize ripple voltage into the battery. Under no conditions shall ripple voltage into the battery exceed 2% RMS. The filter shall be adequate to insure that the DC output of the rectifier/charger will meet the input requirements of the inverter. The inverter shall be able to operate from the rectifier/charger with the battery disconnected. F. Automatic Restart Upon restoration of utility AC power, after a utility AC power outage and prior to a UPS automatic end-of-discharge shutdown, the rectifier/charger shall automatically restart, walk-in, and gradually assume the inverter and battery recharge loads. Upon restoration of utility AC power, after a utility AC power outage and after a full UPS automatic end-of-discharge shutdown, the UPS will (customer selectable) automatically restart, performing the normal UPS start up walk-in. G. Battery Recharge In addition to supplying power for the inverter load, the rectifier/charger shall be capable of producing battery charging current sufficient to replace 95% of the battery discharge power within ten (10) times the discharge time. After the battery is recharged, the rectifier/charger shall maintain the battery at full charge until the next emergency operation. H. Overvoltage Protection There shall be DC over-voltage protection so that if the DC voltage rises to the pre-set limit, the UPS is to shut down automatically and initiate an uninterrupted load transfer to the static bypass line. 2.2.3 Inverter A. General The term inverter shall denote the solid-state equipment and controls to convert DC power from the rectifier/charger or battery to regulated AC power for supporting the critical load. The inverter shall be a transistorized, phase-controlled, pulse width modulated (PWM) design capable of providing the specified AC output. B. Overload Capability The inverter shall be capable of supplying current and voltage for overloads exceeding 100% and up to 150% of full load current. A status indicator and audible alarm shall indicate overload operation. The UPS shall transfer the load to bypass when overload capacity is exceeded. C. Fault Clearing and Current Limit The inverter shall be capable of supplying an overload current of 150% of its full-load rating for thirty seconds. For greater currents or longer time duration, the inverter shall have electronic current-limiting protection to prevent damage to components. The inverter shall be selfprotecting against any magnitude of connected output overload. Inverter control logic shall sense and disconnect the inverter from the critical AC load without the requirement to clear protective fuses. D. Output Power Transformer S300 Specifications Crucial Power Products A dry type power transformer shall be provided for the inverter AC output. It shall have copper wiring exclusively. The transformers hottest spot winding temperature shall not exceed the temperature limit of the transformer insulation class of material when operating at full load at maximum ambient temperature. E. Phase Balance Electronic controls shall be provided to regulate each phase so that an unbalance loading will not cause the output voltage to go outside the specified voltage unbalance or phase displacement. F. Fuse Failure Protection Power semiconductors in the inverter unit shall be fused with fast-acting fuses, so that loss of any one power semiconductor will not cause cascading failures. G. Inverter Shutdown For rapid removal of the inverter from the critical load, the inverter control electronics shall instantaneously turn off the inverter transistors. Simultaneously, the static transfer switch shall be turned on to maintain continuous power to the critical load. H. Inverter DC Protection The inverter shall be protected by the following disconnect levels: • DC Overvoltage Shutdown • DC Undervoltage Warning (Low Battery Reserve), user adjustable from 1 to 99 minutes • DC Undervoltage Shutdown (End of Discharge) I. Overdischarge Protection To prevent battery damage from overdischarging, the UPS control logic shall automatically raise the shutdown voltage set point as discharge time increases beyond fifteen (15) minutes. J. Inverter Output Voltage Adjustment The inverter shall use a manual control to adjust the output voltage from +/- 5% of the nominal value. K. Output Frequency The output frequency of the inverter shall be controlled by an oscillator. The oscillator shall be temperature compensated and hold the inverter output frequency to +/- 0.1% for steady state and transient conditions. Drift shall not exceed 0.1% during a 24-hour period. Total frequency deviation, including short time fluctuations and drift, shall not exceed 0.1% from the rated frequency. 