Download Series 300 UPS

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Audio power wikipedia , lookup

Electric power system wikipedia , lookup

Electrical substation wikipedia , lookup

Electrification wikipedia , lookup

Pulse-width modulation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage optimisation wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power engineering wikipedia , lookup

Opto-isolator wikipedia , lookup

Islanding wikipedia , lookup

Rectifier wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Power inverter wikipedia , lookup

Power electronics wikipedia , lookup

Metadyne wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Transcript
Crucial Power Products
Series 300 UPS
GUIDE SPECIFICATIONS
for a 10 - 125 kVA
Three-Phase Uninterruptible Power System
CSI 16610 Uninterruptible Power Supply Systems
1.0 GENERAL
1.1 SUMMARY
This specification defines the electrical and mechanical characteristics and requirements for a
continuous-duty three-phase, solid-state, uninterruptible power supply (UPS) system. The UPS
shall provide high-quality AC power for sensitive electronic equipment loads.
1.2 STANDARDS
The UPS shall be designed in accordance with the applicable sections of the current revision of
the following documents. Where a conflict arises between these documents and statements
made herein, the statements in this specification shall govern.
•
•
•
•
•
•
•
•
•
ANSI C62.41 (IEEE 587)
ASME
CSA 22.2, No. 107.1
FCC Part 15, Class A
ISO 9001
National Electrical Code (NFPA-70)
NEMA PE-1
OSHA
UL Standard 1778
The UPS shall be UL listed per UL Standard 1778, and shall be CSA certified.
1.3 SYSTEM DESCRIPTION
1.3.1 Design Requirements - UPS Module
A. Voltage. Input/output voltage specifications of the UPS shall be:
Input: ( ) volts, three-phase, 3-wire-plus-ground.
Output: ( ) volts, three-phase, 4-wire-plus-ground.
B. Output Load Capacity. Specified output load capacity of the UPS shall be ( ) kVA at 0.8
lagging power factor.
C. Field-Installable Power Upgrade. Selected systems shall be able to accept a field-installed
power upgrade to the next highest power rating without an increase in cabinet size, as follows:
10 kVA UPS modules can be field upgraded to 15 kVA
S300 Specifications
Crucial Power Products
20 kVA UPS modules can be field upgraded to 30 kVA
40 kVA UPS modules can be field upgraded to 50 kVA
65 kVA UPS modules can be field upgraded to 75 kVA
100 kVA UPS modules can be field upgraded to 125 kVA
1.3.2 Design Requirements - Matching Battery Cabinet
A. Battery Cells: Sealed, lead-acid, valve-regulated.
B. Reserve Time: ( ) minutes at full load, 0.8 power factor, with ambient temperature between
20 and 30캜.
C. Recharge Time: to 95% capacity within ten (10) times discharge time.
1.3.3 Modes of Operation
The UPS shall be designed to operate as an on-line reverse transfer system in the following
modes:
A. Normal - The critical AC load is continuously supplied by the UPS inverter. The
rectifier/charger derives power from a utility AC source and supplies DC power to the
inverter while simultaneously float-charging a power reserve battery.
B. Emergency - Upon failure of utility AC power, the critical AC load is supplied by the
inverter, which without any switching, obtains power from the battery. There shall be no
interruption in power to the critical load upon failure or restoration of the utility AC
source.
C. Recharge - Upon restoration of utility AC power, after a utility AC power outage, the
rectifier/charger shall automatically restart, walk-in, and gradually assume the inverter
and battery recharge loads.
D. Bypass - If the UPS must be taken out of service for maintenance or repair, or
should the inverter overload capacity be exceeded, the static transfer switch shall
perform a reverse transfer of the load from the inverter to the bypass source with no
interruption in power to the critical AC load.
1.3.4 Performance Requirements
1. AC Input to UPS
A. Voltage Configuration for Standard Units: three-phase, 4-wire plus ground.
B. Voltage Range: + 10%, -25% of nominal.
C. Frequency: Nominal frequency +/- 5%.
D. Power Factor: 0.90 lagging minimum at nominal input voltage and full rated UPS
output load.
S300 Specifications
Crucial Power Products
E. Inrush current: 800% of full load current maximum.
F. Current Limit: 125% of nominal AC input current maximum. 100% of nominal for
optional generator operation.
G. Input Current Walk-In: 20 seconds to full rated input current maximum. Field
selectable 5 or 20 seconds.
H. Current Distortion: 30% THD maximum at full load. An optional input filter shall be
available to reduce input current distortion to 10% THD maximum at full load.
