RPR 60KVA PowerBay
Modular Redundant Power Router
Cabinet System
Redundant -48VDC A/B Input power router system for reliable uninterrupted powering of single input
DC power equipment such as DC-AC inverter systems.
Compact footprint: 7' tall x 24"W x 30"D cabinet. Scalable and modular.
Single, Dual or Triple bus configurations for flexible DC source input routing.
CSI RPR300 high density redundant power router modules. Hot-swap capable with individual output
circuit breakers to feed inverter module inputs. 60KVA Bay accepts six RPR300 modules for 1,800A
cabinet DC routing ampacity.
Integrated supervisory controllers provide voltage, current, thermal status, breaker trip alarm and other
status data.
Proven 10 year high reliability RPR product history - units installed in many communications facilities.
High power density solution to feed new generation 3-Phase DC-AC Telecom inverters from redundant
A/B DC power plants.
Application notes:
DIAGRAM
Power from redundant and isolated "A" and "B" -48VDC power plants is fed to the RPR (Redundant
Power Router) module input. Internal low loss "steering diodes" provide power combining without risk
of backfeed from one DC plant to the other. There is no transfer interruption in load support from one
plant or the other providing the power through the routing circuit. Normal operation features an
approximate 50% load share from both DC plants assuming the input voltage to the RPR system is equal.
Entire inverter load can be supplied from only one DC plant or the other during maintenance or
emergency shutdown of the opposing DC plant. RPR modules are fed from A/B inputs and provide circuit
breaker protected "C-bus" redundant fed outputs to feed to the DC-AC inverter module inputs.
Functional block diagram of power routing:
DIAGRAM
Doc# 048–XXX–00/Nov 01.08
General Specifications
Model #
RPR cabinet
Single Bus
RPR cabinet
DUAL BUS
RPR cabinet
TRIPLE BUS
RPR150 Module
RPR300 Module
Configuration
A/B Bulk feed 1,800A
input buses. Common
return bus bar. Six RPR
module shelves fed by
single bus.
Dual A/B 900A input
buses. Common return
bus bar. Six RPR
module shelves. Three
shelves on bus 1, three
on bus 2.
Triple A/B 600A input
buses. Common return
bus bar. Six RPR
module shelves.
Two shelves each on
bus 1, 2 and 3.
A/B -48VDC input, Cbus redundant diode
routed power module.
Hot swap capable.
Input Fuses, 150A
output circuit breaker.
Part #
016-959-10
Description
7' tall x 19" welded
frame relay rack with
box bay kit. Footprint
measurements: 24" W x
30 D"
016-958-10
Includes steel powder
coated removable side
panels, removable rear
panel, front panel steel
powder coated blanking
plates for unused panel
positions.
016-957-10
Includes internal vertical
ground bus for chassis
grounds. Relay rack
includes frame ground
lug threaded hole
locations, 3 qty. 5/8"
weld nuts on top of
frame for vertical rackauxiliary frame support
attachment via threaded
rod. -48VDC Input hot
and return bus bars
mounted to
016-950-10
isolated support
structure. All copper
components nickel-tin
plated and installed with
stainless steel hardware.
Box bay
016-951-10
system includes labeling
for all buses, cautionary
statements, front panel
bus and RPR module ID
labels.
Doc# 048–XXX–00/Nov 01.08
Redundant user
replaceable cooling
fans.
A/B -48VDC input, Cbus redundant diode
routed power module.
Hot swap capable.
Input Fuses, 300A
output circuit breaker.
Redundant user
replaceable cooling
fans.
All input, internal bus
and user load
terminations are twobolt configured. Breaker
trip/module fault form-c
dry alarm contacts
provided for remote
monitoring. Power
cabinet includes six RPR
module shelves with
integral polarized and
isolated power interface
connectors for hot swap
of modules as required.
Module output
connections are isolated
to support 1:1
connection to DC-AC
10KVA 3phase inverter
modules (RPR300).
Specifications:

Dimensions: 24" W x 30" D x 7' T. 19" Welded frame rack with box bay housing. Removable Steel
side panels, rear panel.

Weight: 400 + Lbs depending upon configuration.

Mounting configurations: Front flush mount control and blanking panels. Rear rack vertical and
horizontal copper bus internal distribution for A/B -48VDC inputs, A/B common returns, C-bus
redundant routed -48VDC outputs.

RPR module output circuit breakers: 150A or 300A rated, magnetic, time delay trip with
automatic self trip for overload, thermal fault conditions. Accessible via flip up front panel door.
Doc# 048–XXX–00/Nov 01.08

Input bus configuration: Single 1,800A bus, Dual 900A bus and triple 600A bus versions provide
large copper -48VDC A and B input connections. Common A/B return bus is rated at 1,800A. All
hot and return input connections support four lug landing positions (up to 750MCM) with twobolt hardware. C-bus outputs support up to two 750MCM lug landing locations.
Lacing bars provided for power cable management. Input busses can be configured to support
bulk input feed from direct A and B plant rectifier bus or fuse/breaker fed from rectifier PDF bay
distribution protection devices.

Thermal management: RPR modules include redundant user replaceable cooling fans with
integrated controller. Air flow is back to front discharge. Thermal dissipation: RPR300 typical
load: 150 watts per module. Worst case cabinet dissipation: 900W.

Shipment packaging: Cabinet bolted vertically to plywood protected pallet crate box with
internal packaging, documentation, accessories. Shipped via truck freight only. FOB factory
(Seattle, WA).
Doc# 048–XXX–00/Nov 01.08