2.2.4 Display and Controls A. Monitoring and Control S300 Specifications Crucial Power Products The UPS shall be provided with a microprocessor based unit status display and controls section designed for convenient and reliable user operation. A system power flow diagram shall be provided as part of the monitoring and controls sections which depicts a single-line diagram of the UPS. Illuminated visual indicators shall be of the long-life light-emitting diode (LED) type. All of the operator controls and monitors shall be located on the front of the UPS cabinet. The monitoring functions such as metering, status and alarms shall be displayed on an alphanumeric LCD display. Additional features of the monitoring system shall include: • Menu-driven display with text format selectable in five (5) languages (English, German, French, Spanish, or Italian) • Real time clock (time and date) • Alarm history with time and date stamp • Battery back-up memory B. Metering The following parameters shall be displayed: • • • • • • • • • • Input AC voltage line-to-line and line-to-neutral for each phase Input AC current for each phase Input frequency Battery voltage Battery charge/discharge current Output AC voltage line-to-line and line-to-neutral for each phase Output AC current for each phase Output frequency Percent of rated load being supplied by the UPS Battery time left during battery operation C. Alarm Messages The following alarm messages shall be displayed: • • • • • • • • • • • • • • • • • • • Input power out of tolerance Input phase rotation incorrect Incorrect input frequency Charger in reduced current mode Battery Charger Problem Battery failed test Low battery warning (adjustable 1 to 99 minutes) Low battery shutdown DC bus overvoltage Bypass frequency out of range Load transferred to bypass Excessive retransfers attempted Static switch failure UPS output not synchronized to input power Input power single phased Input voltage sensor failed Inverter leg over current in X-phase Output undervoltage Output overvoltage S300 Specifications Crucial Power Products • • • • • • • • • • • Output overcurrent System output overloaded Load transferred to bypass due to overload Overload shutdown Control Error Critical power supply failure Load transferred due to internal protection External shutdown (remote EPO activated) Fan failure Overtemperature shutdown impending Overtemperature shutdown An audible alarm shall be provided and activated by any of the above alarm conditions. D. Status Messages The following UPS status messages shall be displayed: • • • • • • Normal operation Load on maintenance bypass Load on UPS Load on static bypass System shutdown UPS on battery E. Controls UPS start-up, shutdown, and maintenance bypass operations shall be accomplished by a single rotary control switch. An advisory display and menu-driven user prompts shall be provided to guide the operator through system operation without the use of additional manuals. Pushbuttons shall be provided to display the status of the UPS and to test and reset visual and audible alarms. F. Power Status Diagram A mimic panel shall be provided to depict a single line diagram of the UPS. Indicating lights shall be integrated within the single line diagram to illustrate the status of the UPS. Two LEDs located on the diagram shall indicate whether UPS input and/or output power is present. The diagram shall be color coded with the positions of the rotary control switch for visual confirmation of the UPS operating mode. G. On-Line Battery Test The UPS shall be provided with a menu driven On-Line Battery Test feature. The test shall ensure the capability of the battery to supply power to the inverter while the load is supplied power in the normal mode. If the battery fails the test, the system shall automatically do the following: 1. 2. 3. 4. Transfer the load to bypass Restart the rectifier/charger Display a warning message Sound an audible alarm S300 Specifications Crucial Power Products 5. Retransfer the load back to normal mode The battery test feature shall have the following user selectable options: 1. 2. 3. 4. DC bus voltage threshold (pass/fail value) Interval between tests (2 to 9 weeks) Date and time of initial test Enable/disable test 2.2.5 Static Transfer Switch A. General A static transfer switch and bypass circuit shall be provided as an integral part of the UPS. The static switch shall be a naturally commutated high-speed static (SCR-type) device rated to conduct full load current continuously. The switch shall have an overload rating of 125% rated load continuously, 200% rated load for thirty seconds, and 2000% rated load for two cycles. The static transfer switch control logic shall contain an automatic transfer control circuit that senses the status of the inverter logic signals, and operating and alarm conditions. This control circuit shall provide an uninterrupted transfer of the load to an alternate bypass source, without exceeding the transient limits specified herein, when an overload or malfunction occurs within the UPS, or for bypassing the UPS for maintenance. B. Uninterrupted Transfer The transfer control logic shall automatically turn on the static transfer switch, transferring the critical AC load to the bypass source, after the transfer logic senses any of the following conditions: • • • • Inverter overload capacity exceeded Critical AC load overvoltage or undervoltage Battery protection period expired UPS fault condition The transfer control logic shall inhibit an automatic transfer of the critical load to the bypass source if any of the following conditions are present: • Inverter/bypass voltage difference exceeding preset limits • Bypass frequency out of limits • Bypass out-of-synchronization range with inverter output C. Uninterrupted Retransfer Retransfer of the critical AC load from the bypass source to the inverter output shall be automatically initiated unless inhibited by manual control. The transfer control logic shall inhibit an automatic retransfer of the critical load to the inverter if one of the following condition exists: • • • • Bypass out of synchronization range with inverter output Inverter/bypass voltage difference exceeding preset limits Overload condition exists in excess of inverter full load rating UPS fault condition present S300 Specifications Crucial Power Products 2.2.6 Maintenance Bypass Switch A. General A manually operated maintenance bypass switch shall be incorporated into the UPS cabinet to directly connect the critical load to the input AC power source, bypassing the rectifier/charger, inverter, and static transfer switch. B. Isolation All energized terminals shall be shielded to ensure that maintenance personnel do not inadvertently come in contact with energized parts or terminals. A means to de-energize the static switch shall be provided when the UPS is in the maintenance bypass mode of operation. C. Maintenance Capability With the critical load powered from the maintenance bypass circuit, it shall be possible to check out the operation of the rectifier/charger, inverter, battery, and static transfer switch. 