Download Load Surge Management

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Utility frequency wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Electric machine wikipedia , lookup

Audio power wikipedia , lookup

Power factor wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Electrical substation wikipedia , lookup

Three-phase electric power wikipedia , lookup

Wireless power transfer wikipedia , lookup

Electric power system wikipedia , lookup

Vehicle-to-grid wikipedia , lookup

General Electric wikipedia , lookup

Buck converter wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Electric motorsport wikipedia , lookup

Mains electricity wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Islanding wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Rectifier wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power engineering wikipedia , lookup

Electrification wikipedia , lookup

Power electronics wikipedia , lookup

Power inverter wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Transcript
Galaxy 4000 UPS
40 / 50 / 65 / 75 kVA
You're not buying a UPS…
…you're buying peace of mind
All content in this presentation is protected – © 2008 American Power Conversion Corporation
Galaxy 4000 offers 10 features that
really matter to customers
1. Lower cost of ownership
2. A incredible reliability track record and large installation
base (15,000 Galaxy UPS)
3. Easy interfacing with networks and monitoring systems
4. Clean utility power – no reflected distortion
5. Input Power Factor Correction
6. Fault tolerant circuitry
7. Load surge management technology
8. Generator compatibility and smaller generator sizing
9. Backed by over 150 MGE Field Engineers
10.Knowing you’re on-line (RemotePowerMonitoring™)
APC by Schneider Electric – Name – Date
Power Range
● 40 kVA (32 kW)
● 50 kVA (40 kW)
● 65 kVA (52 kW)
● 75 kVA (60 kW)
208V input / 208V output standard (60 Hz)
30 kVA
26 kVA
UPS provides
0.8 PF Output
UPS provides
unity PF Output
kW = kVA
Output
Power
Typical UPS
operating range
0-70% load
0 kVA
Constant kW Technology: All MGE three
phase UPS are constant kW and will provide
unity power factor outputs up to their rated kW
level.
APC by Schneider Electric – Name – Date
Technical Specifications
25.8”
or
32.8”
Cabinet Configurations
19”
32”
Wall
Mounted MBP
42 Pole
Distribution
Cabinet
(optional)
UPS Module
208 V in
208 V out
External
Battery
Cabinet
72.1”

33.5”




APC by Schneider Electric – Name – Date
42 pole panelboard
distribution
Optional main input
circuit breaker
Optional Branch
Circuit Monitoring (no
local meter)


