Transcript
UPS Proposal Document: Avaya 9 kVA Online UPS
PRICING OVERVIEW (AVAYA NPL)
Item
9-slot UPS Enclosure
9-slot Battery Enclosure
12-slot UPS Enclosure, Seismic
9-slot Battery Enclosure, Seismic
Internal Battery Module (2 per slot; order in
quantities of 2)
Extended Battery Cabinet (EBC) A
Extended Battery Cabinet (EBC) B
Extended Battery Cabinet (EBC) C
Extended Battery Cabinet (EBC) D
Extended Battery Cabinet (EBC) E
Extended Battery Cabinet (EBC) F
3 kVA Power Module
20A Charger Module (required for EBCs)
Maintenance Bypass Cabinet
Web/SNMP Card
Alarm Relay Card
Com Code
700326689
700326705
700326697
700326713
NPL
$2,749.00
$2,249.00
$5,299.00
$4,599.00
700248982
700326721
700326739
700326747
700326754
700326762
700326770
700248974
700249030
700329907
700249048
700249055
$230.00
$9,149.00
$10,899.00
$13,849.00
$16,899.00
$18,899.00
$23,799.00
$2,290.00
$2,185.00
$1,249.00
$410.00
$135.00
Quantity
Total
PRODUCT OVERVIEW
The Avaya 9 kVA UPS, with its scaleable, modular and redundant design, provides the highest level of reliability
for telecommunications systems. Designed for optimum performance, Avaya online UPSs provide unparalleled
reliability and power protection.
Avaya UPS Features & Benefits
 Grows with changing environments by incorporating scalable design with 3 kVA power modules
 Eliminates single point-of-failure with N+X power and logic redundancy
 Isolates connected equipment from all incoming power problems to provide the highest degree of
protection with online, double-conversion technology
 Doubles battery service life and gives you advanced warning of the end of useful battery life with
Advanced Battery Management (ABM) technology
 Eases setup and service with hot-swappable, lightweight power and battery modules
Top Reasons to Buy an Avaya UPS
When it comes to providing the best possible power protection solution for your Avaya telecommunications
equipment, select the best--an Avaya UPS.

Online, Double-conversion Technology
All Avaya UPS models feature a rugged, online design where power is completely regenerated before
reaching the connected load so that no disturbances reach the connected equipment. An Avaya UPS
provides complete protection from all nine common power problems. In addition, the online design is
compatible with generators.

Advanced Battery Management (ABM)
Avaya UPS models feature Advanced Battery Management, which doubles battery service life, optimizes
recharge time, and provides advanced warning of the end of useful battery life. With increased battery life,
you won't need to replace the batteries as quickly. As a result, the total cost of ownership for an Avaya UPS
800.322.4877
Page 1 of 6
powerware.com/avaya
is reduced. In addition, most competitive UPS models use an LED to indicate that the batteries are dead
with no advanced notice.

Configurable Design
The 9 kVA UPS features N+X redundancy and is scalable to grow with expanding applications. By
installing 3 kVA power modules, customers have the flexibility of increasing the capacity of the UPS
without purchasing a new one. Extra 3 kVA power modules eliminate single point-of-failure and provide
N+X redundancy.

Extended Backup Times
Avaya has custom solutions designed to provide up to 8 hours of backup time. Competitive UPS offerings
are often difficult to configure for long runtimes.

Avaya Authorized and Approved
Each Avaya labeled UPS is designed and tested to meet the rigorous Avaya specifications of
telecommunications and ancillary equipment.

Web/SNMP Card
Avaya models are equipped with the Web/SNMP card for advanced communication and monitoring
capabilities.
Web/SNMP Card
Included with the UPS, the Web/SNMP card enables you to monitor and control remote UPSs from web browsers
or industry standard network management systems. The Web/SNMP card supports real-time web and SNMP
(Simple Network Management Protocol) communication over 10/100BaseT Ethernet connections.
LanSafe Software
Each Avaya UPS ships with a CD containing LanSafe software, which delivers comprehensive support including
graceful, remote shutdown of UPS units and network monitoring tools. LanSafe supports all major operating
systems.
LanSafe Features and Benefits
 Patent pending Cost $avings Calculator allows you to determine overall savings resulting from the LanSafe
monitoring system
 Exclusive Stealth Mode Operation enables LanSafe to run in the background without visual traces
 3-D PowerScope and ControlRoom views eliminate the guesswork from UPS metering and status
information
 History View provides around-the-clock visual representation of the system event log in calendar format
SAMPLE CONFIGURATIONS AND PICTURES
The 9 kVA UPS is a configurable product. The pictures below provide an overview of sample configurations.
3 kVA Power Module
800.322.4877
Page 2 of 6
Battery Module
powerware.com/avaya
9 kVA UPS with 6 battery modules (top 3 slots with power modules)
15 kVA (or 9 kVA N+2) UPS with 20 battery modules
UPS with 9-slot battery enclosure
9 kVA N+2 UPS with 20A charger module and EBC
800.322.4877
Page 3 of 6
powerware.com/avaya
SITE PREPARATION
With larger UPS models such as the 9 kVA UPS, it is extremely important to make sure that you review that site at
which the UPS will be located. Here are a few general guidelines:





Find out the dimensions and weight of the UPS to be used (include any battery cabinets). Make sure
that the installation site has enough space available.
Does the UPS have adequate ventilation? The UPS uses internal fans to cool the UPS. You should not
install the UPS in a sealed container or small, sealed room.
Ensure the UPS can be placed in its final position. Will the UPS components fit through doors? Are
there any stairs?
Is the floor strong enough? The UPS and its battery cabinets can be heavy so make sure the site has the
proper floor loading capacity.
Check to see if there is an adequate electrical supply near to the UPS. Compare UPS fuse ratings
(amps) and breaker types and whether any electrical work may be needed (i.e. cabling to the UPS terminal
block input). The site may have its own electrical contractors.
ADDITIONAL PRODUCT INFORMATION
Avaya UPS web site: http://www.powerware.com/AVAYA/USA/Products/9_18kva.asp
Model Selection Guide
Model
9 kVA
Enclosures
9-slot UPS Enclosure
9-slot Battery Enclosure
12-slot UPS Enclosure,
Seismic
9-slot Battery Enclosure,
Seismic
Batteries
Battery Module
EBC A
EBC B
EBC C
EBC D
EBC E
EBC F
Additional Components
3 kVA Power Module
20A Charger Module
Maintenance Bypass
Cabinet
Alarm Relay Card
800.322.4877
SAP Code
Multiple
Power Out
(kVA/kW)
9.0 / 7.5
Installed Dimensions
(HxWxD, in.)
Varies
Installed
Weight (lb.)
Varies
700326689
700326705
N/A
N/A
47 x 24 x 28.4
47 x 24 x 28.4
158
156
700326697
N/A
47 x 24 x 28.4
270
700326713
N/A
60.7 x 24 x 28.4
260
700248982
700326721
700326739
700326747
700326754
700326762
700326770
N/A
N/A
N/A
N/A
N/A
N/A
N/A
2 per slot
43x24x32.5
43x40x32.5
43x40x32.5
60x40x32.5
60x40x32.5
77x40x32.5
30
1,272
1,978
2,542
3,264
3,813
5,084
700248974
700249030
3.0 / 2.5
N/A
1 per slot
1 per slot
17
17
700329907
N/A
21x14x16.8
35
700249055
N/A
Fits in rear panel slot
0.5
Page 4 of 6
powerware.com/avaya
Additional Specifications1
Electrical Input
Voltage
Voltage Range
Input Connection
Input Power Factor
Frequency
Dedicated Circuit Breaker Rating
Dedicated Circuit Breaker Rating
w/20A Charger Module
Power Draw of UPS
Power Draw of UPS w/20A
Charger Module
Electrical Output
UPS Power Ratings
Power Module Rating
Power Module Quantity
On Utility / On Battery Voltage Regulation
Efficiency
Heat Dissipation
Frequency Regulation
Battery Transfer Time
Communications
LCD Display
Language Support
Communications Port
Communications Slots
Emergency Power Off
General
Topology
Diagnostics
UPS Bypass
Environment & Safety
Safety Markings
EMC Markings
Surge Suppression
Audible Noise
Ambient Operating Temperature
Ambient Storage Temperature
Relative Humidity
REPO Port
Ventilation
Mean Time Before Failure (MTBF):
800.322.4877
200/100, 208/120, 220/110, 240/120 Vac
176-276V
Hardwired
.98
50/60 Hz (±3 Hz)
60A
80A
42A
58A
9 kVA
3.0 kVA
Three (four for N+1, five for N+2)
±3% of nominal
88% in normal operation; 97% in high performance mode
(optional)
2.93 kBTU/hr; 3.90 kBTU/hr for configurations with 20A
Charger Module
±3 Hz online; ±0.1 Hz on battery
0 ms; seamless transfer to battery power
4 x 20 character backlit display, programmable
English, French, Spanish and German
RS-232, standard
2 slots available. Web/SNMP card is the default selection;
second slot available for Alarm Relay Card
(EPO) Input for external EPO
True online, double-conversion
Full system self-test on power up
Automatic on overload or UPS failure
UL, cUL
FCC class A
IEEE/ANSI C62.41
<50 dBA
32 to 104ºF
-4 to 104ºF (140ºF w/o battery)
5% to 95%, non-condensing
Meets NEC code 645-11 intent and UL requirements
The air around the UPS must be clean and free of dust,
corrosive chemicals, and other contaminants. The UPS uses
internal fans to circulate the air for cooling. The air must be
free to circulate around the UPS and battery cabinet(s). Do
not operate the UPS in a sealed room or container.
>80,000 hr.; Demonstrated 180,000 hr.
Page 5 of 6
powerware.com/avaya
Standard UPS Batteries
Battery Type
Battery Replacement
EBC
Battery String Quantity
Battery Voltage Rating
Movement/Stability
Sealed, lead-acid; maintenance free
Hot-swappable
EBC A: 1 string; EBC B and C: 2 strings; EBC D and E: 3
strings; EBC F: 4 strings
12V batteries
EBCs are equipped with casters for movement. Cabinets
can also be secured for seismic mounting.
1. Due to continuing product improvement programs, specifications are subject to change without notice.
OPTIONS
Maintenance Bypass Cabinet
The maintenance bypass cabinet is a wall-mounted option equipped with a bypass switch. It allows you to service
or replace the UPS without shutting down the equipment connected to the UPS.
Seismic Enclosure
The 9 kVA UPS can be configured for seismic zone 4 installations. A 12-slot UPS enclosure and a 9-slot battery
enclosure are for use in areas such as California that have earthquake safety requirements. Note that the UPS
enclosure has 12 slots instead of 9.
Alarm Relay Card
The Alarm Relay Card is used to connect the UPS to a DEFINITY Remote Maintenance Board to monitor alarm
contacts. It fits into the option slot on the rear panel of the UPS.
800.322.4877
Page 6 of 6
powerware.com/avaya