Download dc source battery charger model bcd1315r series

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Solar micro-inverter wikipedia , lookup

Ohm's law wikipedia , lookup

Islanding wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Power inverter wikipedia , lookup

Current source wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Electric battery wikipedia , lookup

Charging station wikipedia , lookup

Voltage optimisation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Rectifier wikipedia , lookup

Voltage regulator wikipedia , lookup

Schmitt trigger wikipedia , lookup

Power electronics wikipedia , lookup

Rechargeable battery wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Current mirror wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
DC SOURCE
BATTERY CHARGER
MODEL
BCD1315R SERIES
Design Features
• Fully Isolated Design
• Adjustable output voltage for charging standard or deep cycle
lead-acid, VRLA or Gel cell type battery
• User selectable 2 or 3 stage charging profile
• Battery temperature compensation
• Battery overheat detection and shutdown with automatic recovery
(using supplied battery temperature sensor)
• Extremely rugged and well suited for demanding environments
• Ultra-quiet low EMI operation
Description
• Can be left permanently connected
The BCD1315R Rack mount DC Source Battery Charger charges a 12V, 24V or
48V one or two bank battery system (batteries must share a common ground)
from a 24 or 48 VDC source.
The newly updated Current Mode switching design offers 60% more power
in the same 2U rackmount enclosure as our BCD1015R series. The low ripple
charging profile and standard equalize cycle greatly increases the lifetime
of expensive battery systems. Extra input and output filtering reduce EMI
to extremely low levels. Reliability features include an input fuse, thermal
shutdown, current limiting, reverse battery hookup protection and output
short circuit protection with automatic recovery.
The output voltage is easily adjusted above or below the standard output
voltage to accommodate special charging requirements. A high quality bright
LED Digital Volt/Ammeter allows the monitoring of charging current and
charging voltage. We are confident that you will get many years of reliable
service from this DC Battery Charger.
• Spark free connection to batteries
• Battery reverse polarity connection protected
• Audible & visual indicators for output overload, low input voltage,
low output voltage & over-temperature
• Over-temperature shutdown with automatic recovery
• Short circuit protection with automatic recovery
• Output over-voltage crowbar
• Dry contact output fail relay
• 3 year parts and labour warranty
Applications
• Telecom Central Offices
• Electric Utilities and Substations
• Manufacturing Plants
Benefits
• Steel Mills
• Efficient and Accurate Battery Charging
• Military Applications (COTS)
• No Interference with radios or other sensitive electronics
• Industrial Controls
• Ideal for unattended operation with dry contact output fail relay and automatic
recovery from most faults
• Railway Trackside Cabinets
• Conservative design ensures years of safe and trouble free operation
An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters
8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA)
www.analyticsystems.com
DC SOURCE
BATTERY CHARGER
MODEL
BCD1315R SERIES
Electical (Input)
Nominal (ip)
24V
48V
Actual (VDC)
20-35V
40-60V
Input Amps (max)
80A
40A
Input Fuse (ATC)
40A x 3
20 x 3
Noise on Input
< 100mV
< 50mV
Output Nominal
12V (1 Bank)
24V (1 or 2 Bank)
Stages
2 (constant current to float) or 3 (constant current to absorption to float) - user selectable
Float Voltage (VDC)
13.6
27.2
54.4
Absorption Voltage (VDC)
14.4
28.8
57.6
Voltage Adjustment Range (VDC)
+/- 1V
+/- 2V
+/- 4V
Temperature Compensation
-30 mV/°C
-60 mV/°C
-120 mV/°C
Charging Current (Amps)
100A
50A
25A
Absorption to Float Current (Amps)
10
5.0
2.5
Battery Size (Amp Hrs.)
200-400
100-200
50-100
Output Overvoltage Crowbar Trip Voltage
16V
32V
64V
Output Ripple & Noise
< 50 mV
< 50 mV
< 50 mV
Regulation (Line & Load)
< +/- 0.5%
Duty Cycle
Continuous 100% for 24 hours per day
Efficiency
> 83% @ Maximum Output
Electrical (Output)
48V (1 or 2 Bank)
Environmental Specification
Operating Temp. Range
-25° to +40°C @ maximum output Derate Linearly 2.5% per °C from +40°C to +80°C
(Optional -40°C extra wide temp. operation avail.)
Humidity
0 - 95% Relative Humidity (non-condensing)
Audible Noise
34.5 dB at 1 meter when fan operating, 0 dB otherwise
Typical Service Life
> 10 yrs. (87,600 hrs)
Isolation
Input-Case & Input-Output 1500VDC (500V @ 24V I/P)
Output-Case 500VDC (1500VDC @ 48V O/P)
Mechanical Specification
Depth
13.5 in/ 34.3 cm
Width
19.0 in/ 48.3 cm
Height
2U (3.5 in)/ 8.9 cm
Clearance
1 inch (2.5 cm) all around
Material
Marine Grade Aluminum
Finish
Black Anodize / Powder Epoxy Coat
Fastenings
All 18-8 Stainless Steel
Weight
12.0 lb / 5.5 kg
Connections
Four contact output terminals
Warranty
3 years
Safety
Designed to meet CSA 22.2.107.1 & UL458
Note: Specifications are subject to change without notice.
An ISO9001 and AS9100 Registered Company Battery Chargers • Inverters • Power Supplies • Voltage Converters
8128 River Way, Delta B.C. V4G 1K5 Canada T. 604.946.9981 F. 604.946.9983 TF. 800.668.3884 (US/CANADA)
www.analyticsystems.com