2.2.7 Battery Power Pack The battery power pack shall include sealed, lead-acid valve regulated battery cells housed in a separate cabinet that matches the UPS cabinet styling to form an integral system line-up. Battery cells shall be mounted on slide-out trays for ease of maintenance. A disconnect means shall be included for isolation of the battery pack from the UPS module. Casters and leveling feet shall also be provided with the battery power pack cabinet for ease of installation. 2.2.8 Accessories (Optional Equipment) A. Optional Input Filter The rectifier/charger shall include an input filter to reduce reflected input current distortion to 10% THD at full load with nominal input voltage. Another benefit of the input filter shall be to maintain the input power factor at 0.90 lagging minimum from full load to half load with nominal input voltage. B. Optional Input Isolation Transformer An input isolation transformer shall be included. The isolation transformer shall be a delta-wye configuration to provide common mode noise attenuation for all system operating modes including while on bypass. In addition to the noise attenuation feature, this transformer shall be provided for the following applications: 1. Operation from delta utility configuration, or 2. Any voltage configuration with line-to-neutral loads on the UPS output where an input neutral conductor is not supplied The input isolation transformer shall be factory installed inside the UPS module cabinet. 208/208 and 480/208 UPS module input/output voltage configurations shall be served by the same transformer through tap selection for additional system flexibility. C. Optional External Maintenance Bypass Cabinet S300 Specifications Crucial Power Products A matching external maintenance bypass cabinet shall be provided to enable the UPS module to be completely isolated from the electrical system while the critical load is powered through the external maintenance bypass line. This optional cabinet shall provide make-before-break operation for transfers to and from the external maintenance bypass line with a single rotary switch. The following components shall be standard: single rotary switch with auxiliary contacts, inter-cabinet wiring, casters, and leveling feet. The following components shall be optional: input circuit breaker, shielded isolation transformer, and load (output) circuit breaker. This matching cabinet shall bolt to the right side of the UPS module with a barrier shield to separate the two cabinets. Only front access shall be required for installation and service. D. Optional Slim-Line Distribution Cabinet A matching distribution cabinet shall be provided for flexible cable distribution of power from the UPS output to the critical loads. The distribution cabinet shall include one or two 42-pole (225 Amp) panelboards. Both plug-in and bolt-in style panelboards shall be available to accommodate specific site requirements. A 225 Amp main circuit breaker shall be provided with each panelboard. The slim-line distribution cabinet shall be designed as a bolt-on section to the right side of the UPS module cabinet for field installation by the installing contractor. The slim-line distribution cabinet shall add no more than ten (10) inches to the width of the UPS system. Branch circuit breakers and flexible distribution cables shall be specified by the end user or the installing contractor. E. Optional Remote Contact Board Isolated Form C contacts shall be provided to indicate a change of status of each of the following conditions: • • • • • UPS on battery alarm Low battery reserve alarm Load on bypass alarm Summary alarm New alarm - a separate alarm for a second summary alarm F. Optional Remote Status Panel A remote status panel shall be provided and shall include the following: • • • • • • • • Load on UPS LED Load On Bypass LED Battery Discharge LED Low Battery Reserve LED UPS Alarm Condition LED New Alarm Condition LED (for a second UPS alarm condition) Audible Alarm with Reset pushbutton Lamp Test/Reset pushbutton The remote status panel shall be provided in a NEMA Type 1 enclosure for wall mounting. G. Optional RS-232C Interface Port S300 Specifications Crucial Power Products An RS-232C interface port shall be provided for remote display of UPS status information at a computer terminal (by others). The UPS via the RS-232C port will support an Enhanced Terminal interface feature. The UPS will 밺raw?a picture of its own display panel on the remote terminal screen. The UPS will treat the terminal as if it were the front panel LCD display and pushbuttons, enabling the remote user to view screens, set any modifiable values, turn the load on or