Download Installation and Operation

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power electronics wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric battery wikipedia , lookup

Battery charger wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
Installation and
Operation
Smart-UPSTM
Uninterruptible Power Supply
SURTD3000XLI
SURTD5000XLI
220/230/240 Vac
su0835a
Tower/Rack-Mount 3U
Smart-UPSTM RT
Uninterruptible Power Supply
SURTD 3000/5000 VA 200-240 Vac
Tower/Rack-Mount 3U
English
EN 990-2690C
07/2014
1
INTRODUCTION
The APCTM by Schneider Electric Smart-UPSTM RT is a high performance, uninterruptible power
supply (UPS). The UPS provides protection for electronic equipment from utility power blackouts,
brownouts, sags, and surges and small utility fluctuations and large disturbances. The UPS also
provides battery backup power for connected equipment until utility power returns to safe levels or
the batteries are fully discharged.
This user manual is available on the enclosed Documentation CD and on the
APC by Schneider Electric web site, www.apc.com.
INSTALLATION
Read the Safety Guide before installing the UPS.
Unpacking
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
„
„
„
UPS (with battery modules disconnected)
Front bezel
Literature kit containing:
„
Product documentation
„
Smart-UPS RT User Manuals CD
„
Warranty Information
„
„
„
„
„
XLT/XLI/XLTW models:
PowerChuteTM software CD
Serial cable
3000 VA XLI models: two output power cords,
two input power cords
3000 VA models: conversion faceplate for
accommodating a Network Management
Card
5000 VA XLI models: four output power cords,
Network Management Card documentation
Specifications
TEMPERATURE
OPERATING
STORAGE
32° to 104° F (0° to 40° C)
5° to 113° F (-15° to 45° C) charge the UPS
battery every six months
MAXIMUM
ELEVATION
OPERATING
STORAGE
10,000 ft (3,000 m)
50,000 ft (15,240 m)
HUMIDITY
0 to 95% relative humidity
WEIGHT
UPS 120 lbs (55 kg)
UPS with packaging 140 lbs (64 kg)
This unit is intended for indoor use only.
Select a location sturdy enough to
handle the weight.
Do not operate the UPS where there is
excessive dust or the temperature and
humidity are outside the specified limits.
Ensure that the air vents on the front
and rear of the UPS are not blocked.
2
Wiring and Connecting the UPS
5000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS
•
Wiring must be performed by a qualified electrician.
•
Install a high magnetic 30/32 A utility circuit breaker.
•
Adhere to all national and local electrical codes.
•
Use #10 AWG gauge (5 mm2) wire.
1.
2.
3.
Switch the utility circuit breaker OFF.
Remove the input access panel.
Remove circular knockout.
4.
Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not
included).
5.
6.
7.
Switch the utility circuit breaker ON.
Check line voltages.
Replace the access panel.
3
CONNECTING THE BATTERY MODULES AND ATTACHING THE FRONT BEZEL
∂
•
÷
≠
4
BASIC CONNECTORS
The serial connector is to be used for interfacing with APC by Schneider
Electric PowerChute software and terminal emulation software.
serial com
Use only APC by Schneider Electric approved cables.
Any other interface cable will be incompatible with the UPS
connector.
Manual bypass enables the user to manually put connected equipment into
bypass mode.
normal bypass
Emergency Power Off terminal allows the user to connect the UPS to the
central EPO system.
EPO terminal
TVSS screw
external battery
pack connector
The UPS features a transient voltage surge suppression (TVSS) screw for
connecting the ground lead on surge suppression devices such as telephone
and network line protectors.
When connecting grounding cable, disconnect the unit from the utility
power outlet.
Optional external battery packs provide extended run time during power
outages. These units support up to ten external battery packs.
See the APC by Schneider Electric web site, www.apc.com for the
information on the external battery pack, SURT192XLBP.
