Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
DG Protection Requirements for DG Interconnection Protection Requirements for DG Interconnection Basic functional requirements for all cases: The Typical Protection Requirements apply mainly to the FIRST distributed generator to be connected onto a particular distribution feeder. If there are more than ONE distributed generators connected onto the same distribution feeder, the interactions between distributed generators must be studied to determine the impacts, especially islanding issues. Increase in distribution fault levels due to DG fault contribution must be reviewed in order to ensure correct interrupting rating of distribution equipment and proper protection setting coordination. DG must meet FortisAlberta’s Voltage-Flicker and Power Quality requirements. Typical Protection Requirements for DG Interconnection: Case 1 Generator Type: Interconnection Type: Synchronous Generator Export to Utility PROTECTION REQUIREMENT Transfer tripping the DG interconnecting breaker from substation feeder breaker Transfer tripping to have Fail Safe feature (i.e. the DG interconnecting breaker will be tripped if telecommunication is not available for any reason) (Note: If DG islanding with utilities’ distribution load is possible for any single contingency condition, additional transfer tripping logic/scheme will be required) Directional over-current protection on the interconnected feeder breaker, unless the maximum fault contribution from the DG is less than the instantaneous setting of the nondirectional protection of the interconnected feeder breaker Transfer tripping the DG interconnecting breaker from any feeder OCR (Oil Circuit Recloser) which, if opened, could create an islanding situation of the DG with utilities’ distribution feeder load Transfer tripping to have Fail Safe feature (i.e. the DG interconnecting breaker will be tripped if telecommunication is not available for any reason) Configuration of the utility side (i.e. 25 kV side) of the interconnecting transformer must be grounded Y DG must have protective device(s) to detect and clear any distribution fault FUNCTIONAL PURPOSE To prevent islanding of DG with utilities’ distribution feeder load, in the event that, the feeder breaker is opened for any reason To prevent the unnecessary tripping of the interconnected feeder for any distribution fault occurred on the adjacent distribution feeder To prevent islanding of DG with utilities’ distribution feeder load, in the event that, the feeder OCR is opened for any reason To prevent any over-voltage condition imposed on distribution equipment caused by line-to-ground fault after the utility source is cleared (If generator side (i.e. low voltage) configuration is grounded wye, the generator windings must be effectively grounded. To prevent and/or minimize the injury/damage of personnel (including on the interconnected feeder DG must have over/under voltage protection DG must have over/under frequency protection the public) and equipment caused by any distribution feeder fault To protect the connected distribution equipment and load from over/under voltage damage To protect the connected distribution equipment and load from over/under frequency damage Typical Protection Requirements for DG Interconnection: Case 2 Generator Type: Interconnection Type: Synchronous Generator NO Export to Utility PROTECTION REQUIREMENT Directional over-current protection (looking into the utility system at the interconnection point) to trip the interconnecting breaker at the DG site (i.e. Trip on any current flow into the utility system from the DG) FUNCTIONAL PURPOSE To prevent any possibility of export from the DG to the utility system Directional over-current protection on the interconnected feeder breaker, unless the maximum fault contribution from the DG is less than the instantaneous setting of the nondirectional protection of the interconnected feeder breaker Configuration of the utility side (i.e. 25 kV side) of the interconnecting transformer must be grounded Y To prevent the unnecessary tripping of the interconnected feeder for any distribution fault occurred on the adjacent distribution feeder DG must have over/under voltage protection DG must have over/under frequency protection To provide fault detection and fault clearing for any distribution fault on the interconnected feeder To prevent any over-voltage condition imposed on distribution equipment caused by line-to-ground fault after the utility source is cleared. If generator side (i.e. low voltage) configuration is grounded wye, the generator windings must be effectively grounded. To protect the connected distribution equipment and load from over/under voltage damage To protect the connected distribution equipment and load from over/under frequency damage Typical Protection Requirements for DG Interconnection: Case 3 Generator Type: Interconnection Type: Induction Generator Export to Utility PROTECTION REQUIREMENT Transfer tripping the DG interconnecting breaker from substation feeder breaker, unless the DG can NOT self excite Transfer tripping to have Fail Safe feature (i.e. the DG interconnecting breaker will be tripped if telecommunication is not available for any reason) (Note: If DG islanding with utilities’ distribution load is possible for any single contingency condition, additional transfer tripping logic/scheme will be required) Directional over-current protection on the interconnected feeder breaker, unless the maximum fault contribution from the DG is less than the instantaneous setting of the nondirectional protection of the interconnected feeder breaker Transfer tripping the DG interconnecting breaker from any feeder OCR (Oil Circuit Recloser) which, if opened, could create an islanding situation of the DG with utilities’ distribution feeder load, unless the DG can NOT self excite Transfer tripping to have Fail Safe feature (i.e. the DG interconnecting breaker will be tripped if telecommunication is not available for any reason) Configuration of the utility side (i.e. 25 kV side) of the interconnecting transformer must be grounded Y FUNCTIONAL PURPOSE To prevent islanding of DG with utilities’ distribution feeder load, in the event that, the feeder breaker is opened for any reason To prevent the unnecessary tripping of the interconnected feeder for any distribution fault occurred on the adjacent distribution feeder To prevent islanding of DG with utilities’ distribution feeder load, in the event that, the