DS-I 11 6-20KVA maintenance manual V1.0 0. foreword This manual must be used together with “user manual”, “DS-I11 and 31 series panel operation guide” or “UPS power monitor users manual”, “wiring diagram”. DS-I Series 6-20K user manual.pdf DS-I Series 6-10K DS-I 11and 31 Series UPS Power Wiring Diagram.pdf UPS Panel Operating Guide.pdf Monitor.pdf DS-I Series 6-10K Wiring Diagram.pdf 1. Introduction about DS-I11 and DS-I31 series 1.1 boards There are 9 types of boards for DS-I11 series: Model description 1 SNT_PCB_PS1103_ZK DSP controlled board. Also used in DS-I31 2 PCB_PS1103_DR9 Rectifier power board. Include SCR rectifier, discharge circuit, PFC and DC bus SCH_PS1103_DR9.pd f 3 SNT_PCB_PS110310_FG Inverter power board. Include DC bus, inverter, bypass SNT_SCH_PS110310_ FG.pdf 4 SNT_PCB_PS1103_DY Power supply board. Output 12Vdc supply for whole system SNT_SCH_PS1103_DY .pdf 5 SNT_PCB_PS1103_CD Charger board. 1pcs for standard model, 2pcs for long backup model. Max charge voltage is 220Vdc. SNT_SCH_PS1103_CD .pdf 6 SNT_PCB_PS110310_CR Input EMI board. Include input filter, battery fuse. 7 SNT_PCB_PS110310_FR Output EMI board. Include output filter, output optional relay. 8 PCB_PS1103_DR8 IGBT driver board. Assembled on power board. SCH_PS1103_DR8.pd f 9 SNT_PCB_PS1103_JP Keyboard. Include keyboard and LCD. There are 11 types of boards for DS-I31 series: Model description 1 SNT_PCB_PS1103_ZK DSP controlled board. Also used in DS-I 31 2 PCB_PS1103_DR10 PFC power board. Include discharge circuit, PFC and DCbus. There are 2 PFC power board in 20KVA. SCH_PS1103_DR10.p df 3 SNT_PCB_PS110310_FG Inverter power board. Include DC bus, inverter, bypass. There are 2 PFC power board in 20KVA SNT_SCH_PS110310_ FG.pdf 4 SNT_PCB_PS1103_DY (10KVA) Power supply board. Output 12Vdc supply for whole system SNT_SCH_PS1103_DY .pdf SNT_PCB_PS1103_PW1 (20KVA) SNT_SCH_PS1103_PW 1.pdf 5 SNT_PCB_PS1103_CD Charger board. 1pcs for standard model, 2pcs for long backup model. Max charge voltage is 220Vdc. SNT_SCH_PS1103_CD .pdf 6 SNT_PCB_PS1103_EM1 Input EMI board. Include input filter, battery fuse. 7 SNT_PCB_PS1103_EM2 Output EMI board. Include output filter, output optional relay. 8 PCB_PS1103_DR8 IGBT driver board. Assembled on power board. SCH_PS1103_DR8.pd f 9 PCB_PS1103_EM3 Battery EMI board. 10 SNT_PCB_PS1103_JP Keyboard. Include keyboard and LCD. 11 SNT_PCB_PS1103_DR2 Rectifier board. Include SCR rectifier. SNT_SCH_PS1103_DR 2.pdf Optional boards: There are 3 types of optional boards: Model 1 SNT_PCB_PS1103_DR3 description ECO board. If choose ECO board, must choose ECO board. It can be fast assembled on SNT_PCB_PS110310_FG 2 SNT_PCB_PS1103_BJ Parallel board. If choose parallel mode, the UPS must be assembled with parallel board yet 3 PCB_PS1103_TF1 Dry contact board. It can offer many function signals to user NOTE: All board may be upgraded continuously, including function, model and so on. For optional kits assemble, please refer to the assembling operation manual. 1.2 cables Fig.1.2 cable design One cable in UPS includes cable, connectors, cable number label, direction label shown as fig.1.2 Routing direction label indicates that where is this connector connected to, such as CD1-J2 means connect to socket J2 on SNT_PCB_PS1103_CD board 1#. Every cable has one and only cable number. Wiring direction of DS-I 11 and DS-I 31 are shown as below: 6-10KVA Wiring.pdf DS-I 3110 Wiring.pdf DS-I 3120 Wiring.pdf User can see where is one cable connected to. 1.3 main components 1). Input circuit breaker: assembled at rear panel Input fuses, battery fuses: assembled on input EMI board Rectifier SCRs: DS-I 11: assembled on SNT_PCB_PS110310_FG as fig.1.3.1 Fig.1.3.1 DS-I 11 series rectifier power board DS-I 31: assembled on SNT_PCB_PS1103_DR2 as fig.1.3.2 Fig.1.3.2 DS-I 31 series SCR board PFC IGBTs, PFC Diodes, discharge relay(no for 6KVA), discharge SCR DS-I 11: assembled on PCB_PS1103_DR9 as fig.1.3.1 DS-I 31: assembled on PCB_PS1103_DR10 as fig.1.3.3 Fig.1.3.3 DS-I 31 series PFC power board 2). Failure mode of main component FUSE: normal- resistor is near zero broken- resistor is very large SCR: normal- resistor is about xx Kohms~xxx Kohms broken- shorted, resistor is near zero DIODE: normal- voltage from Anode to Cathode is about 0.7V broken- shorted, voltage is near zero; opened, voltage can’t be tested IGBT(internal anti-parallel diode): normal- voltage from E node to C node (Vec) is about 0.7V, resistor (Rce) is about xx Kohms, capacitor between G and E (Cge) is about xx nf broken- shorted, Vec is about zero, Rce is about zero, and probably Cge is about 0; opened, Vec can’t be tested. Probably devices near gate of IGBT may also be destroyed, such as driver resistors, TVS and so on 2. To get the fault or warn information a). UPS is continuous beeping, some LEDs are steady red, fault alarm(something are broken) b). UPS is sounded once per second, some LEDs are red flicker, warn alarm(something are wrong) c). Press to see the higtory log, it tells what have happened d).Choose then press RIGHT button to get S-code information Note: S-code scrolls like as S0-S1-A0-A1-A2-A3-A4-A5, please record them all, or you can downlowd the S-code according to power monitor software. Fig.2.1 Panel 3. To get the failure point According the history log and S-code, we can judge what have happened. See the S-code as fig.2.2 1 16 Fig.2.2 S-code Every number of S-code indicates one warn or fault. If the number is set to be “1”, it means something has happened. Description of every code has been listed in user manual. 3.1 Solution for faults S-code Cause Solution A0-1 1). Bypass voltage is out of synchronous range 2). Bypass voltage changed too fast to be tracked by inverter Check if bypass voltage on LCD and through testing utility are same, if yes, it is probably that utility is abnormal A0-2 Main input is abnormal Check if utility is abnormal A0-3 Rectifier fault It’s a composited fault, it maybe for rectifier over temperature, soft start failure, DCbus over voltage or else A0-4 Inverter fault It’s a composited fault, it maybe for inverter over temperature, inverter voltage abnormal, DCbus over voltage or else A0-13 Input phase A over current. As DS-I 11 series, it means input over current. A0-14 Input phase B over current. Reserved in DS-I 11 series. A0-15 Input phase C over current. Reserved in DS-I 11 series. 1). Check if PFC IGBT is broken, if yes, please replace it. 2). Check if DC bus is shorted, if yes, please replace all DC capacitors and check again 3). Check if IGBT drivers are lost, if yes, please replace IGBT drivers and check if some cables are not connected correctly 4). Input voltage is too low when load big loads 5). Check if PFC current transformer is broken, if yes, please replace it A0-16 Inverter voltage fault 1). Check if inverter IGBT is broken, if yes, please replace it. 2). Check if inverter IGBT driver is lost, if yes, please replace it 3). Check if cable from DSP board to inverter power board is not connected correctly A1-9 Input voltage fault 1). Check if input voltage is out of range 2). Check if voltage display on LCD is same as tested input voltage A1-10 Input frequency fault Check if input frequency is out of range A1-11 Input sequence fault Check