5000 VA
XLI models
output circuit
breakers
3000/5000VA
XLJ/XLT/XLTW
models
output circuit
breakers
5
CONNECTING EQUIPMENT AND POWER TO THE UPS
1.
2.
Connect equipment to the UPS (cables not included for XLJ/XLT/XLTW models).
Avoid using extension cords.
• 3000 VA XLJ/XLT/XLI/XLTW and 5000 VA XLJ/XLT/XLTW models: Using a power cord,
plug the UPS into a two-pole, three-wire, grounded receptacle only.
•
3.
4.
5.
5000 VA XLJ models: To draw full 5000 VA from the UPS have a qualified electrician cut
off the input plug and hardwire the UPS to the appropriate power panel.
Turn on all connected equipment. To use the UPS as a master ON/OFF switch, ensure all
connected equipment is switched ON. The equipment will not be powered until the UPS is
turned on.
To power up the UPS press the
button on the front panel.
•
The UPS battery charges when it is connected to utility power. The battery charges to 90%
capacity during the first three hours of normal operation. Do not expect full battery run
capability during this initial charge period.
For additional computer system security, install PowerChute Server Smart-UPS monitoring
software.
OPTIONS
Refer to the APC by Schneider Electric web site, www.apc.com for available accessories.
‰
‰
‰
‰
External Battery Pack SURT192XLBP
Rail Kit SURTRK2
Isolation Transformer
Service Bypass Panel
6
OPERATION
SMART-UPS RT FRONT DISPLAY
Load
Battery Charge
Indicator
Description
Online
The Online LED illuminates when the UPS is drawing utility power and performing
double conversion to supply power to connected equipment.
On Battery
The UPS is supplying battery power to the connected equipment.
Bypass
The Bypass LED illuminates indicating that the UPS is in bypass mode. Utility
power is sent directly to connected equipment during bypass mode operation.
Bypass mode operation is the result of an internal UPS fault, an overload condition
or a user initiated command either through an accessory or the manual bypass
switch. Battery operation is not available while the UPS is in bypass mode. Refer to
Troubleshooting in this manual.
Fault
The UPS detects an internal fault.
Refer to Troubleshooting in this manual.
Overload
An overload condition exists. See Troubleshooting.
Replace
Battery
The battery is disconnected or must be replaced. See Troubleshooting.
Feature
Function
Power On
Press this button to turn on the UPS. (See below for additional capabilities.)
Power Off
Press this button to turn off the UPS.
7
Feature
Function
Cold Start
When there is no utility power and the UPS is off, press and hold the
power up the UPS and connected equipment.
button to
The UPS will emit two beeps. During the second beep, release the button.
Self-Test
Automatic: The UPS performs a self-test automatically when turned on, and every
two weeks thereafter (by default). During the self-test, the UPS briefly operates the
connected equipment on battery.
Manual: Press and hold the
Diagnostic Utility Voltage
button for a few seconds to initiate the self-test.
The UPS has a diagnostic feature that displays the utility voltage. Plug
the UPS into the normal utility power.
The UPS starts a self-test as part of this procedure. The self-test
does not affect the voltage display.
Press and hold the
button to view the utility voltage bar graph
display on the right of the
display. The five-LED, Battery Charge
front panel shows the utility input voltage.
Refer to the figure at left for the voltage reading (values are not listed
on the UPS).
The display indicates the voltage is between the displayed value on the
list and the next higher value.
8
USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FACTORY
DEFAULT
USER SELECTABLE
CHOICES
Automatic Self-Test
On start-up and
every 14 days,
thereafter
On start-up and every 7
days thereafter
On start-up and every 14
days thereafter
On start-up only
No self-test
Set the interval at which the
UPS will execute a self-test.
Date of Last Battery
Replacement
Manufacture date
Date of
battery replacement
Reset this date when you replace
the battery modules.
Minimum Run time
Before Return from
Shutdown
0 seconds
0 to 3600 s of run time
Specify the minimum run time
following a low battery
shutdown, before powering
connected equipment.