feeder OCR is opened for any reason To prevent any over-voltage condition imposed on distribution equipment caused by line-to-ground fault after the utility source is cleared. If generator side (i.e. low voltage) configuration is grounded wye, the generator windings DG must have protective device(s) to detect and clear any distribution fault on the interconnected feeder, unless the DG can NOT self excite DG must have over/under voltage protection DG must have over/under frequency protection must be effectively grounded. To prevent and/or minimize the injury/damage of personnel (including the public) and equipment caused by any distribution feeder fault To protect the connected distribution equipment and load from over/under voltage damage To protect the connected distribution equipment and load from over/under frequency damage Typical Protection Requirements for DG Interconnection: Case 4 Generator Type: Interconnection Type: Induction Generator NO Export to Utility PROTECTION REQUIREMENT Directional over-current protection (looking into the utility system at the interconnection point) to trip the interconnecting breaker at the DG site (i.e. Trip on any current flow into the utility system from the DG) FUNCTIONAL PURPOSE To prevent any possibility of export from the DG to the utility system Directional over-current protection on the interconnected feeder breaker, unless the maximum fault contribution from the DG is less than the instantaneous setting of the nondirectional protection of the interconnected feeder breaker Configuration of the utility side (i.e. 25 kV side) of the interconnecting transformer must be grounded Y To prevent the unnecessary tripping of the interconnected feeder for any distribution fault occurred on the adjacent distribution feeder DG must have over/under voltage protection DG must have over/under frequency protection To provide fault detection and fault clearing for any distribution fault on the interconnected feeder To prevent any over-voltage condition imposed on distribution equipment caused by line-to-ground fault after the utility source is cleared (If generator side (i.e. low voltage) configuration is grounded wye, the generator windings must be effectively grounded. To protect the connected distribution equipment and load from over/under voltage damage To protect the connected distribution equipment and load from over/under frequency damage Typical Protection Requirements for DG Interconnection: Case 5 Generator Type: Interconnection Type: Inverter Generator Export to Utility PROTECTION REQUIREMENT Transfer tripping the DG interconnecting breaker from substation feeder breaker, unless the DG can NOT self excite Transfer tripping to have Fail Safe feature (i.e. the DG interconnecting breaker will be tripped if telecommunication is not available for any reason) (Note: If DG islanding with utilities’ distribution load is possible for any single contingency condition, additional transfer tripping logic/scheme will be required) Directional over-current protection on the interconnected feeder breaker, unless the maximum fault contribution from the DG is less than the instantaneous setting of the nondirectional protection of the interconnected feeder breaker Transfer tripping the DG interconnecting breaker from any feeder OCR (Oil Circuit Recloser) which, if opened, could create an islanding situation of the DG with utilities’ distribution feeder load, unless the DG can NOT self excite Transfer tripping to have Fail Safe feature (i.e. the DG interconnecting breaker will be tripped if telecommunication is not available for any reason) Configuration of the utility side (i.e. 25 kV side) of the interconnecting transformer must be grounded Y FUNCTIONAL PURPOSE To prevent islanding of DG with utilities’ distribution feeder load, in the event that, the feeder breaker is opened for any reason To prevent the unnecessary tripping of the interconnected feeder for any distribution fault occurred on the adjacent distribution feeder To prevent islanding of DG with utilities’ distribution feeder load, in the event that, the feeder OCR is opened for any reason To prevent any over-voltage condition imposed on distribution equipment caused by line-to-ground fault after the utility source is cleared. If generator side (i.e. low voltage) configuration is grounded wye, the generator windings must be effectively grounded. DG must have protective device(s) to detect and clear any distribution fault on the interconnected feeder, unless the DG can NOT self excite DG must have over/under voltage protection DG must have over/under frequency protection To prevent and/or minimize the injury/damage of personnel (including the public) and equipment caused by any distribution feeder fault To protect the connected distribution equipment and load from over/under voltage damage To protect the connected distribution equipment and load from over/under frequency damage Typical Protection Requirements for DG Interconnection: Case 6 Generator Type: Interconnection Type: Inverter Generator NO Export to Utility PROTECTION REQUIREMENT Directional over-current protection (looking into the utility system at the interconnection point) to trip the interconnecting breaker at the DG site (i.e. Trip on any current flow into the utility system from the DG) FUNCTIONAL PURPOSE To prevent any possibility of export from the DG to the utility system Directional over-current protection on the interconnected feeder breaker, unless the maximum fault contribution from the DG is less than the instantaneous setting of the nondirectional protection of the interconnected feeder breaker Configuration of the utility side (i.e. 25 kV side) of the interconnecting transformer must be grounded Y To prevent the unnecessary tripping of the interconnected feeder for any distribution fault occurred on the adjacent distribution feeder DG must have over/under voltage protection DG must have over/under frequency protection To provide fault detection and fault clearing for any distribution fault on the interconnected feeder To prevent any over-voltage condition imposed on distribution equipment caused by line-to-ground fault after the utility source is cleared (If generator side (i.e. low voltage) configuration is grounded wye, the generator windings must be effectively grounded. To protect the connected distribution equipment and load from over/under voltage damage To protect the connected distribution equipment and load from over/under frequency damage