Download FCPS-24F/FCPS-24FE Field Charger/Power Supply

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Flexible electronics wikipedia , lookup

Voltage optimisation wikipedia , lookup

Wireless power transfer wikipedia , lookup

Islanding wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electrification wikipedia , lookup

Electrical substation wikipedia , lookup

Audio power wikipedia , lookup

Power inverter wikipedia , lookup

Power over Ethernet wikipedia , lookup

Electric power system wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

Rectifier wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Distribution management system wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Standby power wikipedia , lookup

Earthing system wikipedia , lookup

Control system wikipedia , lookup

Power engineering wikipedia , lookup

Mains electricity wikipedia , lookup

Opto-isolator wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Power supply wikipedia , lookup

Switched-mode power supply wikipedia , lookup

AC adapter wikipedia , lookup

Transcript
12 Clintonville Road
Northford, CT 06472
203-484-7161
FAX: 203-484-7118
FCPS-24F/FCPS-24FE
Field Charger/Power Supply
Installation, Operation and Application Manual
Document #50079
05/23/97
Rev:
P/N 50079:D
D
ECN 97-145
Installation Precautions
- Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm
control panel. Disconnect all sources of power before servicing. Control unit and
associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized. Do not attempt to
install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure
proper system operation, this product must be tested in accordance with NFPA 721993 Chapter 7 after any programming operation or change in site-specific software.
Reacceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that are
not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49O C/32-120 O F
and at a relative humidity of 85% RH (non-condensing) at 30O C/86 O F.
However, the useful life of the system's standby batteries and the electronic
components may be adversely affected by extreme temperature ranges and
humidity. Therefore, it is recommended that this system and its peripherals be
installed in an environment with a nominal room temperature of 15-27O C/60-80O
F.
Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device
voltage.
Fire Alarm System Limitations
Like all solid state electronic devices, this system may operate erratically or can
be damaged when subjected to lightning induced transients. Although no system is
completely immune from lightning transients and interferences, proper grounding will
reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to
an increased susceptibility to nearby lightning strikes. Consult with the Technical
Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards.
Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching
of the enclosure. When possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not interfere with battery,
transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over tightening may damage
threads, resulting in reduced terminal contact pressure and difficulty with screw
terminal removal.
This system contains static-sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are removed
from the body. Use static suppressive packaging to protect electronic assemblies
removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability depend upon proper
installation.
While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke detectors, heat
detectors, manual pull stations, audible warning devices, and a fire alarm control
with remote notification capability can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or
loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such
as in chimneys, in walls, or roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor of a building. A second
floor detector, for example, may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused
by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical
circuits, children playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the
control panel and in rooms used by the system for the connection of alarm
transmission wiring, communications, signaling, and/or power. If detectors are
not so located, a developing fire may damage the alarm system, crippling its
ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are
located on the other side of closed or partly open doors or are located on another
floor of a building.
A fire alarm system will not operate without any electrical power. If AC power fails,
the system will operate from standby batteries only for a specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For
this reason, the rate-of-rise feature of each detector should be tested at least once
per year by a qualified fire protection specialist.
Equipment used in the system may not be technically compatible with the control.
It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled.
The most common cause of fire alarm malfunctions, however, is inadequate
maintenance. All devices and system wiring should be tested and maintained by
professional fire alarm installers following written procedures supplied with each
device. System inspection and testing should be scheduled monthly or as required
by National and/or local fire codes. Adequate written records of all inspections should
be kept.
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency
energy and if not installed and used in accordance with the instruction manual, may
cause interference to radio communications. It has been tested and found to comply
with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC
Rules, which is designed to provide reasonable protection against such interference
when operated in a commercial environment. Operation of this equipment in a
residential area is likely to cause interference, in which case the user will be required
to correct the interference at his own expense.
Technical Publishing
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise
emissions from digital apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les
limites applicables aux appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Document PRECAULG.P65 12/31/96
Table of Contents
Chapter 1
System Overview
Section 1.0: Description
Section 1.1: Features
Section 1.2: LED Indicators
Section 1.3: Configuration Jumpers, Resistors & Diodes
Section 1.4: Optional Device MPM-4F Description
Section 1.5: Specifications
Section 1.6: Installation Standards and Codes
Figure 1-1: FCPS Board Layout
Section 1.7: General
Figure 1-2: Simplified FCPS Block Diagram
4
4
4
4
5
5
6
6
7
8
8
Chapter 2
Installation
Section 2.0: General
Section 2.1: Backbox Mounting
Section 2.2: MPM-4F Installation
Figure 2-1: Backbox Mounting Dimensions
Figure 2-2: MPM-4F Installation Diagram
Section 2.3: UL Power-limited Wiring Requirements
Figure 2-3: Power-limited Wiring Requirements
9
9
9
9
10
10
11
11
Chapter 3
Operation
12
Section 3.0: Trouble Supervision
12
Section 3.1: Supervision via FACP Notification Appliance Ckt
12
Figure 3-1: Wiring Diagram for Multiple FCPS Units
13
Section 3.2: Full Supervision via Input Circuit or Monitor Module 13
Chapter 4
Special Applications
Section 4.0: Specific Applications
Section 4.1: Controlling Four Outputs from One Input
Figure 4-1a: Control Module Application (Style Y)
Figure 4-1b: Control Module Application (Style Z)
Section 4.2: Controlling Four Outputs from Two NAC Inputs
Figure 4-2: Two Inputs Controlling Four Outputs
Section 4.3: Controlling Four Outputs from One NAC Input
Figure 4-3: One NAC Input Controlling Four Outputs
Section 4.4: Stand-alone Power Supply - Nonresettable
Figure 4-4: Stand-alone Power Supply
Section 4.5: Remote Power Supply resettable/Nonresettable
Figure 4-5: One NAC Input - Resettable & Nonresettable
Section 4.6: Control Module Activation of Output Circuits
Figure 4-6: Control Module Activation of Outputs
Section 4.7: Door Release Service Application
Figure 4-7: Using the FCPS with 24 VDC Door Holders
14
14
14
14
15
16
16
17
17
18
18
19
19
20
20
21
21
Chapter 5
Battery Calculations
Section 5.0: External Device Power
Section 5.1: Device Standby Current Draw
Table 5-1: Load in Standby
Table 5-2: Load in Alarm
Table 5-3: Secondary Power Source Calculations
22
22
22
22
23
24
Document # 50079
Rev. D
05/23/97
Page
3
CHAPTER ONE
System Overview
1.0
Description
The FCPS-24F is a compact, cost-effective, remote power supply and battery charger.
This remote power supply consists of a filtered 24 VDC output that may be configured
to drive four Notification Appliance Circuits (two Style Y or Style Z, and two Style Y only).
Alternately, the four Notification Appliance Circuits may be configured as resettable or
nonresettable power outputs. The FCPS-24FE offers the same features as the FCPS24F but allows connection to 220/240 VAC input.
1.1
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Self contained in lockable cabinet.
24 VDC remote power supply.
Outputs are completely power-limited.
Two optically-isolated input/control circuits.
Two Style Y/Style Z Notification Appliance Circuits.
Two additional circuits that are configurable as Style Y Notification Appliance Circuits.
Alternately, all four or a combination of the circuits may be configured as
24 VDC power outputs.
Output power circuits may be configured as resettable or nonresettable.
3.0 amps maximum current available for any one output circuit.
4.0 amps total of continuous current available.
6.0 amps maximum short term (one hour maximum) current can be
provided.
Fully filtered power output.
Integral supervised battery charger.
Up to 7.0 AH batteries in remote power supply cabinet.
Fully supervised power supply, battery, and Notification Appliance Circuits.
Selectable Earth Fault detection.
Delay of AC loss reporting (8 or 16 hours).
Fixed terminal blocks for field wiring that are capable of accepting up to 12
AWG wire.
Normally closed trouble contact.
MPM-4F optional charger Voltmeter/Ammeter.
1.2 LED Indicators
•
•
•
•
AC power on (green).
AC Fail/Earth Fault (yellow).
Battery/charger trouble (yellow).
Circuits field wiring faults (yellow). Circuits 1 through 4 are supervised for
shorts and opens during the inactive state.
Note: Unless otherwise specified, the term 'FCPS' shall be used in this manual, where
appropriate, to refer to both the FCPS-24F and FCPS-24FE power supplies.
Page 4
Document # 50079 Rev. D
05/23/97
1.3 Configuration Jumpers, Resistors & Diodes
•
Battery Charging Circuit (JP1) - To disable local battery charger, cut jumper
JP1 (an external charger listed for fire protective signaling is required).
•
Optional MPM-4F Voltmeter/Ammeter - To enable charger current measurement with MPM-4F, cut JP1 and plug-in MPM-4F connector to the P3
header.
•
Earth Fault Detection (R27)- To disable local earth fault detection, cut
resistor R27. Note that Earth Fault detection is required in Canada.
•
Trouble Supervision (R63, D31, JP2) - These components are used to
configure local trouble reporting through the remote power supply trouble
contact. Refer to the Trouble Supervision section for a complete description.
•
Delay AC Loss Reporting (R76 and R134) - When a Digital Alarm Communicator Transmitter (DACT) is installed in the FACP, the reporting of an AC
loss condition to a central station must be delayed. With 24-hour battery
standby, cut R134 to delay AC loss reporting for 8 hours. With 60-hour