I. Surge Protection: Sustains input surges without damage per criteria listed in ANSI
C62.41-1980.
2. AC Output, UPS Inverter
A. Voltage Configuration: three-phase, 4-wire plus ground.
B. Voltage Regulation:
+/- 1% three-phase RMS average for a balanced three-phase load for
the combined variation effects of input voltage, connected load, battery
voltage, ambient temperature, and load power factor.
+/- 2% three-phase RMS average for a 50% unbalanced load for the
combined variation effects of input voltage, connected load, battery
voltage, ambient temperature, and load power factor.
C. Frequency: Nominal frequency +/- 0.1%.
D. Frequency Slew Rate: 1.0 Hertz per second maximum. Field selectable from 0.1 to
1.0 Hz per second.
E. Phase Displacement:
+/- 1 degree for balanced load.
+/- 3 degrees for 50% unbalanced load.
F. Bypass Line Sync Range: +/- 0.5 Hertz. Field selectable +/- 0.5, 1.0, 3.0, 5.0 Hz.
G. Voltage Distortion:
5% total harmonic distortion (THD) for linear loads.
3% maximum for any single harmonic.
H. Load Power Factor Range: 0.9 leading to 0.5 lagging.
I. Output Power Rating: Rated kVA at 0.8 lagging power factor.
S300 Specifications
Crucial Power Products
J. Overload Capability:
125% for 10 minutes (without bypass source).
150% for 30 seconds (without bypass source).
K. Inverter Output Voltage Adjustment: +/- 5% manual adjustment.
L. Voltage Transient Response:
20% load step +/- 4%
30% load step +/- 5%
50% load step +/- 8%
loss or return of AC input power +/- 1%
manual transfer of 100% load +/- 4%.
M. Transient Recovery Time: to within 1% of output voltage within 50 milliseconds.
N. Voltage Unbalance: balanced load to 20% unbalanced load +/- 1%, 50%
unbalanced load +/-2%, 100% unbalanced load +/- 5%.
O. Fault Clearing: Sub-cycle current of at least 300%.
1.4 ENVIRONMENTAL CONDITIONS
The UPS shall be able to withstand the following environmental conditions without damage or
degradation of operating characteristics:
A. Operating Ambient Temperature:
UPS Module: 32캟 to 105캟 (0캜 to 40캜).
Battery: 77 +/- 9캟 (25 +/- 5캜).
B. Storage/Transport Ambient Temperature:
-4캟 to 158캟 (-20캜 to 70캜).
C. Relative Humidity:
0 to 95%, non-condensing.
D. Altitude:
Operating: to 6600 ft. (2 000 meters) above Mean Sea Level. Derated for higher altitude
applications.
Storage/Transport: to 40,000 ft. (12 200 meters) above Mean Sea Level.
S300 Specifications
Crucial Power Products
E. Audible Noise:
Noise generated by the UPS under any condition of normal operation shall not exceed
65 dBA measured 1 meter from surface of the UPS.
1.5 SUBMITTALS
1.5.1 Proposal Submittals
Submittals with the proposal shall include:
a. System configuration with single-line diagrams.
b. Functional relationship of equipment including weights, dimensions, and heat
dissipation.
c. Descriptions of equipment to be furnished, including deviations from these
specifications.
d. Size and weight of shipping units to be handled by installing contractor.
e. Detailed layouts of customer power and control connections.
f. Detailed installation drawings including all terminal locations.
1.5.2 UPS Delivery Submittals
Submittals upon UPS delivery shall include:
a. A complete set of submittal drawings.
b. One (1) instruction manual that shall include a functional description of the
equipment with block diagrams, safety precautions, instructions, step-by-step operating
procedures and routine maintenance guidelines, including illustrations.
1.6 WARRANTY
1.6.1 UPS Module
The UPS manufacturer shall warrant the UPS module against defects in materials and
workmanship for 12 months after initial start-up or 18 months after ship date, whichever period
expires first.
1.6.2 Battery
The battery manufacturer뭩 standard warranty shall be passed through to the end user.
1.7 QUALITY ASSURANCE
1.7.1 Manufacturer Qualifications
S300 Specifications
Crucial Power Products
A minimum of twenty year뭩 experience in the design, manufacture, and testing of solid-state
UPS systems is required. The system shall be designed and manufactured according to world
class quality standards. The manufacturer shall be ISO 9001 certified.
1.7.2 Factory Testing
Before shipment, the manufacturer shall fully and completely test the system to assure
compliance with the specification. These tests shall include operational discharge and recharge
tests on at least a one-minute battery plant to assure guaranteed rated performance.