Audible Alarm
Setting
ON
ON, OFF
Enable or disable all alarms
permanently.
Simple Shutdown
Delay
90 seconds
0 to 1800 s
Set the interval between the time
when the UPS receives a simple
shutdown command and the
actual shutdown.
Simple Low Run
Time Warning
150 seconds
0 to 1800 s
Change the warning interval
default to a higher setting if the
operating system requires a
longer interval for shutdown.
The low battery warning beeps
are continuous when 150
seconds of run time remain.
Output Voltage Setting
200 VAC:
210 - 280 VAC
208 VAC:
220 - 280 VAC
220 VAC:
235 - 280 VAC
230 VAC:
245 - 280 VAC
240 VAC:
255 - 280 VAC
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
FUNCTION
High Bypass Point
255 VAC
9
DESCRIPTION
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE, OPTIONAL SMART SLOT
ACCESSORY CARDS, OR TERMINAL MODE.
FUNCTION
FACTORY
DEFAULT
Low Bypass Point
160 VAC
USER SELECTABLE
CHOICES
DESCRIPTION
Output Voltage Setting
200 VAC:
160 - 185 VAC
208 VAC:
160 - 190 VAC
220 VAC:
160 - 195 VAC
230 VAC:
160 - 200 VAC
240 VAC:
160 - 205 VAC
Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage
XLJ models:
200 VAC
XLT models:
208 VAC
XLTW models:
220 VAC
XLI models:
230 VAC
200, 208, 220,
230, 240 VAC
Allows the user to select the on
on-line output voltage.
Output Frequency
Automatic
50 ± 3 Hz or
60 ± 3 Hz
50 ± 3 Hz
60 ± 3 Hz
50 ± 1 Hz
60 ± 1 Hz
50 ± 0.1 Hz
60 ± 0.1 Hz
50 ± 3 Hz or 60 ± 3 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of External
Battery Packs
0
0 to 100
Defines the number of external
connected battery packs for
proper run time prediction.
Bypass Acceptable
Not required
Required/ Not required
Phase and frequency lock
required/not required before the
UPS will switch to bypass.
10
CONNECTING THE EPO (EMERGENCY POWER OFF) OPTION
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Adhere to National and local electrical codes when wiring the EPO.
EPO
switch
The EPO switch is internally powered by the UPS for use with non-powered switch circuit breakers.
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC
standard).
Both Class 2 and SELV circuits must be isolated from all primary circuitry. Do not connect any
circuit to the EPO terminal block unless it can be confirmed that the circuit is Class 2 or SELV.
If circuit standard cannot be confirmed, use a contact closure switch.
Use one of the following cable types to connect the UPS to the EPO switch:
•
CL2: Class 2 cable for general use
•
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
•
CL2R: Riser cable for use in a vertical run in a floor to floor shaft.
•
CLEX: Limited use cable for use in dwellings and for use in raceways.
•
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control cable).
11
TERMINAL MODE TO CONFIGURE UPS PARAMETERS
3000 VA models:
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not wishing
to use PowerChute software or an optional Network Management Card.
Connect the serial cable to the serial com connector on the back of the UPS.
If PowerChute software is not installed do not perform steps 1 and 7.
1.
For Windows users: STOP the PowerChute Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Stop.
1a. For Linux users: STOP the PowerChute Server using the following steps:
•
Change directory to /etc/init.d.
•
Initiate the command ./PowerChute stop.
2. Open a terminal program. Example: HyperTerminal
•
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3. Double-click on the HyperTerminal icon.
•
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
•
Select the COM port that is connected to your UPS. The port settings are:
9 bits per second - 9600
9 data - bits 8
9 parity - none
9 stop bit - 1
9 flow control - none
•
Press ENTER
4. Press 1 to modify the UPS parameters.
5. Follow the prompts.
6. Exit the terminal program.
7.
For Windows users: START the PowerChute Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Start.
7a. For Linux users: START the PowerChute Server using the following steps:
•
Change directory to /etc/init.d.