battery standby, cut R76 and R134 to delay the report by 16 hours.
•
Disable Resettable Power Function for Output Circuit #2 or #4 (R175 and
R176).
Cut R175 to make Output #2 nonresettable power.
Cut R176 to make Output #4 nonresettable power.
1.4 Optional Device MPM-4F Description
The MPM-4F is used for:
• Monitoring battery/charger voltage (Voltmeter)
• Monitoring charger current (Ammeter)
The MPM-4F is most commonly required in military installations. It consists of
two analog edge meters (a voltmeter and an ammeter) which connects to the
P3 Header.
The voltmeter measures battery and charger voltage. It is electrically connected across battery terminals TB2.1 and TB2.2. When the battery is
disconnected, the voltmeter measures charger voltage only. Periodically
(approximately 2 seconds every 40 seconds) the FCPS performs a battery test
by disabling the charger. During this period, charger current that is measured
by the ammeter, drops to zero. The voltmeter now only measures the battery
voltage. Battery voltage ranges from 20.4 (low battery) to 27.6 (fully charged).
The ammeter is electrically connected across JP1 and measures current
delivered from the charger to the battery, except for the period during the battery
test. Charger current is normally limited to 250mA. In order to enable the
ammeter, JP1 must be cut.
1.5 Specifications
Primary (AC) Power
• FCPS-24F: 120 VAC 50/60 Hz, 2.0 A maximum.
• FCPS-24FE: 220/240 VAC 50/60 Hz, 1.0 A maximum.
Document # 50079
Rev. D
05/23/97
Page
5
•
Wire size: minimum #14 AWG with 600V insulation
Control Input Circuit
• Trigger Input Voltage - 9 to 32 VDC
• Input Current Draw in Alarm Polarity
16 - 32V 2.0mA per input
9 - 16V 1.0mA per input
Trouble Contact Rating
• 5 amps at 24VDC
Output Circuits (19.1 - 26.4 VDC, filtered)
• 3.0 amps maximum for any one circuit
• 4.0 amps maximum total continuous current for all outputs
• 6.0 amps maximum total short term (one hour maximum) current for all
outputs
Auxiliary Power Output
• Specific Application Power - 45 mA Short Circuit.
Secondary Power (Battery) Charging Circuit
• Supports lead acid batteries only.
• Float Charge Voltage: 27.6V
• Maximum Charge Current: 250 mA
• Maximum Battery Capacity: 7.0 AH
1.6 Installation Standards and Codes
The FCPS complies with the following standards:
NFPA 72-1993 National Fire Alarm Code
Underwriters Laboratories:
• UL 864 Standard for Control Units for Fire Alarm Systems
• UL 1481 Power Supplies for Fire Alarm Systems
In addition, the installer should be familiar with the following standards:
• NEC Article 300 Wiring Methods
• NEC Article 760 Fire Protective Signaling Systems
• Applicable Local and State Building Codes
• Requirements of the Local Authority Having Jurisdiction
Other documents supporting Fire•Lite Alarms products referenced in this
manual are listed below.
• Device Compatibility Document 15384
• The MS-9200 Instruction Manual, Document 15668
• The Sensiscan 2000 Installation Manual, Document 15017
Page 6
Document # 50079 Rev. D
05/23/97
To Transformer #2
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Output
Earth
AC Neutral
AC Hot
1 + (Style Y/Z)
1 - (Style Y/Z)
1 + (Style Z)
1 - (Style Z)
2 + (Style Y)
2 - (Style Y)
3 + (Style Y/Z)
3 - (Style Y/Z)
3 + (Style Z)
3 - (Style Z)
4 + (Style Y)
4 - (Style Y)
To Transformer #1
R175
D31
R76
JP2
In +
In -
(Control Input #1 from FACP)
Out +/Trouble Contact
Out -
Cut JP1 to Enable
Voltmeter/Ammeter
R176
R63
JP1
Battery fuse 10A 3AG slow blow
R134
Trouble Contact
In +
(Control Input #2 from FACP)
In Auxiliary Output (Specific Application
Power, 45 mA Short Circuit)
Common
AC On
AC Failure/Earth Fault
Battery/Charger Trouble
Output 1 Trouble
Output 2 Trouble
Output 3 Trouble
Output 4 Trouble
To MPM-4F
(Voltmeter/Ammeter)
Connection
Battery (+)
Battery (-)
7AH, 24 VDC
R27
Figure 1-1: FCPS Board Layout
Document # 50079
Rev. D
05/23/97
Page
7
1.7 General
The FCPS may be used in a number of different applications. It may be used as a
remotely-mounted power supply and battery charger where it can power up to four,
coded or non-coded, Notification Appliance Circuits. Alternately, any or all of these
circuits may be used as 24 VDC output circuits capable of powering four wire smoke
detectors or any device that requires filtered power. These circuits may be configured
as resettable or nonresettable outputs.
Style Y/Style Z
Notification
Appliance Circuit or
24 VDC Output #1
Notification
Appliance Circuit
Control Input #1
(from FACP)
Style Y Notification
Appliance Circuit or
24 VDC Output #2
Style Y/Style Z
Notification
Appliance Circuit or
24 VDC Output #3
Notification
Appliance Circuit
Control Input #2
(from FACP)
Style Y Notification
Appliance Circuit or
24 VDC Output #4
Battery Charger
AC Power
Specific
FCPS Trouble
Application Contact Output
Power
Figure 1-2: Simplified FCPS Block Diagram
One of the most common applications for the FCPS remote power supply utilizes the
NAC repeater feature. In this application, one or two Notification Appliance Circuits
(NAC) are connected from the main FACP NAC output(s) to the remote power supply
Control Input circuits. When these Control Input circuits activate (due to reverse polarity
of the NAC output), the power supply will activate its corresponding outputs. NAC
Control Input #1 controls power supply output circuits #1 and #2. NAC Control Input #2
controls output circuits #3 and #4 (refer to Figure 4-2).
During the inactive state, the remote power supply supervises its NAC field wiring for
short and open circuits. If a fault is detected, the supply will enter a trouble condition
and illuminate the corresponding NAC trouble LED (Output Circuits 1-4). However,