2.0 PRODUCT
2.1 FABRICATION
2.1.1 Materials
All materials of the UPS shall be new, of current manufacture, high grade and free from all
defects and shall not have been in prior service except as required during factory testing.
The maximum working voltage, current, and di/dt of all solid-state power components and
electronic devices shall not exceed 75% of the ratings established by their manufacturer. The
operating temperature of solid-state component sub-assembly shall not be greater than 75% of
their ratings. Electrolytic capacitors shall be computer grade and be operated at no more than
95% of their voltage rating at the maximum rectifier charging voltage.
2.1.2 Wiring
Wiring practices, materials and coding shall be in accordance with the requirements of the
National Electrical Code (NFPA 70). All bolted connections of bus bars, lugs, and cables shall
be in accordance with requirements of the National Electrical Code and other applicable
standards. All electrical power connections are to be torqued to the required value and marked
with a visual indicator.
Provision shall be made for power cables to enter or leave from the top or bottom of the UPS
cabinet.
2.1.3 Construction and Mounting
The UPS unit, comprised of input autotransformer, rectifier/charger with input filter, inverter,
static transfer switch, and maintenance bypass switch, shall be housed in a single free-standing
NEMA type 1 enclosure. Cabinet doors/covers shall require a tool for gaining access. Casters
and leveling feet shall be provided for ease of installation. Front access only shall be required
for expedient servicing, adjustments, and installation. The UPS cabinet shall be structurally
adequate and have provisions for hoisting, jacking, and forklift handling.
The UPS cabinet shall be cleaned, primed, and painted with the manufacturer뭩 standard color.
The UPS shall be constructed of replaceable subassemblies. Printed circuit assemblies shall be
plug-in. Like assemblies and like components shall be interchangeable.
2.1.4 Cooling
Cooling of the UPS shall be by forced-air. Redundant fans shall be used. Low velocity fans shall
be used to minimize audible noise output. Fan power shall be provided by the UPS output.
S300 Specifications
Crucial Power Products
The thermal design, along with all thermal and ambient sensors, shall be coordinated with the
protective devices before excessive component or internal cabinet temperatures are exceeded.
2.1.5 Grounding
The AC output neutral shall be electrically isolated from the UPS chassis. The UPS chassis
shall have an equipment ground terminal. Provisions for local bonding shall be provided.
2.2 COMPONENTS
2.2.1 Input Autotransformer
An input autotransformer shall be included. The input autotransformer shall be factory installed
inside the UPS module cabinet. 208/208 and 480/208 UPS module input/output voltage
configurations shall be served by the same transformer through tap selection for additional
system flexibility.
2.2.2 Rectifier/Charger
A. General
The term rectifier/charger shall denote the solid-state equipment and controls necessary to
convert incoming AC power to regulated DC power for input to the inverter and for battery
charging. The rectifier/charger shall be a phase-controlled, solid-state SCR type with constant
voltage/current limiting control circuitry.
B. AC Input Current Limiting
The rectifier/charger unit shall be provided with AC input current limiting whereby the maximum
input current shall be limited to 125% of the full input current rating. The rectifier/charger shall
operate at a reduced current limit mode whenever the critical load is powered from the UPS
static bypass circuit such that the maximum UPS input current will not exceed 125% of full load
input current. In addition, the rectifier/charger input current limit shall be automatically reduced
to 25% of full load input current whenever the critical load is powered from the UPS internal
maintenance bypass circuit. An optional second circuit shall limit input current to 100% of rated
full load current when activated by a customer supplied contact closure to signal a customer
function such as generator operation.
C. Input Current Walk-In
The rectifier/charger shall contain a timed walk-in circuit that causes the unit to gradually
assume the load over a 20-second time interval after input voltage is applied. Walk-in time shall
be field selectable for 5 or 20 seconds.
D. Fuse Failure Protection
Power semiconductors in the rectifier/charger shall be fused with fast-acting fuses, so that loss
of any one power semiconductor shall not cause cascading failures.
E. DC Filter
S300 Specifications
Crucial Power Products
The rectifier/charger shall have an output filter to minimize ripple voltage into the battery. Under
no conditions shall ripple voltage into the battery exceed 2% RMS. The filter shall be adequate
to insure that the DC output of the rectifier/charger will meet the input requirements of the
inverter. The inverter shall be able to operate from the rectifier/charger with the battery
disconnected.
F. Automatic Restart
Upon restoration of utility AC power, after a utility AC power outage and prior to a UPS
automatic end-of-discharge shutdown, the rectifier/charger shall automatically restart, walk-in,
and gradually assume the inverter and battery recharge loads. Upon restoration of utility AC
power, after a utility AC power outage and after a full UPS automatic end-of-discharge
shutdown, the UPS will (customer selectable) automatically restart, performing the normal UPS
start up walk-in.