•
Initiate the command ./PowerChute start.
12
5000 VA models:
Terminal Mode is a menu driven interface that enables configuration of the UPS by users not using
PowerChute software or the installed Network Management Card interfaces.
Connect the serial cable to the serial port on the back of the UPS.
If PowerChute software is not installed do not perform steps 1 and 5.
1.
For Windows users: STOP the PowerChute Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC PowerChute Server – right click the mouse and select Stop.
1a. For Linux users: STOP the PowerChute Server using the following steps:
•
Change directory to /etc/init.d.
•
Initiate the command ./PowerChute stop.
2. Open a terminal program. Example: HyperTerminal
•
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
3.
Double-click on the HyperTerminal icon.
•
Follow the prompts to choose a name and select an icon. Disregard the message, “...must
install a modem,” if it is displayed. Click OK.
•
Select the COM port that is connected to your UPS. The port settings are:
9 bits per second - 9600
9 data - bits 8
9 parity - none
9 stop bit - 1
9 flow control - none
•
Press ENTER
4.
Example for setting the number of external battery packs (SURT192XLBP):
Once the blank terminal window is open, follow these steps to enter the number of battery packs:
•
Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User
Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears
on the screen prior to typing the next character.
Network Management Card defaults:
•
User Name: apc
•
•
Password:
apc
Press 1 and ENTER to select Device Manager.
•
Select the model by entering the corresponding number, then press ENTER.
•
Press 3 and ENTER to select Configuration.
•
Press 1 and ENTER to select Battery.
13
•
Press 2 and ENTER to change the Battery Settings.
•
5.
Type in the number of external battery packs (four battery modules per pack), and
press ENTER.
(Number of packs: 1 = 1 SURT192XLBP, 2 = 2 SURT192XLBP etc.)
•
Press 3 and ENTER to accept the changes.
•
Press ESC multiple times (5) to return to the main menu.
•
Press 4 and ENTER to log out.
For Windows users: START the PowerChute Server using the following steps:
•
From the Desktop, go to Start => Settings => Control Panel =>
Administrative Tools => Services.
•
Select APC by Schneider Electric PowerChute Server – right click the mouse and select
Start.
5a. For Linux users: START the PowerChute Server using the following steps:
•
Change directory to /etc/init.d.
•
Initiate the command ./PowerChute start.
14
MAINTENANCE AND TRANSPORT
Replacing the Battery Module
This UPS has an easy to replace, hot-swappable battery module. Replacement is a safe procedure,
isolated from electrical hazards. You may leave the UPS and connected equipment on during the
procedure. See your dealer or go to the APC by Schneider Electric web site, www.apc.com for
information on replacement battery modules.
The battery replacement procedure must include replacing all battery modules in the UPS and
connected external battery pack(s).
Once the battery(s) are disconnected, the connected equipment is not protected
from power outages.
Be careful during battery replacement, the battery modules are heavy.
Be sure to deliver spent batteries to a recycling facility or ship to the manufacturer
in the replacement battery packing material.
REMOVING BATTERY MODULES
X
[
Y
Z
\
15
REPLACING BATTERY MODULES
X
Y
Z
]
[
^
\
_
⎯
Disconnecting the Battery for Transport
Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S.
Department of Transportation (DOT) and IATA regulations.
The battery(s) may remain in the UPS.
1. Shut down and disconnect any equipment attached to the UPS.
2.
Shut down and disconnect the UPS from the power supply.
3.
Unplug the battery connectors. Refer to Replacing Battery modules in this manual.
For shipping instructions go to the APC by Schneider Electric web site, www.apc.com.
16
TROUBLESHOOTING, SERVICE, AND WARRANTY INFORMATION
Use the table below to solve minor installation and operation problems. Refer to the APC by
Schneider Electric web site, www.apc.com for assistance with complex UPS problems.
PROBLEM AND POSSIBLE
CAUSE
SOLUTION
UPS WILL NOT TURN ON
Battery not connected properly.
button not pushed.