once the Notification Appliance Circuits are activated, the supervision is disabled and
the circuits are no longer supervised. Supervision of other power supply faults such as
low battery, Earth Fault, AC loss and battery charger failure will continue and may be
monitored via the trouble relay contact.
If a specific application requires that all four outputs activate at the same time, only one
NAC control input from the FACP is necessary. For this application, the Notification
Appliance Circuit from the FACP is wired into NAC Control Input #1 of the remote supply
and then a pair of wires are connected from NAC Control Output #1 to NAC Control Input
#2 (refer to Figure 4-3).
Page 8
Document # 50079 Rev. D
05/23/97
CHAPTER TWO:
Installation
2.0
General
Carefully unpack the system and check for shipping damage. Select a location for the
cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not
encountered. The area should be readily accessible with sufficient room to easily install
and maintain the panel. Locate the top of the cabinet approximately five feet above the
floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed and
determine the appropriate knockouts. All wiring must be in accordance with the National
and/or Local codes for fire alarm systems.
2.1 Backbox Mounting
1) Remove the main PC board assembly by unscrewing the four screws in the
corners of the board. Two permanent standoffs support the board in the
center.
Set the board aside in a safe, clean place. Avoid static discharge which
may damage the board.
2) Mark and predrill holes for the top two keyhole mounting bolts.
3) Install two upper fasteners in the wall with the screw heads protruding
approximately 1/4".
4) Using the upper keyholes, mount the backbox over the two screws.
5) Mark the lower two holes, remove backbox and drill mounting holes.
6) Mount backbox, install remaining fasteners and tighten.
7) When the location is dry and free of construction dust, reinstall the main PC
board (refer to Figure 2.1).
2.2 MPM-4F Installation
1) Cut Jumper JP1.
2) With a nut driver, loosen bottom nut of the lower transformer.
3) Slide in MPM-4F meter bracket between transformer and nut.
4) Fasten the nut.
5) Connect the meter assembly cable to P3 header (refer to Figure 2.2).
Document # 50079
Rev. D
05/23/97
Page
9
Top
2.875"
Backbox=14.5"
Depth=3.562"
0.75"
9.1"
2.7"
10.625"
Door=15.218"
1.125"
Bottom
Figure 2-1: Backbox Mounting Dimensions
Transformer
JP1
Bottom Nut
P3
Header
MPM-4F Meter
Bracket
Meter Assembly
Cable
Figure 2-2: MPM-4F Installation Diagram
Page 10
Document # 50079 Rev. D
05/23/97
2.3 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the
cabinet. All power-limited circuit wiring must remain at least 0.25" away from any
nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and
nonpower-limited circuit wiring must enter and exit the cabinet through different
conduits. One such example of this is shown below. Your specific application may
require different conduit knockouts to be used. Any conduit knockouts may be used.
For power-limited applications, use of conduit is optional.
If input circuit wiring
is nonpower-limited, the 24
VDC output on terminals 8 & 9
cannot be used and all wiring
must be run in conduit.
Figure 2-3: Power-limited Wiring Example
Document # 50079
Rev. D
05/23/97
Page
11
CHAPTER THREE:
Operation
3.0 Trouble Supervision
When a trouble occurs on the FCPS, it must also appear on the main Fire Alarm Control
Panel. The remote power supply has two ways of sending this trouble signal to the
FACP. However, only one of the trouble reporting methods may be used.
3.1 Supervision via FACP Notification Appliance Circuit
Supervision of FACP to FCPS Wiring
The FACP supervises the connection between itself and the FCPS via an End-of-Line
Resistor (ELR). The ELR must be installed at the FCPS end of the circuit. If no additional
devices are connected to these terminals, the ELR must be connected directly across
terminals 3 and 4. An open or short on this circuit will be detected at the FACP as an
NAC trouble (refer to Figure 4-2).
Supervision of FCPS Faults
The FACP will detect these power supply faults as an open circuit condition on its NAC.
Any of the following conditions will cause an internal trouble contact on the FCPS to open
provided the FACP NAC is not in alarm:
a)
b)
c)
d)
e)
A field wiring fault on any output of the power supply during the inactive state.
An AC fail condition at the power supply (may be delayed depending on R134).
A battery fail condition at the power supply.
Battery charger fail.
Earth Fault condition.
Any power supply trouble will break the connection between the FACP and the ELR
provided the FACP's NAC is not in alarm. The FACP's ELR must be placed after the
last NAC appliance connected to FCPS terminals 3 & 4 or, if no appliances are
connected to these terminals, the ELR must be connected directly across terminals 3
& 4 (refer to Figure 4-2 and 4-3).
Note: Circuit Control Input #2 cannot be used to supervise the power supply but an ELR
is still required for FACP wiring supervision.
Multiple FCPS-24 Controlled by a Single NAC
In a standby condition with no troubles, the FACP NAC output produces a negative
voltage which forces current to flow through the ELR. If any FCPS is in a trouble state,
that FCPS will open connection between input terminal TB3.1 and TB3.3. This will cause
a break in the NAC, which will then be reported by the FACP as a NAC open trouble.
The alarm polarity sent by the FACP will always force restoration of connection between
TB3.1 and TB3.3 on all FCPS units, unless this function was disabled by cutting resistor
R63 or by the removal of JP2 and D31 (refer to Figure 3-1).
Page 12
Document # 50079 Rev. D
05/23/97
Figure 3-1: Wiring Diagram of Multiple FCPS Units