G. Battery Recharge
In addition to supplying power for the inverter load, the rectifier/charger shall be capable of
producing battery charging current sufficient to replace 95% of the battery discharge power
within ten (10) times the discharge time. After the battery is recharged, the rectifier/charger shall
maintain the battery at full charge until the next emergency operation.
H. Overvoltage Protection
There shall be DC over-voltage protection so that if the DC voltage rises to the pre-set limit, the
UPS is to shut down automatically and initiate an uninterrupted load transfer to the static
bypass line.
2.2.3 Inverter
A. General
The term inverter shall denote the solid-state equipment and controls to convert DC power from
the rectifier/charger or battery to regulated AC power for supporting the critical load. The
inverter shall be a transistorized, phase-controlled, pulse width modulated (PWM) design
capable of providing the specified AC output.
B. Overload Capability
The inverter shall be capable of supplying current and voltage for overloads exceeding 100%
and up to 150% of full load current. A status indicator and audible alarm shall indicate overload
operation. The UPS shall transfer the load to bypass when overload capacity is exceeded.
C. Fault Clearing and Current Limit
The inverter shall be capable of supplying an overload current of 150% of its full-load rating for
thirty seconds. For greater currents or longer time duration, the inverter shall have electronic
current-limiting protection to prevent damage to components. The inverter shall be selfprotecting against any magnitude of connected output overload. Inverter control logic shall
sense and disconnect the inverter from the critical AC load without the requirement to clear
protective fuses.
D. Output Power Transformer
S300 Specifications
Crucial Power Products
A dry type power transformer shall be provided for the inverter AC output. It shall have copper
wiring exclusively. The transformers hottest spot winding temperature shall not exceed the
temperature limit of the transformer insulation class of material when operating at full load at
maximum ambient temperature.
E. Phase Balance
Electronic controls shall be provided to regulate each phase so that an unbalance loading will
not cause the output voltage to go outside the specified voltage unbalance or phase
displacement.
F. Fuse Failure Protection
Power semiconductors in the inverter unit shall be fused with fast-acting fuses, so that loss of
any one power semiconductor will not cause cascading failures.
G. Inverter Shutdown
For rapid removal of the inverter from the critical load, the inverter control electronics shall
instantaneously turn off the inverter transistors. Simultaneously, the static transfer switch shall
be turned on to maintain continuous power to the critical load.
H. Inverter DC Protection
The inverter shall be protected by the following disconnect levels:
• DC Overvoltage Shutdown
• DC Undervoltage Warning (Low Battery Reserve), user adjustable from 1 to 99 minutes
• DC Undervoltage Shutdown (End of Discharge)
I. Overdischarge Protection
To prevent battery damage from overdischarging, the UPS control logic shall automatically raise
the shutdown voltage set point as discharge time increases beyond fifteen (15) minutes.
J. Inverter Output Voltage Adjustment
The inverter shall use a manual control to adjust the output voltage from +/- 5% of the nominal
value.
K. Output Frequency
The output frequency of the inverter shall be controlled by an oscillator. The oscillator shall be
temperature compensated and hold the inverter output frequency to +/- 0.1% for steady state
and transient conditions. Drift shall not exceed 0.1% during a 24-hour period. Total frequency
deviation, including short time fluctuations and drift, shall not exceed 0.1% from the rated
frequency.
2.2.4 Display and Controls
A. Monitoring and Control
S300 Specifications
Crucial Power Products
The UPS shall be provided with a microprocessor based unit status display and controls section
designed for convenient and reliable user operation. A system power flow diagram shall be
provided as part of the monitoring and controls sections which depicts a single-line diagram of
the UPS. Illuminated visual indicators shall be of the long-life light-emitting diode (LED) type. All
of the operator controls and monitors shall be located on the front of the UPS cabinet. The
monitoring functions such as metering, status and alarms shall be displayed on an
alphanumeric LCD display. Additional features of the monitoring system shall include:
• Menu-driven display with text format selectable in five (5) languages (English, German,
French, Spanish, or Italian)
• Real time clock (time and date)
• Alarm history with time and date stamp
• Battery back-up memory
B. Metering
The following parameters shall be displayed:
•
•
•
•
•
•
•
•
•
•
Input AC voltage line-to-line and line-to-neutral for each phase
Input AC current for each phase
Input frequency
Battery voltage
Battery charge/discharge current
Output AC voltage line-to-line and line-to-neutral for each phase
Output AC current for each phase
Output frequency
Percent of rated load being supplied by the UPS
Battery time left during battery operation
C. Alarm Messages
The following alarm messages shall be displayed:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Input power out of tolerance
Input phase rotation incorrect
Incorrect input frequency
Charger in reduced current mode
Battery Charger Problem
Battery failed test
Low battery warning (adjustable 1 to 99 minutes)
Low battery shutdown
DC bus overvoltage
Bypass frequency out of range
Load transferred to bypass
Excessive retransfers attempted
Static switch failure
UPS output not synchronized to input power
Input power single phased
Input voltage sensor failed
Inverter leg over current in X-phase
Output undervoltage
Output overvoltage
S300 Specifications
Crucial Power Products
•
•
•
•
•
•
•
•
•
•
•
Output overcurrent
System output overloaded
Load transferred to bypass due to overload
Overload shutdown
Control Error
Critical power supply failure
Load transferred due to internal protection
External shutdown (remote EPO activated)
Fan failure
Overtemperature shutdown impending
Overtemperature shutdown
An audible alarm shall be provided and activated by any of the above alarm conditions.
