Download Control technique

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
Control technique
Interface relay MK 3044
Output interface relay
0232909
·
·
·
·
·
·
Approvals and marking
Principle circuit diagram
A1
11
21
12 14
22 24
B1
B2
According to IEC 255, VDE 0435 part 201
With separate control input
very low control current £ 5 mA
With changeover contacts for switching of low and big loads
With LED indicator
Width 22,5 mm
Application
I 5mA
A2
M6168_b
· Link between control and power levels
· For separating potentials
Some electronic devices, e.g. frequency inverters, microprocessor
systems etc. offer the possibility to signalize faults and operating conditions
via one or more logic outputs. However, the problem is the minimum
loading of these outputs and the voltage of e.g. DC 15 V, which is not
normal in the control technique.
Circuit diagram
Function
A1 11 21
The MK 3044 is a interface relay with an additional control input. The
supply voltage DC 24 V will be applied to A1/A2. The relay switches, when
the input B1/B2 is connected to a voltage between AC/DC10...30 V.
B1 B2
L1 L2
11
21
Indication
LED:
T1 T2
12 14
on, when relay energised
22 24
Technical data
22 24
M5733
Input
12 14 A2
MK 3044.12
Nominal voltage A1-A2:
Control voltage B1-B2:
Voltage range:
Control current B1-B2:
Nominal consumption:
DC 24 V
AC/DC 10 ... 30 V
0,9 ... 1,2 UN
£ 5 mA
£1W
Output
Contacts
MK 3044.12:
Switching voltage:
Switching current:
Turn-off time:
Thermal current I th:
Switching capacity
to AC 15
NO contact:
NC contact:
Electrical life
to AC 15 at 3 A, AC 230 V:
Permissible switching
frequency:
Short circuit strength
max. fuse rating:
Mechanical life:
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
1
2 changeover contacts
U = 0,3 ... 60 V
I = 1 ... 300 mA
7 ms
5A
3 A / AC 230 V
1 A / AC 230 V
EN 60 947-5-1
EN 60 947-5-1
EN 60 947-5-1
> 3 x 105 switching cycles
3000 switching cycles / h
6 A gL
EN 60 947-5-1
> 30 x 106 switching cycles
MK 3044 / 09.11.01 d
Technical data
General data
Operating mode:
Temperature range:
Clearance and creepage
distances
overvoltage category /
contamination level:
EMC
Electrostatic discharge:
HF-irradiation:
Fast transients:
Surge voltages
between
wires for power supply:
between wire and ground:
Interference suppression:
Degree of protection:
Housing:
Terminals:
Housing:
Vibration resistance:
Climate resistance:
Terminal designation:
Wire connection:
Wire fixing:
Mounting:
Weigth:
Continuous operation
- 20 ... + 60 °C
4 kV / 2
IEC 60 664-1
8 kV (air)
10 V/m
2 kV
EN 61 000-4-2
EN 61 000-4-3
EN 61 000-4-4
1 kV
2 kV
Limit value class B
EN 61 000-4-5
EN 61 000-4-5
EN 55 011
IP 40
EN 60 529
IP 20
EN 60 529
Thermoplastic with V0 behaviour
according to UL subject 94
Amplitude 0,35 mm
frequency 10 ... 55 Hz EN 60 068-2-6
20 / 60 / 04
EN 60 068-1
EN 50 005
2 x 1,5 mm 2 solid or
2 x 1,0 mm2 stranded wire with sleeve
DIN 46 288-1/-2/-3/-4
Flat terminals with self-lifting
clamping piece
EN 60 999
DIN rail
EN 50 022
140 g
Dimensions
Width x height x depth:
22,5 x 82 x 99 mm
Standard type
MK 3044.12 DC 24 V
Article number:
· Output:
· Nominal voltage UN:
· Width:
0036733
2 changeover contacts
DC 24 V
22,5 mm
stock item
Ordering example
MK 3044 .12
DC 24 V
Nominal voltage
Contacts
Type
E. DOLD & SÖHNE KG • D-78114 Furtwangen
e-mail [email protected] • internet http://www.dold.com
• Postf. 1251 • Tel. +49 7723 654 0 • Telefax +49 7723 654 356
2
Related documents