Download SP2 Series Wall‑mount Speaker Strobes

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Fault tolerance wikipedia , lookup

Sound reinforcement system wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Islanding wikipedia , lookup

Studio monitor wikipedia , lookup

Buck converter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage optimisation wikipedia , lookup

Wassim Michael Haddad wikipedia , lookup

Transmission line loudspeaker wikipedia , lookup

Stray voltage wikipedia , lookup

Resilient control systems wikipedia , lookup

Metadyne wikipedia , lookup

Surge protector wikipedia , lookup

Distribution management system wikipedia , lookup

Loudspeaker wikipedia , lookup

Loudspeaker enclosure wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Mains electricity wikipedia , lookup

Public address system wikipedia , lookup

Transcript
Fire Alarm Systems | SP2 Series Wall‑mount Speaker Strobes
SP2 Series Wall‑mount Speaker Strobes
▶ High intelligibility
▶ Low profile design
▶ Low current draw
▶ Power taps of ¼, ½, 1 and 2 watts
▶ Compatible with 25 V or 70.7 V distribution amplifiers
▶ Dual voltage in one unit (12 V and 24 V)
▶ Selectable candela settings of 15 cd and 15/75 cd for
the 12 V model and 15, 15/75, 30, 75, and 110 cd for
the 24 V model
▶ Synchronizable with the MDL Sync•Circuit Module
The System Sensor SP2 Series Wall‑mount Speaker Strobes
provide the sound quality essential to voice evacuation with
a broad frequency range and low harmonic distortion for
crystal clear sound performance, making them ideal for
hotel, hospital, and commercial applications. The strobes
have field‑selectable settings for 15, 15/75, 30, 75, and
110 cd. These speaker strobes have a field‑reversible strobe
allowing the speaker to be mounted either on the right or
left to avoid potential obstructions.
Certifications and Approvals
System Sensor holds these Listings and Approvals:
Region
Certification
USA
UL
CSFM
NYC/MEA
UUKC: Signaling Appliances and
Equipment for the Hearing Impaired
(UL1971), UUMW: Speakers and
Amplifiers for Fire Protective Signaling
Systems (UL1480, UL1711, and UL2043)
7320-1653: 133
127‑02‑E
Installation/Configuration Notes
Compatible Products
The following products are compatible with the SP2 Series
Speaker Strobes:
Category
Product ID
Product Description
Control
Panels
Compatible with all 24 V Bosch Control Panels when used in
continuous mode. For synchronization, use an SSMDL or
SSMDLW Synchronization Module.
Modules
SSMDL
Synchronization module (red)
SSMDLW
Synchronization module (white)
Mounting Considerations
These strobes can be mounted on the indicated back boxes
for the indicated applications:
Conduit
Applications
four‑inch square
•
Surface
Mounted
•*
Flush
Mounted
•
*Surface mounting on a four‑inch square back box requires
the use of an SSBBS‑SP2 Back Box Skirt.
Strobe Cautions
Do not exceed:
•
•
The voltage range for the chosen nominal voltage (8 V
to 17.5 V for 12 V nominal or 16 V to 33 V for 24 V
nominal)
70 strobes and a maximum line impedance of 4 Ω per
loop when using a synchronization module
www.boschsecurity.com
2 | SP2 Series Wall‑mount Speaker Strobes
•
The maximum line impedance of the control panel
Wiring
Note
These strobe units are not recommended for
use in coded or pulsed signaling circuits.
The input terminals accept wires with diameters between
18 AWG (1.2 mm) and 12 AWG (2.3 mm).
Parts Included
Quant.
Component
1
SP2 Speaker Strobe
1
Hardware pack
1
Literature pack
Power Requirements
Maximum Operating Strobe Current
(12 VDC):
15 cd: 127 mA RMS
15/75 cd: 127 mA RMS