D. Status Messages
The following UPS status messages shall be displayed:
•
•
•
•
•
•
Normal operation
Load on maintenance bypass
Load on UPS
Load on static bypass
System shutdown
UPS on battery
E. Controls
UPS start-up, shutdown, and maintenance bypass operations shall be accomplished by a single
rotary control switch. An advisory display and menu-driven user prompts shall be provided to
guide the operator through system operation without the use of additional manuals.
Pushbuttons shall be provided to display the status of the UPS and to test and reset visual and
audible alarms.
F. Power Status Diagram
A mimic panel shall be provided to depict a single line diagram of the UPS. Indicating lights
shall be integrated within the single line diagram to illustrate the status of the UPS. Two LEDs
located on the diagram shall indicate whether UPS input and/or output power is present. The
diagram shall be color coded with the positions of the rotary control switch for visual
confirmation of the UPS operating mode.
G. On-Line Battery Test
The UPS shall be provided with a menu driven On-Line Battery Test feature. The test shall
ensure the capability of the battery to supply power to the inverter while the load is supplied
power in the normal mode. If the battery fails the test, the system shall automatically do the
following:
1.
2.
3.
4.
Transfer the load to bypass
Restart the rectifier/charger
Display a warning message
Sound an audible alarm
S300 Specifications
Crucial Power Products
5. Retransfer the load back to normal mode
The battery test feature shall have the following user selectable options:
1.
2.
3.
4.
DC bus voltage threshold (pass/fail value)
Interval between tests (2 to 9 weeks)
Date and time of initial test
Enable/disable test
2.2.5 Static Transfer Switch
A. General
A static transfer switch and bypass circuit shall be provided as an integral part of the UPS. The
static switch shall be a naturally commutated high-speed static (SCR-type) device rated to
conduct full load current continuously. The switch shall have an overload rating of 125% rated
load continuously, 200% rated load for thirty seconds, and 2000% rated load for two cycles. The
static transfer switch control logic shall contain an automatic transfer control circuit that senses
the status of the inverter logic signals, and operating and alarm conditions. This control circuit
shall provide an uninterrupted transfer of the load to an alternate bypass source, without
exceeding the transient limits specified herein, when an overload or malfunction occurs within
the UPS, or for bypassing the UPS for maintenance.
B. Uninterrupted Transfer
The transfer control logic shall automatically turn on the static transfer switch, transferring the
critical AC load to the bypass source, after the transfer logic senses any of the following
conditions:
•
•
•
•
Inverter overload capacity exceeded
Critical AC load overvoltage or undervoltage
Battery protection period expired
UPS fault condition
The transfer control logic shall inhibit an automatic transfer of the critical load to the bypass
source if any of the following conditions are present:
• Inverter/bypass voltage difference exceeding preset limits
• Bypass frequency out of limits
• Bypass out-of-synchronization range with inverter output
C. Uninterrupted Retransfer
Retransfer of the critical AC load from the bypass source to the inverter output shall be
automatically initiated unless inhibited by manual control. The transfer control logic shall inhibit
an automatic retransfer of the critical load to the inverter if one of the following condition exists:
•
•
•
•
Bypass out of synchronization range with inverter output
Inverter/bypass voltage difference exceeding preset limits
Overload condition exists in excess of inverter full load rating
UPS fault condition present
S300 Specifications
Crucial Power Products
2.2.6 Maintenance Bypass Switch
A. General
A manually operated maintenance bypass switch shall be incorporated into the UPS cabinet to
directly connect the critical load to the input AC power source, bypassing the rectifier/charger,
inverter, and static transfer switch.