off, or otherwise be able to perform any functions possible through the normal front panel display. H. Optional IBM* System/38* Power Warning Signal An isolated signal, normally closed when utility power fails and the UPS battery is discharging, shall be provided for user connection to computer power warning interface. * IBM, System/38, and AS/400 are trademarks of International Business Machines Corporation. I. Optional IBM* AS/400* UPS Signal The following isolated normally open contacts shall be provided for user connection to an IBM AS/400 UPS signal interface: • • • • UPS on (UPS is supplying power) Bypass active (bypass is supplying power) Utility failure (battery is discharging) Battery low (limited battery time remaining) A 50-foot shielded cable, compliant with NEMA Class 2 for plenum applications, with subminiature 9-pin D-type connector, shall be provided for connection to the signal interface. J. Optional Contact Isolator Board A contact isolator board shall be included to provide an interface for the following: • External battery circuit breaker UVR (undervoltage release) • External battery circuit breaker auxiliary contacts • Reduced AC input current limit (shall reduce UPS input current limit to 100% of nominal when activated by a user supplied contact closure). K. Optional SiteScan/Sitemaster Interface An interface board shall be provided to communicate with Crucial Power site monitoring products. Monitored equipment parameters and alarms shall be transmitted through a twistedpair control wiring connection (cable not included in option) for display at the centralized terminal. Note that use of this option precludes the ability to also select the RS-232C option. L. Optional DC Ground Fault Alarm This feature shall annunciate an alarm condition when either the positive (+) or negative (-) DC bus is grounded. M. Optional Battery Circuit Breaker S300 Specifications Crucial Power Products A battery circuit breaker shall be provided to isolate the battery from the UPS. This breaker shall have an undervoltage release (UVR) and auxiliary contacts, and shall be in a separate wall mounted NEMA-1 enclosure. The battery breaker provides a manual disconnecting means, short circuit protection, and overcurrent protection for the battery system. When opened, there shall be no battery voltage in the UPS enclosure. The UPS shall be automatically disconnected from the battery by opening the breaker when the battery reaches the minimum discharge voltage level. N. Optional Computer Interface System A Computer Interface System shall be provided to perform an automatic unattended orderly shutdown of the customer뭩 operating system when necessary. This system shall include the software required to interface the UPS to the computer. The software monitors the UPS for power failure and low battery alarm while operating as a background task on the computer. After a power failure occurs, the software shall perform an automatic shutdown when the preprogrammed timer expires. If the UPS reaches a low battery alarm, the software shall override the timer and perform an automatic shutdown. This system requires the optional remote contact board to provide isolated normally closed contacts. This system shall include a shielded interface cable with a 25-pin subminiature D-shell connector to fit the serial port of the computer file server. Cable shall be available in selected lengths from 25 to 300 feet. O. Optional Multi-Computer Interface System A Multi-Computer Interface System shall be provided where a single UPS is powering multiple computer file servers (up to 48). This system shall perform an automatic unattended orderly shutdown of the customer뭩 operating system in each computer when necessary. The MultiInterface Unit (MIU) shall provide the hardware required to interface the UPS to each computer. The software provided allows each computer to monitor the UPS for power failure and low battery alarm while operating as a background task. After a power failure occurs, the software shall perform an automatic shutdown of each computer when the pre-programmed timer expires. If the UPS reaches a low battery alarm, the software shall override the timer and perform an automatic shutdown of each computer. This system requires the optional remote contact board to provide isolated normally closed contacts. This system shall include a shielded primary cable with a 9-pin subminiature D-shell connector, the Multi-Interface Unit (MIU), and shielded secondary cables with RJ11 and 25-pin subminiature D-shell connectors. Cables shall be available in selected lengths from 25 to 300 feet. P. Optional IBM* AS/400* Multi-Interface System An AS/400 Multi-Interface System shall be provided where a single UPS is powering multiple AS/400 units (up to 8). The MultiInterface Unit (MIU) shall provide the required UPS status information to each AS/400 so it can perform an automatic unattended orderly shutdown when necessary. Each AS/400 includes the software required to interface with the UPS. The following status messages are activated in the IBM system: • • • • UPS on (UPS is supplying power) Bypass active (bypass is supplying power) Utility failure (battery is discharging) Battery low (limited battery time remaining) Each AS/400 individually monitors the UPS status to determine when to initiate a quick power down to preserve data and protect hardware during a utility power outage. This system requires the optional remote contact board to provide isolated