Check that the battery connectors are fully engaged.
Press the
button once to power the UPS and the connected equipment.
UPS not connected to utility
power supply.
Check that the power cable from the UPS to the utility power supply is securely
connected at both ends.
Very low or no utility voltage.
Check the utility power supply to the UPS by plugging in a table lamp. If the
light is very dim, have the utility voltage checked.
UPS WILL NOT TURN OFF
button not pushed.
Press the
Internal UPS fault.
button once to turn the UPS off.
Do not attempt to use the UPS. Unplug the UPS and have it serviced
immediately.
UPS BEEPS OCCASIONALLY
Normal UPS operation when
running on battery.
None. The UPS is protecting the connected equipment.
UPS DOES NOT PROVIDE EXPECTED BACKUP TIME
Charge the battery(s). Battery modules require recharging after extended outages.
They wear faster when put into service often or when operated at elevated
temperatures. If the battery(s) are near the end of their service life, consider
replacing the battery(s) even if the Replace Battery LED is not illuminated.
The UPS battery(s) are weak
due to a recent outage or
battery(s) are near the end of
their service life.
FRONT PANEL LEDS FLASH SEQUENTIALLY
The UPS has been shut down
remotely through software or an
optional accessory card.
ALL LEDS ARE OFF AND THE
The UPS is shut down and the
battery is discharged from an
extended outage.
None. The UPS will restart automatically when utility power returns.
UPS IS PLUGGED INTO A WALL OUTLET
None. The UPS will return to normal operation when the power is restored and
the battery has a sufficient charge.
BYPASS AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE
The UPS is overloaded
The connected equipment exceeds the specified “maximum load” as defined in
Specifications on the APC by Schneider Electric web site, www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessential
equipment from the UPS to eliminate the overload condition.
17
PROBLEM AND POSSIBLE
CAUSE
SOLUTION
BYPASS LED ILLUMINATES
The bypass switch has been
turned on manually or through
an accessory.
If bypass is the chosen mode of operation, ignore the illuminated LED.
If bypass is not the chosen mode of operation move the bypass switch on the
back of the UPS, to the normal position.
FAULT AND OVERLOAD LEDS ILLUMINATE, UPS EMITS A SUSTAINED ALARM TONE
The UPS has ceased sending
power to connected equipment.
The connected equipment exceeds the specified “maximum load” as defined in
Specifications on the APC by Schneider Electric web site, www.apc.com.
Disconnect nonessential equipment from the UPS to eliminate the overload
condition.
Press the OFF button, then the ON button to restore power to connected
equipment.
FAULT LED ILLUMINATES
Internal UPS fault.
Do not attempt to use the UPS. Turn the UPS off and have it serviced
immediately.
REPLACE BATTERY LED ILLUMINATES
Replace Battery LED flashes and
short beep is emitted every two
seconds to indicate the battery is
disconnected.
Check that the battery connectors are fully engaged.
Weak battery.
Allow the battery to recharge for 24 hours. Then, perform a self-test. If the
problem persists after recharging, replace the battery.
Failure of a battery self-test.
The UPS emits short beeps for one minute and the Replace Battery LED
illuminates. The UPS repeats the alarm every five hours. Perform the self-test
procedure after the battery has charged for 24 hours to confirm the Replace
Battery condition. The alarm stops and the LED clears if the battery passes the
self-test.
UPS OPERATES ON BATTERY ALTHOUGH NORMAL LINE VOLTAGE EXISTS
Very high, low, or distorted line
voltage. Inexpensive fuel
powered generators can distort
the voltage.
Move the UPS to a different outlet on a different circuit. Test the input voltage
with the utility voltage display.
DIAGNOSTIC UTILITY VOLTAGE
All five LEDs are illuminated
The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination
If the UPS is plugged into a properly functioning utility power outlet, the line
voltage is extremely low.
ONLINE LED
There is no LED illumination
The UPS is running on battery, or it is not turned on.