B. Isolation
All energized terminals shall be shielded to ensure that maintenance personnel do not
inadvertently come in contact with energized parts or terminals. A means to de-energize the
static switch shall be provided when the UPS is in the maintenance bypass mode of operation.
C. Maintenance Capability
With the critical load powered from the maintenance bypass circuit, it shall be possible to check
out the operation of the rectifier/charger, inverter, battery, and static transfer switch.
2.2.7 Battery Power Pack
The battery power pack shall include sealed, lead-acid valve regulated battery cells housed in a
separate cabinet that matches the UPS cabinet styling to form an integral system line-up.
Battery cells shall be mounted on slide-out trays for ease of maintenance. A disconnect means
shall be included for isolation of the battery pack from the UPS module. Casters and leveling
feet shall also be provided with the battery power pack cabinet for ease of installation.
2.2.8 Accessories (Optional Equipment)
A. Optional Input Filter
The rectifier/charger shall include an input filter to reduce reflected input current distortion to
10% THD at full load with nominal input voltage. Another benefit of the input filter shall be to
maintain the input power factor at 0.90 lagging minimum from full load to half load with nominal
input voltage.
B. Optional Input Isolation Transformer
An input isolation transformer shall be included. The isolation transformer shall be a delta-wye
configuration to provide common mode noise attenuation for all system operating modes
including while on bypass. In addition to the noise attenuation feature, this transformer shall be
provided for the following applications:
1. Operation from delta utility configuration, or
2. Any voltage configuration with line-to-neutral loads on the UPS output where an input
neutral conductor is not supplied
The input isolation transformer shall be factory installed inside the UPS module cabinet.
208/208 and 480/208 UPS module input/output voltage configurations shall be served by the
same transformer through tap selection for additional system flexibility.
C. Optional External Maintenance Bypass Cabinet
S300 Specifications
Crucial Power Products
A matching external maintenance bypass cabinet shall be provided to enable the UPS module
to be completely isolated from the electrical system while the critical load is powered through
the external maintenance bypass line. This optional cabinet shall provide make-before-break
operation for transfers to and from the external maintenance bypass line with a single rotary
switch. The following components shall be standard: single rotary switch with auxiliary contacts,
inter-cabinet wiring, casters, and leveling feet. The following components shall be optional: input
circuit breaker, shielded isolation transformer, and load (output) circuit breaker. This matching
cabinet shall bolt to the right side of the UPS module with a barrier shield to separate the two
cabinets. Only front access shall be required for installation and service.
D. Optional Slim-Line Distribution Cabinet
A matching distribution cabinet shall be provided for flexible cable distribution of power from the
UPS output to the critical loads. The distribution cabinet shall include one or two 42-pole (225
Amp) panelboards. Both plug-in and bolt-in style panelboards shall be available to
accommodate specific site requirements. A 225 Amp main circuit breaker shall be provided with
each panelboard.
The slim-line distribution cabinet shall be designed as a bolt-on section to the right side of the
UPS module cabinet for field installation by the installing contractor. The slim-line distribution
cabinet shall add no more than ten (10) inches to the width of the UPS system. Branch circuit
breakers and flexible distribution cables shall be specified by the end user or the installing
contractor.
E. Optional Remote Contact Board
Isolated Form C contacts shall be provided to indicate a change of status of each of the
following conditions:
•
•
•
•
•
UPS on battery alarm
Low battery reserve alarm
Load on bypass alarm
Summary alarm
New alarm - a separate alarm for a second summary alarm
F. Optional Remote Status Panel
A remote status panel shall be provided and shall include the following:
•
•
•
•
•
•
•
•
Load on UPS LED
Load On Bypass LED
Battery Discharge LED
Low Battery Reserve LED
UPS Alarm Condition LED
New Alarm Condition LED (for a second UPS alarm condition)
Audible Alarm with Reset pushbutton
Lamp Test/Reset pushbutton
The remote status panel shall be provided in a NEMA Type 1 enclosure for wall mounting.
G. Optional RS-232C Interface Port
S300 Specifications
Crucial Power Products
An RS-232C interface port shall be provided for remote display of UPS status information at a
computer terminal (by others). The UPS via the RS-232C port will support an Enhanced
Terminal interface feature. The UPS will 밺raw?a picture of its own display panel on the remote
terminal screen. The UPS will treat the terminal as if it were the front panel LCD display and
pushbuttons, enabling the remote user to view screens, set any modifiable values, turn the load
on or off, or otherwise be able to perform any functions possible through the normal front panel
display.