3.2 Full Supervision via Input Circuit or Monitor Module
This method of supervision provides FACP annunciation of the FCPS trouble condition
even if the FACP is in alarm. The FACP's Notification Appliance Circuit is not used for
supervision. Cut diode D31, jumper JP2 and resistor R63. Monitor FCPS trouble
contacts at terminals TB3-3 and TB3-5. Any trouble condition listed above will trigger
the internal trouble contact regardless of voltage polarity on the input 1. An addressable
monitor module or any FACP input circuit may be used to track the condition of the
trouble contact (refer to Figures 4-4, 4-5 and 4-6).
Document # 50079
Rev. D
05/23/97
Page
13
CHAPTER FOUR:
Special Applications
4.0 Specific Applications
4.1 Controlling Four Outputs from One Input
All four FCPS output circuits can be controlled from one control input, which in Figures
4-1a and 4-1b is illustrated as a control module. The control module can be powered
from the FCPS auxiliary 24 VDC power output (TB3 terminals 8 & 9) and supervised by
an EOL relay.
All four remote power supply outputs are shown as Notification Appliance Circuits.
Alternately, circuits 2 and/or 4 could be used as nonresettable power output circuits
which is accomplished by cutting resistors R175 for circuit 2 or R176 for circuit 4 (refer
to Figures 4-4 and 4-5).
The control module is shown to demonstrate the use of the power supply on a
multiplexed system. The control module could be replaced with any circuit capable of
polarity reversal. Note that Figure 4-1a shows Style Y configuration and Figure 4-1b
shows Style Z configuration.
Optional Style
Z Return
Style Y
Optional Style
Z Return
Style Y
*
*
* Use listed ELR (P/N R-2.2K) to terminate Style Y NAC. ELRs are not
required when Style Z return is wired.
Note: All Notification Appliance Circuits are supervised.
Style Y
*
*
CKT #1
CKT #2 CKT #3
CKT #4
Refer to Section 1.1 for current ratings.
SLC
Loop to Addressable
FACP
+ -
Control
Input #1
Control
Module
Control
Input #2
24 VDC NAC Power
Common
Specific
Application
Power
47 K ELR for Control Module
Part Number A2143-20 (F-ELR)
required in Canada
EOL Power
Supervision Relay
(A77-716B)
Figure 4-1a: Control Module Application (Style Y)
Page 14
Document # 50079 Rev. D
05/23/97
Notes: (The following notes apply to Figure 4-1a)
1) When the remote power supply is in an inactive state (control module not active), a trouble
on the power supply will result in an open circuit condition on the control module. As an
alternative to monitor for trouble conditions, the trouble contact on the FCPS may be used for
independent trouble monitoring (refer to Figures 4-5 and 4-6).
2) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
3) For Style Y application, an ELR must be installed between Terminals 6 and 7 for control module
wiring supervision (the ELR value is dependent on the module employed).
4) Supervise the wiring between the FCPS 24 VDC output on TB3 terminals 8 &9 and the control
module with an EOL relay (A77-716B).
5) For a list of compatible devices, refer to the Fire-Lite Device Compatibility Document.
Optional Style
Z Return
* Use listed ELR (P/N R-2.2K) to terminate Style Y NAC. ELRs are
not required when Style Z return is wired.
Note: All Notification Appliance Circuits are supervised.
Optional Style
Z Return
Style Y
Style Y
*
CKT #1
*
* Style Y
*
CKT #4
CKT #2 CKT #3
Refer to Section 1.1 for current ratings.
SLC Loop to
Addressable FACP
- +
Control
Module
24 VDC Power
Common
Specific Application
Power
EOL Supervision
Relay
(A77-716B)
Figure 4-1b: Control Module Application (Style Z)
Notes: (The following notes apply to Figure 4-1b)
1) When the remote power supply is in an inactive state (control module not active), a trouble
on the power supply will result in an open circuit condition on the control module. As an
alternative to monitor for trouble conditions, the trouble contact on the FCPS may be used
for independent trouble monitoring (refer to Figures 4-5 and 4-6).
2) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
3) Supervise the wiring between the FCPS 24 VDC output on TB3 terminals 8 &9 and the control
module with an EOL relay (A77-716B).
4) For a list of compatible devices, refer to the Fire-Lite Device Compatibility Document.
Document # 50079
Rev. D
05/23/97
Page
15
4.2 Controlling Four Outputs from Two NAC Inputs
This application expands notification appliance power by an additional 6.0 amps.
Use up to four Class B (Style Y) outputs or two Class A (Style Z) and two Class B
(Style Y) outputs. In this example, the FACP Notification Appliance Circuits will
activate the remote power supply when reverse polarity activation occurs due to an
alarm condition. NAC #1 will activate FCPS outputs 1 & 2 and NAC #2 will activate
outputs 3 & 4. Trouble conditions on the power supply are monitored by the FACP
via Notification Appliance Circuit #1. Since Input #1 can monitor troubles, it is
advisable to control silenceable notification appliances with this circuit and
nonsilenceable or resettable smoke detector power with Control Input #2.
Optional Style
Z Return
Optional Style
Z Return
*
*
1
2
3
4
5
*
6
7
* Use listed ELR (P/N R-2.2K) to terminate Style Y NAC. ELRs are
not required when Style Z return is wired.
Note: All Notification Appliance Circuits are supervised.
*
8
9
10 11 12
Refer to Section 1.1 for current ratings.
Continuation of Notification Appliance
Circuit #1 from FACP
Note 1
ELR
This circuit may be power-limited or nonpower-limited
Control Input #1
Notification
Appliance
Circuit #1
Fire Alarm
Control Panel
Control Input #2
Notification
Appliance
Circuit #2
Continuation of Notification Appliance
Circuit #2 from FACP
Note 1
ELR
This circuit must be power-limited by the FACP
