Download POWER SUPPLY CONTROL PSC 100 The control and monitoring unit

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Distributed control system wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electric battery wikipedia , lookup

Power over Ethernet wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Islanding wikipedia , lookup

Resilient control systems wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electrical substation wikipedia , lookup

Buck converter wikipedia , lookup

Alternating current wikipedia , lookup

Rechargeable battery wikipedia , lookup

Fault tolerance wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Opto-isolator wikipedia , lookup

Rectifier wikipedia , lookup

AC adapter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Control system wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
POWER SUPPLY CONTROL PSC 100
The control and monitoring unit – for AEG SVS Switch Mode Rectifier
Application
The PSC 100 control unit combined
with AEG’s digital Switch Mode
Rectifiers allows for the design of
powerful DC Power Systems
compared to DC systems with only
stand-alone rectifiers. Apart from
the power cabling only a simple and
clear arrangement of Bus wiring is
required between PSC 100 and the
max. 31 rectifiers. The auxiliary
power supply of the PSC 100 is
supplied by the AC mains 230V or
400V 50Hz.
Communication
Up to 31 rectifiers will be able to
communicate with the PSC 100
control by Master-Slave-method. The
PSC 100 will control and monitor all
the SMR‘s of the system, will adjust
the desired output voltage and will
also control the recharge of the
battery after mains power failure or
after a power-up of the PSC 100
control. Altogether 4 different charge
characteristics can be selected by
remote contact.
Temperature
The battery temperature is measured
by a temperature sensor for
temperature dependent battery
charging.
Easy Installation
The PSC 100 is delivered as a
„ready to install“ kit incl. the CAN
Bus wiring. The components are
prepared for mounting on a clip-on
rail. Only multimeter and screw
driver but no other tools are required
for commissioning and testing of the
DC system.
Mode of operation
The active current sharing of the
PSC 100-control ensures a regular
loading of all the SMR’s.
..................................................
..................................................
The regular loading of the Switch
Mode Rectifiers will result in steady
power losses of all the SMR’s and
therefore steady temperature
distribution inside the cubicle. The
PSC 100 monitors the
communication to all SMR’s,
deviation of battery temperature,
sensor short circuit or open circuit
and the internal PSC hardware. The
failure signals generated by the
SMR’s like mains deviation, DC
deviation, SMR temperature too high
and also the common failure signal
are part of the reply signal concept.
Ü Active current sharing
Ü Control and monitoring up to
31 SMR’s by one central unit
Ü Temperature guided battery
charging
Ü 4 selectable charge characteristics
Ü Compact design
Ü CE-compliant
Ü ISO 9001 certification
POWER SUPPLY CONTROL PSC 100
The control and monitoring unit – for AEG SVS Switch Mode Rectifier
Technical Data
TYPE
PSC 100 with aux. supply 230V AC
PSC 100 with aux. supply 400V AC
E-number.
Nominal input voltage
Input current
Low function voltage with safe
disconnection
Indicators (LED flash code)
8 000 007 012
230V ± 20 % 50Hz
≤ 100mA
In acc. to EN 50178
8 000 007 013
400V ± 20 % 50Hz
External function
SMR load distribution at parallel operation
Design
Protective system
Working temperature
Storage temperature
Mechanical and vibration stability
Size W x H x D (mm)
Weight
Mains connection
SMR communication wire
Operation; Battery sensor short circuit or open circuit; battery temp. deviation;
internal reference voltage failure; addressing failure; CAN Bus failure;
SMR disturbance; broken wire of external set value
Common alarm by potential free relay contact; selection of 2. / 3. / 4.
charge characteristic; ext. set value by input of 0 - 4,9 V DC
Approx. 5 % of total system current
Incl. module carrier and clip-on rail
IP 20
0°C up to 45°C
- 20°C up to +70°C
In acc. to EN 50178 part 9.4.3.2
110 x 72 x 30 PSC
155 x 72 x 59 PSC aux. supply
approx. 0,5 Kg
Combicon plug by the Phönix company; scope of our supply
5 m CAN-Bus ribbon cable incl. 10 plugs; scope of supply
Netz
mains
PSC
aux.supply
SNT
SMPS
~
=
1
SNT
SMPS
~
=
2
SNT
SMPS
~
=
3
~
=
X6
PSC
X1
Betrieb
operation
DIL
Störung
failure
Störung
failure
Batterietemperatur
battery temperature
Batterie
battery
AEG SVS
Power Supply Systems GmbH
A company of Saft S.A.
Emil-Siepmann-Straße 32
D-59581 Warstein Belecke
Telefon +49(0)2902/763-143
Telefax +49(0)2902/763-507
http://www.aegsvs.de
DC-Last
dc load
Sollwert Kennlinie 4
setvalue characteristic 4
Kennliniensteuerung
characteristic controll