H. Optional IBM* System/38* Power Warning Signal
An isolated signal, normally closed when utility power fails and the UPS battery is discharging,
shall be provided for user connection to computer power warning interface.
* IBM, System/38, and AS/400 are trademarks of International Business Machines Corporation.
I. Optional IBM* AS/400* UPS Signal
The following isolated normally open contacts shall be provided for user connection to an IBM
AS/400 UPS signal interface:
•
•
•
•
UPS on (UPS is supplying power)
Bypass active (bypass is supplying power)
Utility failure (battery is discharging)
Battery low (limited battery time remaining)
A 50-foot shielded cable, compliant with NEMA Class 2 for plenum applications, with subminiature 9-pin D-type connector, shall be provided for connection to the signal interface.
J. Optional Contact Isolator Board
A contact isolator board shall be included to provide an interface for the following:
• External battery circuit breaker UVR (undervoltage release)
• External battery circuit breaker auxiliary contacts
• Reduced AC input current limit (shall reduce UPS input current limit to 100% of nominal
when activated by a user supplied contact closure).
K. Optional SiteScan/Sitemaster Interface
An interface board shall be provided to communicate with Crucial Power site monitoring
products. Monitored equipment parameters and alarms shall be transmitted through a twistedpair control wiring connection (cable not included in option) for display at the centralized
terminal. Note that use of this option precludes the ability to also select the RS-232C option.
L. Optional DC Ground Fault Alarm
This feature shall annunciate an alarm condition when either the positive (+) or negative (-) DC
bus is grounded.
M. Optional Battery Circuit Breaker
S300 Specifications
Crucial Power Products
A battery circuit breaker shall be provided to isolate the battery from the UPS. This breaker shall
have an undervoltage release (UVR) and auxiliary contacts, and shall be in a separate wall
mounted NEMA-1 enclosure. The battery breaker provides a manual disconnecting means,
short circuit protection, and overcurrent protection for the battery system. When opened, there
shall be no battery voltage in the UPS enclosure. The UPS shall be automatically disconnected
from the battery by opening the breaker when the battery reaches the minimum discharge
voltage level.
N. Optional Computer Interface System
A Computer Interface System shall be provided to perform an automatic unattended orderly
shutdown of the customer뭩 operating system when necessary. This system shall include the
software required to interface the UPS to the computer. The software monitors the UPS for
power failure and low battery alarm while operating as a background task on the computer.
After a power failure occurs, the software shall perform an automatic shutdown when the preprogrammed timer expires. If the UPS reaches a low battery alarm, the software shall override
the timer and perform an automatic shutdown. This system requires the optional remote contact
board to provide isolated normally closed contacts. This system shall include a shielded
interface cable with a 25-pin subminiature D-shell connector to fit the serial port of the computer
file server. Cable shall be available in selected lengths from 25 to 300 feet.
O. Optional Multi-Computer Interface System
A Multi-Computer Interface System shall be provided where a single UPS is powering multiple
computer file servers (up to 48). This system shall perform an automatic unattended orderly
shutdown of the customer뭩 operating system in each computer when necessary. The MultiInterface Unit (MIU) shall provide the hardware required to interface the UPS to each computer.
The software provided allows each computer to monitor the UPS for power failure and low
battery alarm while operating as a background task. After a power failure occurs, the software
shall perform an automatic shutdown of each computer when the pre-programmed timer
expires. If the UPS reaches a low battery alarm, the software shall override the timer and
perform an automatic shutdown of each computer. This system requires the optional remote
contact board to provide isolated normally closed contacts. This system shall include a shielded
primary cable with a 9-pin subminiature D-shell connector, the Multi-Interface Unit (MIU), and
shielded secondary cables with RJ11 and 25-pin subminiature D-shell connectors. Cables shall
be available in selected lengths from 25 to 300 feet.
P. Optional IBM* AS/400* Multi-Interface System
An AS/400 Multi-Interface System shall be provided where a single UPS is powering multiple
AS/400 units (up to 8). The MultiInterface Unit (MIU) shall provide the required UPS status
information to each AS/400 so it can perform an automatic unattended orderly shutdown when
necessary. Each AS/400 includes the software required to interface with the UPS. The following
status messages are activated in the IBM system:
•
•
•
•
UPS on (UPS is supplying power)
Bypass active (bypass is supplying power)
Utility failure (battery is discharging)
Battery low (limited battery time remaining)
Each AS/400 individually monitors the UPS status to determine when to initiate a quick power
down to preserve data and protect hardware during a utility power outage. This system requires
the optional remote contact board to provide isolated contacts. This system shall include a
shielded primary cable with a 9-pin subminiature D-shell connector, the AS/400 Multi-Interface
S300 Specifications
Crucial Power Products
Unit (MIU), and shielded secondary cables with RJ11 and 9-pin subminiature D-shell
connectors. Cables shall be available in selected lengths from 25 to 300 feet.