Notes:
1) ELRs must be used on the Notification Appliance Circuits. Refer to the respective FACP
installation manual for corresponding ELR value. If no devices are installed on a branch,
dummy load the circuit with the ELR.
2) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
3) For a list of compatible devices, refer to the Fire-Lite Device Compatibility Document.
Figure 4-2: Two Inputs Controlling Four Outputs
Page 16
Document # 50079 Rev. D
05/23/97
4.3 Controlling Four Outputs from One NAC Input
This application expands notification appliance power by an additional 6.0 amps. Use
up to four Class B (Style Y) outputs or two Class A (Style Z) and two Class B (Style Y)
outputs. In this example, the FACP Notification Appliance Circuit will activate the
remote power supply when reverse polarity activation occurs. Trouble conditions on the
power supply are sensed by the FACP through the Notification Appliance Circuit #1.
Since Control Input #1 can monitor the NAC and power supply for troubles only in the
nonactive state, it is advisable to control silenceable notification appliances with this
circuit and nonsilenceable or nonresettable power with Control Input #2.
Optional Style
Z Return
Optional Style
Z Return
*
*
1
2
3
4
5
*
6
7
* Use listed ELR (P/N R-2.2K) to terminate Style Y NAC. ELRs are
not required when Style Z return is wired.
Note: All Notification Appliance Circuits are supervised.
*
8
9 10
11 12
Refer to Section 1.1 for current ratings.
Continuation of Notification Appliance
Circuit #1 from FACP
Note 3
ELR
This circuit may be power-limited or nonpower-limited
Control Input #1
Note 1
Notification
Appliance
Circuit #1
Fire Alarm
Control Panel
Control Input #2
Note 2
Notes:
1) Connect the Notification Appliance Circuit originating from the FACP to TB3 terminals 1 and
2 on the FCPS.
2) Jumper TB3 Terminal 3 to Terminal 6 and Terminal 4 to Terminal 7. This allows a single
Control Input to control the four FCPS outputs. Install the ELR across terminals 6 and 7 to
supervise the Notification Appliance Circuit originating from the FACP as well as the
jumpers. Refer to the respective FACP installation manual for corresponding ELR value.
3) If additional notification appliances are installed, remove the ELR from FCPS TB3 terminals
6 and 7, connect the devices to FCPS terminals 6 and 7 and install the ELR after the last
device.
4) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
5) For a list of compatible devices, refer to Fire-Lite Device Compatibility Document.
Figure 4-3: One NAC Input Controlling Four Outputs
Document # 50079
Rev. D
05/23/97
Page
17
4.4 Stand-Alone Power Supply for Nonresettable Outputs
The FCPS may be used as a remote stand-alone power supply to provide up to an
additional 4.0 amps of power to any devices that require filtered, regulated, nonresettable
power. A nonresettable output is created by jumpering the auxiliary 24VDC output
[TB3-8 (+) & TB3-9 (-)] to Control Input circuits 1 and 2. For addressable panel
applications, a monitor module may be used to monitor the trouble contact of the FCPS.
If the FCPS enters a trouble condition the normally closed contact will open. Cut JP2,
R63 and D31 for this application.
+
Power Output
Circuit #2
Power Output
Circuit #1
-
-
+
Power Output
Circuit #3
+ Power Output
+
1
2
3
4
5
6
7
8
Circuit #4
SLC
Loop to Addressable
FACP
+ -
9 10 11 12
Power-limited non-supervised
End of line relay required for supervision.
Refer to Section 1.1 for current ratings.
Monitor
Module
Control
Input #1
Trouble
Notes 1 & 2
Note 3
ELR
Control
Input #2
Aux 24VDC
Common
Notes:
1) If an addressable M302 Monitor Module is employed to monitor the trouble contacts of the
remote power supply, the module must be supplied with separate 24 VDC power. This
power is required so that the module may supervise the connection to the trouble contacts
of the power supply.
2) One of the FCPS nonresettable power outputs (TB4) can be used to supply 24 VDC to M302
terminals 3 and 4 or a separate power source can be used. The auxiliary power output of
the FCPS power supply (TB3 Terminals 8 & 9) should not be used for this purpose.
3) The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB33 and TB3-5 is dependent on the particular model of monitor module employed to supervise
the FCPS. The Fire-Lite model M300 and M301 require a 47K ELR. The Fire-Lite model
M302 requires a 3.9K ELR.
4) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
5) For a list of compatible devices, refer to Fire-Lite Device Compatibility Document.
6) It may be necessary to use an EOL relay on normally activated outputs for proper
supervision.
Figure 4-4: Remote Stand-Alone Power Supply
Page 18
Document # 50079 Rev. D
05/23/97
4.5 Remote Power Supply - Resettable and Nonresettable
The FCPS may be used as a remote stand-alone power supply to provide up to an
additional 4.0 amps of power to any devices that require filtered, regulated, resettable
or nonresettable power. A monitor module may be used to monitor the trouble contact
of the FCPS. If the FCPS enters a trouble condition the normally closed contact will
open. A resettable output is created by tying the resettable output from the FACP to one
or both of the power supply inputs. A nonresettable output is created by cutting an on
board resistor (R175 for Output 2, R176 for Output 4). For addressable panel
applications, use a monitor module to sense the trouble status of the remote power
supply via the trouble relay contact. Cut JP2, R63 and D31 for this application.
Resettable
Power Output
Circuit #1
+
-
1
2
3
Power Output
Circuit #2
+
4
5
-
6
Note 1
Power Output
Circuit #4
Resettable
Power Output
Circuit #3
+
-
7
8
+
Resettable outputs deliver a negative polarity