Wall mounted
external
Maintenance
Bypass (2 or 3 CB)
Battery cabinet width
depends on capacity of
battery used (i.e. 500 W/cell
battery = 32.8” cabinet
Optional internal
maintenance bypass with
keyed interlock (optional
electrically activated
interlock)
May be configured as dual
or single input
Technical Specifications
Battery system
● Battery system
•Provided in a remote or adjacent
(joined to UPS) matching cabinet(s)
•Battery type: sealed valve
regulated lead acid cells
•Cabinet width varies with the
capacity of the battery used
•Battery life estimated at five years
plus, depending on number of
discharges
•Compatible with “flooded or wet
cell” batteries
APC by Schneider Electric – Name – Date
Internal Maintenance Bypass
APC by Schneider Electric – Name – Date
Technical Specifications
Options
●
Maintenance Bypass: Optional internal or external maintenance bypass cabinet
● Internal maintenance bypass routes power around the core (wall mount cabinet only)
● External maintenance bypass routes power around the entire UPS module - UPS is completely
isolated (wall mount cabinet only)
•2 CB used when there is are separate feeds for the rectifier and bypass sources
•3 CB used when there is the same feed used for the rectifier and bypass sources
●
Dual Input: Provides separate feed for the rectifier and the bypass sources
● Provides two available power sources / avoids problems related to failure of an input circuit breaker
External wrap around
maintenance bypass
Internal maintenance bypass
Dual input – both inputs are
connected when ordered as a single
input
Static Switch
Rectifier
Inverter
Battery
APC by Schneider Electric – Name – Date
Technical Specifications
Options
●
●
●
Distribution: 42 pole panelboard in separate
cabinet
● Allows smaller branch circuits to be fed
directly from the UPS
● Available with optional main input CB
● Available with optional “Branch Circuit
Monitoring” that monitors individual branch
circuit currents (no local display provided)
Communications Cards: Three
communications card slots are standard.
Dry Contact Relay Card is standard.
Communications card port accepts two
additional cards. If more slots are required,
use Multislot.
Seismic Brackets: Brackets secure
cabinet(s) to the floor for safe installation in a
seismic zone 4 environment (i.e. Southern
California) per UBC 97; letters of certification
available
APC by Schneider Electric – Name – Date
Optional main
input CB
The distribution
hosts 42 circuits
Optional branch
circuit monitoring
monitors current
levels on
individual circuits
Easy to Install
● Contractors and installers will like
the Galaxy 4000’s ease of
installation
● All cable connections are easily
accessible from the front of the
UPS
● Top and bottom cable entry are
standard
APC by Schneider Electric – Name – Date
Single Line Diagram
APC by Schneider Electric – Name – Date
CONFIGURATION
On-Line Double Conversion Topology
the only accepted topology for critical
applications
Double Conversion Advantages
● True isolation between the input and output
● Independence of the input and output voltages and frequency
● No-break transfer to battery or bypass power
● Does not rely on the batteries for frequency stabilization
On-Line Double Conversion Technology
APC by Schneider Electric – Name – Date
Fault Tolerant Circuitry
Manages faults without
compromising the UPS
● Output faults are relatively common over the life of
any electrical system – will your UPS be able to
handle them?
● Regardless of the overload capacity of the inverter
(i.e. 150% or 300%), it’s not enough to handle output
faults which range from around 600% to infinite
current.
● Only the utility has enough power to clear most
output faults safely (usually 100 times + the fault
clearing current of the UPS module).
● The inverter’s fast current limiting response
protects it from damage while allowing the utility to
safely clear the fault via the robust static bypass
switch
● regardless of the overload
● Other UPS may suffer fatally from output shorts as
the inverter may self destruct if it cannot current
limit and safely transfer to bypass.
APC by Schneider Electric – Name – Date
Galaxy 3000 with 150% rated
fast current limiting inverter and
fully rated transfer switch.
inverter
fault
Brand
A
Brand A with 300% rated inverter
and slower transfer switch.
Fault Tolerant Circuitry
How fault tolerant circuitry works
● Fault tolerant circuitry relies on two critical features
● Inverter is fast enough to current limit (switch
off) and avoid being overloaded by excessive
fault currents
● Static transfer switch can sustain enough
current to clear the fault without damage
Fault Clearing Sequence
Power Flow
UPS detects current on inverter exceeds 167% of