The LED is blinking
The UPS is running an internal self-test.
18
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
1 . Review the Troubleshooting section of the manual to eliminate common problems.
2 . If the problem persists, contact APC by Schneider Electric Customer Support through
the APC by Schneider Electric web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The
model and serial numbers are located on the rear panel of the unit and
are available through the LCD display on select models.
b. Call Customer Support and a technician will attempt to solve the
problem over the phone. If this is not possible, the technician will issue a
Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the
APC by Schneider Electric web site, www.apc.com for country specific
instructions.
3 . Pack the unit properly to avoid damage in transit. Never use foam beads for
packaging. Damage sustained in transit is not covered under warranty.
a. Note: When shipping within the United States, or to the United
States always DISCONNECT ONE UPS BATTERY before shipping
in compliance with U.S. Department of Transportation (DOT) and
IATA regulations. The internal batteries may remain in the UPS.
b. Batteries may remain connected in the XBP during shipment. Not all
units utilize XLBPs.
4 . Write the RMA# provided by Customer Support on the outside of the package.
5 . Return the unit by insured, prepaid carrier to the address provided by Customer
Support.
19
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT) warrants its products to be free from defects in materials and workmanship for a
period of two (2) years from the date of purchase. The SEIT obligation under this warranty is limited to repairing or replacing,
at its own sole option, any such defective products. Repair or replacement of a defective product or parts thereof does not
extend the original warranty period.
This warranty applies only to the original purchaser who must have properly registered the product within 10 days of
purchase. Products may be registered online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination disclose that the alleged defect in the product does
not exist or was caused by end user or any third person misuse, negligence, improper installation, testing, operation or use of
the product contrary to SEIT recommendations or specifications. Further, SEIT shall not be liable for defects resulting from:
1) unauthorized attempts to repair or modify the product, 2) incorrect or inadequate electrical voltage or connection, 3)
inappropriate on site operation conditions, 4) Acts of God, 5) exposure to the elements, or 6) theft. In no event shall SEIT have
any liability under this warranty for any product where the serial number has been altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION
OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR FURNISHED UNDER THIS
AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND FITNESS
FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY AND NO
OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL OR OTHER
ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE SEIT SOLE
LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES. SEIT
WARRANTIES EXTEND ONLY TO ORIGINAL PURCHASER AND ARE NOT EXTENDED TO ANY THIRD
PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE LIABLE FOR
ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER SUCH DAMAGES ARISE IN
CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE OR STRICT LIABILITY OR WHETHER
SEIT HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT
IS NOT LIABLE FOR ANY COSTS, SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR
INDIRECT, LOSS OF EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT LIABILITY FOR
DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS FRAUDULENT
MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR LIMITED BY
APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material Authorization (RMA) number from customer support.
Customers with warranty claims issues may access the SEIT worldwide customer support network through the APC by
Schneider Electric web site: www.apc.com. Select your country from the country selection drop down menu. Open the
Support tab at the top of the web page to obtain information for customer support in your region. Products must be returned
with transportation charges prepaid and must be accompanied by a brief description of the problem encountered and proof of
date and place of purchase.
20
APC by Schneider Electric
Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is
available at no charge in any of the following ways:
• Visit the APC by Schneider Electric web site, www.apc.com to access
documents in the APC Knowledge Base and to submit customer support
requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC by Schneider Electric web site for specific
countries, each of which provides customer support information.
– www.apc.com/support/
Global support searching APC Knowledge Base and using e-support.
• Contact the APC by Schneider Electric Customer Support Center by
telephone or e-mail.
– Local, country specific centers: go to www.apc.com/support/contact for
contact information.
– For information on how to obtain local customer support, contact the
APC by Schneider Electric representative or other distributor from whom
you purchased your APC by Schneider Electric product.
© 2014 APC by Schneider Electric. Smart-UPS and PowerChute are owned by Schneider Electric
Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective
owners.
EN 990-2690C
07/2014