voltage of up to -5 VDC during reset. In the unlikely
case that this negative voltage causes a problem
resetting certain models of 4-wire smoke detectors,
use TB-4 terminals 3 (+) and 2 (-) for Output #1 and
terminals 9 (+) and 8 (-) for Output #3.
-
9 10 11 12
Refer to Section 1.1 for current ratings.
Fire Alarm
Control Panel
Control Input #1
Resettable
24VDC Output
Note 2
Trouble
Control
Input #2
SLC
ELR
Monitor
Module
Notes 4 & 5
Notes:
1) Outputs 2 and 4 are also resettable 24 VDC power in this example. To make Output 2
nonresettable power, cut R175. To make Output 4 nonresettable, cut R176.
2) The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB33 and TB3-5 is dependent on the particular model of monitor module employed to supervise
the FCPS. Fire-Lite models M300 and M301 require a 47K ELR. Fire-Lite model M302
requires a 3.9K ELR.
3) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
4) If an addressable M302 Monitor Module is employed to monitor the trouble contacts of the
remote power supply, the module must be supplied with separate 24 VDC power. This power
is required so that the module may supervise the connection to the trouble contacts of the
power supply.
5) One of the FCPS nonresettable power outputs (TB4) can be used to supply 24 VDC to M302
terminals 3 and 4 or a separate power source can be used. The auxiliary power output of
the FCPS power supply (TB3 Terminals 8 & 9) should not be used for this purpose.
6) For a list of compatible devices, refer to Fire-Lite Device Compatibility Document.
7) It may be necessary to use an EOL relay on outputs that are normally activated for proper
supervision.
Figure 4-5: One NAC Input - Resettable & Nonresettable Outputs
Document # 50079
Rev. D
05/23/97
Page
19
4.6 Control Module Activation of Output Circuits
This application illustrates the use of addressable control modules instead of Notification
Appliance Circuits on an FACP to activate the FCPS remote power supply. Typically,
this allows for mounting of the power supply at greater distances from the FACP and
expanding the system architecture in various applications.
An addressable control module is used to activate the power supply and an addressable
monitor module is used to sense power supply trouble conditions. The Fire•Lite MS9200 has the capability of locating control and monitor modules up to 10,000 feet away.
Cut JP2, R63 and D31 for this application.
Optional Style
Z Return
*
*
1 2 3 4 5
Optional Style
Z Return
*
* Use listed ELR (P/N R-2.2K) to terminate Style Y NAC. ELRs are
not required when Style Z return is wired.
Note: All Notification Appliance Circuits are supervised.
*
6 7 8 9 10 11 12
Refer to Section 1.1 for current ratings.
SLC Loop
+ -
Control
Module
Note 6
Note 1
EOL Supervision
Relay (A77-716B)
SLC Loop
+ -
Monitor
Module
Notes 4 & 5
Note 2 & 3
Notes:
1) To control all four power supply outputs with one control module, connect output to TB3
Terminals 1 and 2 on the FCPS and jumper Terminal 1 to Terminal 6 and Terminal 2 to
Terminal 7.
2) An ELR must be installed between Terminals 6 and 7 for control module wiring supervision
(the ELR value is dependent on the module employed).
3) The specific ELR required to be installed on the FCPS trouble monitoring contacts at TB3-3
and TB3-5 is dependent on the particular model of monitor module employed to supervise the
FCPS. Fire-Lite models M300 and M301 require a 47K ELR. Fire-Lite model M302 requires
a 3.9K ELR.
4) If an addressable M302 Monitor Module is employed to monitor the trouble contacts of the
remote power supply, the module must be supplied with separate 24 VDC power. This power
is required so that the module may supervise the connection to the trouble contacts of the
power supply.
5) One of the FCPS nonresettable power outputs (TB4) can be used to supply 24 VDC to M302
terminals 3 and 4 or a separate power source can be used. The auxiliary power output of the
FCPS power supply (TB3 Terminals 8 & 9) should not be used for this purpose.
6) Use EOL relay (A77-716B) to supervise 24 VDC power from the FCPS, TB3 terminals 8 & 9.
7) Do not loop wires under screw terminals. Break wires to maintain proper supervision.
8) For a list of compatible devices, refer to Fire-Lite Device Compatibility Document.
Figure 4-6: Control Module Activation of Outputs
Page 20
Document # 50079 Rev. D
05/23/97
4.7 Door Release Service
This application illustrates the use of the FCPS to power 24 VDC door holders. A signal
must be supplied from the FACP to activate the FCPS's outputs. This signal should
consist of a 24 VDC source run through a set of normally closed alarm contacts. During
a normal (nonalarm) condition, 24 VDC should be applied to the FCPS. This will result
in the outputs of the FCPS being activated which will in turn energize the door holders.
When the FACP enters an alarm condition, the relay contact will open and remove the
24 VDC signal from the FCPS, causing the doors to close.
Typical 24 VDC Door Holder circuits.
Use polarized devices only.
1
2
3
4
5
6
7
8
9 10 11 12
Refer to Section 1.1 for current ratings.
Note 4
+ 24 VDC nonresettable
Relay Common
Control Input #1
Relay Normally Closed
Power Supply Common
Fire Alarm
Control Panel
Control input #2
Notes:
1) During a normal condition (nonalarm), +24 VDC should be applied to TB3-1 and TB3-2.
2) The normally closed alarm relay may consist of an actual relay in the Fire Alarm Control Panel
or a control module. If a control module is being used, it may be mounted remotely or at
the control panel.
3) A monitor module may be used to monitor the trouble contacts of the FCPS.
4) Nonresettable power must be used from the FACP.
5) A maximum of 4.0 amps may be drawn continuously for holding doors.