if input wires connection or input voltage sequence is wrong A1-15 Rectifier over temperature 1). Check if environmental temperature is over 40℃ 2). Check if fans are abnormal A1-16 Positive bus over voltage 1) Check if some half-wave loads are connected to UPS , if yes, please remove them 2) Check if maintenance bypass switch is mistaken closed, if yes, please open it 3) Please contact with manufacturer or distributer A2-1 Negative bus over voltage 1) Check if some half-wave loads are connected to UPS , if yes, please remove them 2) Check if maintenance bypass switch is mistaken closed, if yes, please open it 3) Please contact with manufacturer or distributer A2-2 Fan fault 1). Find out that which fan is stopped or rotates slowly and then replace it with same model 2). Check if fan wires connection is loosen 3). Check if the short jumper is disappeared near reserved fan power socket A2-5 Positive DC bus under voltage A2-6 Negative DC bus under voltage 1). Check if PFC IGBTs are broken, if yes, please replace it 2). Check if PFC IGBT drivers are broken, if yes, please replace it A2-7 Battery reversed Check if battery connection is reversed, please connect if correctly A2-13 Battery over temperature 1) Check if battery temperature is too high, please locate batteries at temperature from 20~25℃. 2) Battery life is over, please replace all batteries with same type of batteries. A3-1 Battery voltage is low Alarm, battery backup time is near ZERO, please resume utility or loads will be shutdown A3-3 Battery EOD Battery voltage is under the end of discharge, UPS will shutdown and has no output A3-7 Bypass voltage fault Check if bypass input voltage is normal A3-8 Bypass SCR or relay is failure Open input breaker, and UPS works in battery mode, check if input voltage is same as output voltage, if yes, please replace bypass SCR or relays A3-11 Bypass frequency synchronous Check bypass frequency is out of range A3-14 Overload time out Please remove some loads and UPS will transfer back to inverter A4-1 Manual shutdown Someone has shutdown the UPS manually A4-2 Inverter protect A4-3 Transfer times over limit over Transfer times between inverter and bypass is over 5times in one hour A4-8 Inverter over temperature Check if environmental temp is over 40℃, or fans are abnormal A4-11 Over load Please check load level and remove non-essential load to make sure load percent is under 95% A4-12 Inver relay or fuse fault Check if inverter relay is shorted or opened A4-14 Parallel communication fault 1). Check if one parallel communication cable is disconnected 2). Check if working mode is “P(parallel)” for single UPS, if yes, please set it as “S(single)” A5-2 Output shorted Shutdown UPS and open output breaker, check if load is effective or short, if yes, please remove the load. Check if output connection is short, is yes, please connect it correctly A5-3 Battery test Normal A5-4 Battery maintenance Normal 3.2 How to transfer to maintenance bypass Maintenance bypass kit can be chosen with DS-I 11 and DS-I 31 series. If need to maintenance UPS without interruption, please operate as below: (1). Press “ON/OFF”, and then choose “OFF” to transfer to bypass mode (2). Open battery breaker (3). Close maintenance bypass switch or breaker (4). Open main input breaker 3.3 how to replace or assemble boards (1) replace power board Replace rec and inv board for DS-I.docx (2) assemble output relay DS-I output relay assemble.docx (3) assemble dry contact board a). assemble dry contact board to UPS as fig.3.3.1 Fig.3.3.1 b). connect signal cable from DSP board to dry contact board as fig.3.3.2 Fig. 3.3.2