* IBM and AS/400 are trademarks of International Business Machines Corporation.
Q. Optional Internal Modem
The UPS shall come with an internal modem capable of dialing out from the UPS to notify up to
two remote computers, terminals, PC뭩, or pocket pagers when important events occur. The
modem will also be capable of accepting incoming calls, with the appropriate security, and
connecting to a remote terminal, computer or PC, to perform all those functions normally
available on the front panel including viewing monitoring screens, turning the UPS on and off
and setting modifiable values.
R. Optional SNMP
The UPS shall come equipped with an internal SNMP adapter, which will connect the UPS
directly to any I.P. based network using either Ethernet or Token Ring communications. The
UPS will become a managed device on the network. From a network management station the
system administrator shall be capable of monitoring important system measurements, alarm
status and alarm history data. The network administrator shall also be capable of executing
battery tests, observing the results of such tests and turning the UPS on and off via his SNMP
communications network. In the event of a utility failure the SNMP shall continue with live
communication without the requirement of additional or separate UPS equipment until such time
as the UPS shuts down for Low battery. On resumption of Utility power the SNMP shall resume
full SNMP communication automatically.
3.0 EXECUTION
3.1 FIELD QUALITY CONTROL
The following inspections and test procedures shall be performed by factory trained field service
personnel during the UPS startup.
3.1.1 Visual Inspection
•
•
•
•
•
•
•
Inspect equipment for signs of damage
Verify installation per drawings
Inspect cabinets for foreign objects
Verify neutral and ground conductors are properly sized and configured
Inspect battery cases
Inspect battery for proper polarity
Verify all printed circuit boards are configured properly
3.1.2 Mechanical Inspection
• Check all control wiring connections for tightness
• Check all power wiring connections for tightness
• Check all terminal screws, nuts, and/or spade lugs for tightness
3.1.3 Electrical Inspection
S300 Specifications
Crucial Power Products
•
•
•
•
Check all fuses for continuity
Confirm input voltage and phase rotation is correct
Verify control transformer connections are correct for voltages being used
Assure connection and voltage of the battery string(s)
MANUFACTURER뭆FIELD SERVICE
3.2.1 Service Personnel
The UPS manufacturer shall directly employ a nationwide service organization, consisting of
factory trained field service personnel dedicated to the start-up, maintenance, and repair of UPS
and power equipment. The organization shall consist of regional and local offices.
The manufacturer shall provide a fully automated national dispatch center to coordinate field
service personnel schedules. One toll-free number shall reach a qualified support person 24
hours/day, 7 days/week, 365 days/year. If emergency service is required, response time shall
be 20 minutes or less.
An automated procedure shall be in place to insure that the manufacturer is dedicating the
appropriate technical support resources to match escalating customer needs.
3.2.2 Replacement Parts Stocking
Parts shall be available through an extensive network to ensure around-the-clock parts
availability throughout the country.
Recommended spare parts shall be fully stocked by local field service personnel with back-up
available from national parts center and the manufacturing location. The national parts center
Customer Support Parts Coordinators shall be on-call 24 hours a day, 7 days a week, 365 days
a year for immediate parts availability. Parts from the national parts center shall be shipped
within 4 hours on the next available flight out and delivered to the customer뭩 site within 24
hours.
3.2.3 UPS Maintenance Training
Maintenance training courses for customer employees shall be available by the UPS
manufacturer. This training is in addition to the basic operator training conducted as a part of
the system start-up.
The training course shall cover UPS theory, location of subassemblies, safety, battery
considerations and UPS operational procedures. The course shall include AC to DC conversion
and DC to AC inversion techniques as well as control, metering, and feedback circuits to the
Printed Circuit Board (PCB) level. Troubleshooting and fault isolation using alarm information
and internal self-diagnostics should be stressed.
3.2.4 Maintenance Contracts
A complete offering of preventive and full service maintenance contracts for both the UPS
system and battery system shall be available. An extended warranty and preventive
maintenance package shall be available. Warranty and preventive maintenance service shall be
performed by factory-trained service personnel.
S300 Specifications
Crucial Power Products
NOTE: These Guide Specifications comply with the format outlined by the Construction
Specifications Institute per CSI MP-2-1 and CSI MP-2-2.
Copyright ?2003 Crucial Power Corporation. A division of Emerson
Notice and Conditions | Contacts
S300 Specifications