contacts. This system shall include a shielded primary cable with a 9-pin subminiature D-shell connector, the AS/400 Multi-Interface S300 Specifications Crucial Power Products Unit (MIU), and shielded secondary cables with RJ11 and 9-pin subminiature D-shell connectors. Cables shall be available in selected lengths from 25 to 300 feet. * IBM and AS/400 are trademarks of International Business Machines Corporation. Q. Optional Internal Modem The UPS shall come with an internal modem capable of dialing out from the UPS to notify up to two remote computers, terminals, PC뭩, or pocket pagers when important events occur. The modem will also be capable of accepting incoming calls, with the appropriate security, and connecting to a remote terminal, computer or PC, to perform all those functions normally available on the front panel including viewing monitoring screens, turning the UPS on and off and setting modifiable values. R. Optional SNMP The UPS shall come equipped with an internal SNMP adapter, which will connect the UPS directly to any I.P. based network using either Ethernet or Token Ring communications. The UPS will become a managed device on the network. From a network management station the system administrator shall be capable of monitoring important system measurements, alarm status and alarm history data. The network administrator shall also be capable of executing battery tests, observing the results of such tests and turning the UPS on and off via his SNMP communications network. In the event of a utility failure the SNMP shall continue with live communication without the requirement of additional or separate UPS equipment until such time as the UPS shuts down for Low battery. On resumption of Utility power the SNMP shall resume full SNMP communication automatically. 3.0 EXECUTION 3.1 FIELD QUALITY CONTROL The following inspections and test procedures shall be performed by factory trained field service personnel during the UPS startup. 3.1.1 Visual Inspection • • • • • • • Inspect equipment for signs of damage Verify installation per drawings Inspect cabinets for foreign objects Verify neutral and ground conductors are properly sized and configured Inspect battery cases Inspect battery for proper polarity Verify all printed circuit boards are configured properly 3.1.2 Mechanical Inspection • Check all control wiring connections for tightness • Check all power wiring connections for tightness • Check all terminal screws, nuts, and/or spade lugs for tightness 3.1.3 Electrical Inspection S300 Specifications Crucial Power Products • • • • Check all fuses for continuity Confirm input voltage and phase rotation is correct Verify control transformer connections are correct for voltages being used Assure connection and voltage of the battery string(s) MANUFACTURER뭆FIELD SERVICE 3.2.1 Service Personnel The UPS manufacturer shall directly employ a nationwide service organization, consisting of factory trained field service personnel dedicated to the start-up, maintenance, and repair of UPS and power equipment. The organization shall consist of regional and local offices. The manufacturer shall provide a fully automated national dispatch center to coordinate field service personnel schedules. One toll-free number shall reach a qualified support person 24 hours/day, 7 days/week, 365 days/year. If emergency service is required, response time shall be 20 minutes or less. An automated procedure shall be in place to insure that the manufacturer is dedicating the appropriate technical support resources to match escalating customer needs. 3.2.2 Replacement Parts Stocking Parts shall be available through an extensive network to ensure around-the-clock parts availability throughout the country. Recommended spare parts shall be fully stocked by local field service personnel with back-up available from national parts center and the manufacturing location. The national parts center Customer Support Parts Coordinators shall be on-call 24 hours a day, 7 days a week, 365 days a year for immediate parts availability. Parts from the national parts center shall be shipped within 4 hours on the next available flight out and delivered to the customer뭩 site within 24 hours. 3.2.3 UPS Maintenance Training Maintenance training courses for customer employees shall be available by the UPS manufacturer. This training is in addition to the basic operator training conducted as a part of the system start-up. The training course shall cover UPS theory, location of subassemblies, safety, battery considerations and UPS operational procedures. The course shall include AC to DC conversion and DC to AC inversion techniques as well as control, metering, and feedback circuits to the Printed Circuit Board (PCB) level. Troubleshooting and fault isolation using alarm information and internal self-diagnostics should be stressed. 3.2.4 Maintenance Contracts A complete offering of preventive and full service maintenance contracts for both the UPS system and battery system shall be available. An extended warranty and preventive maintenance package shall be available. Warranty and preventive maintenance service shall be performed by factory-trained service personnel. S300 Specifications Crucial Power Products NOTE: These Guide Specifications comply with the format outlined by the Construction Specifications Institute per CSI MP-2-1 and CSI MP-2-2. Copyright ?2003 Crucial Power Corporation. A division of Emerson Notice and Conditions | Contacts S300 Specifications