1 nominal
Inverter shuts down (1/300 of a cycle) avoiding thermal
2 overload
3 Static Transfer Switch opens simultaneously
Utility clears fault via fully rated Static Transfer
4 Switch
5 UPS returns to inverter power
Load protected throughout sequence
APC by Schneider Electric – Name – Date
DPQ [Digital Power Quality]
The heart of MGE’s performance advantage
● Output created from hundreds of
variable width pulses (Pulse Width
Modulation)
● Control Loop compares output to a
references sine wave and makes
adjustments or correction pulses to
maintain a “power quality envelope”
Power Quality
Envelope (<1% V)
Output Voltage
Feature
Variable Switching Frequency
Benefit
Stable and high efficiency
Tolerates output faults by stopping
Sub Cycle Control of Output
inverter quickly
Active cancellation of harmonics on
Error Correction Pulses
critical bus
Real Time Reference Sine Wave Precision voltage regulation
Fast Switching Frequency
Superior step load performance
APC by Schneider Electric – Name – Date
Up to 8 cycles per mS
(132 / cycle)
DPQ Advantages
Load Surge Management
Devices with high start-up surges
● Step loads or load surges are common in most applications
● i.e. starting distribution transformers, starting banks of
servers, starting motor loads (chillers), medical imaging
equipment
● A UPS not capable of sustaining stable voltage during
step loads can compromise the load by decaying the
voltage under quick load changes
●
●
●
●
●
IT equipment (switch mode
power supplies)
Medical imaging equipment
Distribution transformers
Motor loads
Fluorescent Lighting
IT FACT: starting up one bank of
servers can cause power surges
equal to the rating of a 30 kVA UPS
and may decay your UPS voltage.
APC by Schneider Electric – Name – Date
DPQ Advantages
Active Harmonic Cancellation
● Harmonics are reflected by most loads
(especially IT loads) and pollute the
critical bus
● MGE’s inverter technology recognizes the
harmonics and produces correction
pulses at a high enough resolution to
cancel harmonics
● The result: The critical bus THD is limited
to 3.5%
UPS Output
APC by Schneider Electric – Name – Date
reflected
harmonics
IGBT Rectifier Advantages
● Constant and low input THD (<3%) attenuation at all load
levels
● Will not disturb sensitive loads sharing the utility / input
● Reduction of RMS current
● Reduced installation costs (sizing) / current consumption
reduced by up to 25%, allowing smaller upstream
breakers, transformers, and cables
● Unity (0.99) input power factor
● Reduced generator sizing due to negligible reactive current
● Reduction in component count
● Increased reliability
● Wide frequency and voltage input range (<25%)
● The UPS will not transfer to battery if the generator voltage
drops
● Does not rely on battery power to sustain dynamic loads
● Prolongs battery life
APC by Schneider Electric – Name – Date
MGE has over 15,000
IGBT rectifiers installed
globally (Galaxy 3000
pictured)
Clean Distortion Free Input Power
IGBT Rectifier Advantages
● Eliminates harmful distortion that is reflected back onto the utility from the UPS from disturbing
sensitive equipment sharing the utility power
UPS w/
Input Filter
UPS w/o
Input Filter
Galaxy 3000 w/
IGBT Rectifier
Distortion reflected back
from UPS input onto
other devices sharing
utility power
APC by Schneider Electric – Name – Date
UPS Input
(utility
power)
UPS
Output
IGBT Rectifier Advantages
● Low input THD (<3%) at all load levels
● IGBT rectifier maintains a low THDI level uniformly throughout all load levels
● Potentially harmful harmonic distortion is not reflected back onto the utility to disturb other
equipment sharing the line
THDI versus percent load on UPS
20%
15%
12 Pulse
12 Pulse w/ Filter
6 Pulse w/ Filter
THDI 10%
IGBT
5%
0%
33%
66%
100%
Percent load on UPS
MGE has over 15,000 IGBT rectifiers installed globally
APC by Schneider Electric – Name – Date
IGBT Rectifier Advantages
● Reduced generator sizing
● A unity power factor on the input (PFC or power factor
corrected input) means no leading power factor or
reactive current reflected onto the utility
● Eliminates generator oversizing (low generator to
UPS ratio) - saving up to half the cost of the UPS
module
APC by Schneider Electric – Name – Date
IGBT Rectifier Advantages
● Reduced installation costs
● The power factor corrected input lowers the current
demand by up to 25%
● Lower input current means smaller upstream
breakers, transformers, and cables
APC by Schneider Electric – Name – Date
IGBT Rectifier Advantages
● Increased Reliability
● The IGBT rectifier eliminates the need for an input
filter (<3% THD w/o a filter)
● This means fewer parts - fewer parts means
greater reliability