Maximum Operating Strobe Current
(12 VFWR):
15 cd: 112 mA RMS
15/75 cd: 135 mA RMS
Maximum Operating Strobe Current
(24 VDC):
15 cd: 59 mA RMS
15/75 cd: 69 mA RMS
30 cd: 90 mA RMS
75 cd: 160 mA RMS
110 cd: 209 mA RMS
Maximum Operating Strobe Current
(24 VFWR):
15 cd: 64 mA RMS
15/75 cd: 74 mA RMS
30 cd: 93 mA RMS
75 cd: 158 mA RMS
110 cd: 208 mA RMS
Speaker Voltage (Input):
25.0 VRMS or
70.7 VRMS, selectable
Strobe Voltage (Input):
12 VDC or FWR unfiltered or
24 VDC or FWR unfiltered
Technical Specifications
Trademarks
Environmental Considerations
Temperature (Operating):
+32°F to +120°F (0° to +49°C)
Mechanical Properties
Candela Selections:
15 cd1, 15/75 cd1, 30 cd2, 75 cd2, or
110 cd2
Dimensions (H x W x D):
4.875 in. x 8.25 in. x 2.25 in.
(12.4 cm x 21 cm x 5.7 cm)
Material:
Molded plastic enclosure incorporating a
Xenon flashtube.
Sound Level
(UL Reverberant Room)
at 10 ft (3 m):
¼ W: 75 dBA
½ W: 78 dBA
1 W: 81.2 dBA
2 W: 84 dBA
Speaker Frequency:
400 Hz to 4 kHz
Trademark names are used throughout this document. In
most cases, these designations are claimed as trademarks
or registered trademarks in one or more countries by their
respective owners. Rather than placing a trademark symbol
in every occurrence of a trademark name, Bosch Security
Systems, Inc. uses the names only in an editorial fashion
and to the benefit of the trademark owner with no intention
of infringing the trademark.
Sync•Circuit is a trademark of System Sensor in the United States and other
countries.
System Sensor is a registered trademark or a trademark of Pittway International, Ltd. in the United States and other countries.
1 When set at these settings (15 cd or 15/75 cd) the devices
automatically work on both 12 V and 24 V power supplies.
The 15/75 cd selection is listed at 15 cd per UL1971 but
provides 75 cd on axis.
2
The strobe is not listed for 12 V operating voltages when
set to these selections (30 cd, 75 cd, and 110 cd). When
using a 12 V control panel, this device yields required light
output only in the 15 cd and 15/75 cd settings.
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
[email protected]
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
[email protected]
www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1124663563 | Cur: en-US, V5, 4 Jul 2010
Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
[email protected]
www.boschsecurity.com
SP2 Series Wall‑mount Speaker Strobes | 3
Ordering Information
SP2R1224MC Speaker Strobe (red)
Red, 12 VDC or 24 VDC device with dual voltage capability (25 VRMS or 70 VRMS), field‑selectable taps from 1/4 W to 2 W, and field‑selectable strobe intensities of 15 cd, 15/75 cd,
30 cd, 75 cd, and 110 cd
SP2R1224MC
SP2W1224MC Speaker Strobe (white)
White, 12 VDC or 24 VDC device with dual
voltage capability (25 VRMS or 70 VRMS),
field‑selectable taps from 1/4 W to 2 W, and
field‑selectable strobe intensities of 15 cd,
15/75 cd, 30 cd, 75 cd, and 110 cd
SP2W1224MC
Accessories
SSBBS‑SP2W Back Box Skirt (white)
Back box must be a standard 4‑inch square by
2‑1/8 in. deep
SSBBS-SP2W
SSBBS‑SP2R Back Box Skirt (red)
Back box must be a standard 4‑inch square by
2‑1/8 in. deep
SSBBS-SP2R
www.boschsecurity.com
4 | SP2 Series Wall‑mount Speaker Strobes
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
[email protected]
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
[email protected]
www.boschsecurity.com
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1124663563 | Cur: en-US, V5, 4 Jul 2010
Asia-Pacific:
Represented by
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
[email protected]