APC by Schneider Electric – Name – Date
Graphical User Interface
User friendly operation
Safe, easy operation…
● Operator error is the number one reason
UPS reliability is compromised!
● The operator interface is so simple to
navigate, even first time users can
proceed with confidence
● Displays include:
- alarm / event logs
- battery usage history
- animated power flow diagrams
- phase balancing
- operator instructions
- power graphs
APC by Schneider Electric – Name – Date
Graphical User Interface
User friendly operation
Main Menu
User Instructions
APC by Schneider Electric – Name – Date
Mimic Diagram
Detailed Measurements
Graphs
Load Balancing
Network Based Power Management
We talk to your network!
● Compatible with most platforms
and operating systems (multiserver / multi o/s environments)
● Select the software package and
hardware communications option
that best suites your needs.
Using the Network Management Card (SNMP), the Galaxy 4000
can gracefully manage all your servers over a network connection
APC by Schneider Electric – Name – Date
Communications Cards
We talk your language
● Communications cards for every application
● Internal communications card port
accommodates three communications cards
(dry contact relay card standard)
Easy integration with management and
monitoring systems
Network Management Card - manage up to 32 servers (SNMP based)
Dry Contact Relay Card (standard) - five dry contacts providing UPS status
RS232 / RS485 Serial Interface - serial output (ModBus protocol)
MultiSlot Communications Card Expander - adds three add'l comm ports
IBM AS/400 Volt-Free Contact/Remote Power Off Card
more info on cards
APC by Schneider Electric – Name – Date
RemotePowerMonitoring
Status monitoring and alerts
● Monitors UPS system status
and alerts MGE and operator
on any alarms
● Access to detailed power
system information via
graphical user interface
● 7x24 monitoring by MGE’s
Customer Care Center
● Integrated watch-dog alarm
detects any loss of connectivity
and alerts immediately
Summary Screen
Alarm / Event Log
Mimic Diagram
Message History
The comfort of knowing you’re on-line
APC by Schneider Electric – Name – Date
Automated Computer Aided
Diagnostics
● UPS continuously runs
automated self diagnostics on all
components and alerts users as
to any abnormalities
● Field Engineers can perform
more than 300 tests instantly isolates potential problems to
expedite maintenance
● 100% solid state (no
potentiometers) permits
computerized adjustment of any
parameter
APC by Schneider Electric – Name – Date
Instant analysis of all PCBAs – no
risk of manual calibration errors
Maintainability
Simple to maintain
● No maintenance required for normal operation
● Preventative maintenance (available through Clary Corp.) is suggested to pro-actively mitigate any
potential problems and increase reliability
● As with any electronic assembly – MGE suggests the following items be replaced over the life of
the system to assure reliable performance
• Batteries (suggested every five years)
• Capacitors (every 7-10 years)
• Fans (every (5-10 years)
● Full front access facilitates easy service and thermal scanning (all electromechanical
connections accessible through the front of the UPS)
● Self calibrating boards (no trim pots or thermal drift)
● Digital diagnostics port interfaces with PC and accesses all PCBs and system status
● Backed by over 150 factory trained Field Engineers in North America & 7 field Engineers from
Clary Corp. in P.R.
Full front access
MGE factory trained Field
Engineers are recognized as the
best in the industry.
APC by Schneider Electric – Name – Date
Factory Trained Field Engineers
ready to support you on-site
●
●
●
●
7 factory Field Engineers . Service provided by Clary Corp.
State-of-the-art Customer Care Center oversees service and maintenance to
guarantee a timely and quality response
<4 hour response time in most areas
Local spare parts depots
Clary Corp. 24 hour
service. Available
MGE Customer Care Center in
Costa Mesa, CA
Automated computer
diagnostics
APC by Schneider Electric – Name – Date
Made in the USA with Pride
● Made in the USA
● The Galaxy 4000 is manufactured in a dedicated
building on the MGE campus in Costa Mesa, CA
● Prior to shipment each Galaxy 4000 is
tested by automatic test stations under the
supervision of MGE expert technicians
● Every UPS function is tested and over 100
measurements are electronically
documented
APC by Schneider Electric – Name – Date
Here are just a few of the thousands of
business that depend on the Galaxy
UPS
There are over 15,000 Galaxy UPS installations protecting
critical power around the world.
APC by Schneider Electric – Name – Date
Galaxy 4000 UPS
Thank You