6) For a list of compatible devices, refer to the Fire-Lite Device Compatibility Document.
7) Loss of AC power may cause doors to close due to a momentary power drop while switching
over to batteries.
Figure 4-7: Using the FCPS with 24 VDC Door Holders
Document # 50079
Rev. D
05/23/97
Page
21
CHAPTER FIVE
Battery Calculations
5.0
External Device Power
The FCPS provides filtered 24VDC power that may be used for operating Notification
Appliance Circuits or other external devices. The power for operating external devices
is limited. Use Table 5-1 (standby or nonalarm) and Table 5-2 (alarm) to determine if
external loading is within the capabilities of the power supply.
Refer to the device manufacturer's data sheets packaged with each device to find the
standby and alarm current draws to use in the tables that follow.
5.1 Device Standby Current Draw
The following table should include the total standby current draw of all devices on each
active output, including end of line relays when used for supervision.
Device Type
# of Devices
Main PC Board without AC
Fail Repor t Delay Enabled
(1 maximum)
X
0.032
OR
Main PC Board with AC Fail
Repor t Delay Enabled
Total
Current
(Amps)
Current
(Amps)
=
(1 maximum)
X
0.048
0.008
MPM-4
[
]
X
EOL Relays
[
]
X
=
Smoke Detectors
[
]
X
=
Smoke Detectors
[
]
X
=
EOL Resistors
[
]
X
=
Annunciators
[
]
X
=
Auxiliary Devices
[
]
X
=
Auxiliary Devices
[
]
X
=
Auxiliary Devices
[
]
X
=
Sum Column for Standby Load
=
=
Table 5-1: Load in Standby @24VDC
Page 22
Document # 50079 Rev. D
05/23/97
Amps
Current Calculations
1. When Using the 6.0 amps Maximum Current Available:
Five minutes under full load (6.0 amps current draw) requires 3.0 AH of a 7.0 AH
capacity battery. The remaining 4.0 AH capacity must support the FCPS during its
required standby time. Because of this, the standby current draw cannot exceed the
figures listed below:
1) For 24 hour standby time, the standby current draw cannot exceed 0.166 amps at 24
VDC (24 hours x 0.166A) = 3.984 AH
2) For 60 hour standby time, the standby current draw cannot exceed 0.066 amps at 24
VDC (60 hours x 0.066A) = 3.96 AH
3) Standby Current Calculation
Subtract total standby load calculated above from 0.166 amps for 24 hours standby or
0.066 amps for 60 hours standby. This figure should not be less than zero. If the amount
is less than zero, the required standby time will not be achieved.
2. When Using Less than 6.0 amps Maximum Current:
Use the following tables to determine the proper battery size.
3. When Battery Amp-Hour Requirements are for Greater than 7.0 AH:
Cut FCPS jumper JP1 to disable onboard battery charger and use an external battery
charger.
Device Type
# of Devices
Main PC Board without AC
Fail Repor t Delay Enabled
(1 maximum)
Current
(Amps)
X
Total Current
(Amps)
0.032
OR
=
Main PC Board with AC Fail
Repor t Delay Enabled
(1 maximum)
X
0.048
0.008
MPM-4
[
]
X
EOL Relays
[
]
X
=
Smoke Detectors
[
]
X
=
Smoke Detectors
[
]
X
=
EOL Resistors
[
]
X
=
Annunciators
[
]
X
=
Auxiliary Devices
[
]
X
=
Auxiliary Devices
[
]
X
=
Auxiliary Devices
[
]
X
=
Notification Appliances
[
]
X
=
Notification Appliances
[
]
X
=
Notification Appliances
[
]
X
=
Sum Column for Alarm Load
=
=
Amps
Table 5-2: Load in Alarm @24VDC
Document # 50079
Rev. D
05/23/97
Page
23
Secondary Power Source Calculations
Use the Total Standby and Alarm Load Currents calculated in Tables 5-1 and 5-2 for
the following battery calculation.
Standby Load
Current (Amps)
[
]
X
Alarm Load
Current (Amps)
[
]
X
Required Standby Time in Hours
(24 or 60 Hours)
[
]
=
_________
Required Alarm Time in Hours (i.e.
5 min. = 0.084 hours)
=
[
]
_________
Add Standby and Alarm Load for Required Ampere Hours
=
_________
Multiply by the Derating Factor of 1.2
=
_________
Total Ampere Hours (AH) Required
=
_________
Table 5-3: Secondary Power Source Calculations
Notes:
1) Battery size is limited to 7.0 AH using the internal FCPS battery charger.
2) For battery sizes greater than 7.0 AH, cut FCPS jumper JP1 to disable the internal battery
charger and use an external battery charger.
Page 24
Document # 50079 Rev. D
05/23/97
NOTES
Document # 50079
Rev. D
05/23/97
Page
25
NOTES
Page 26
Document # 50079 Rev. D
05/23/97
NOTES
Document # 50079
Rev. D
05/23/97
Page
27
Limited Warranty
Fire-Lite® warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service.
Products are date stamped at time of manufacture. The sole and exclusive obligation
of Fire-Lite® is to repair or replace, at its option, free of charge for parts and labor,
any part which is defective in materials or workmanship under normal use and service.
For products not under Fire-Lite® manufacturing date-stamp control, the warranty is
eighteen (18) months from date of original purchase by Fire-Lite®'s distributor unless
the installation instructions or catalog sets forth a shorter period, in which case the
shorter period shall apply. This warranty is void if the product is altered, repaired or
serviced by anyone other than Fire-Lite® or its authorized distributors or if there is a
failure to maintain the products and systems in which they operate in a proper and
workable manner. In case of defect, secure a Return Material Authorization form
from our customer service department. Return product, transportation prepaid, to
Fire-Lite®, 12 Clintonville Road, Northford, Connecticut 06472-1653.
This writing constitutes the only warranty made by Fire-Lite® with respect to its
products. Fire-Lite® does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they
are installed or intended. Buyer acknowledges that Fire-Lite® is not an insurer and
assumes no risk for loss or damages or the cost of any inconvenience, transportation,
damage, misuse, abuse, accident or similar incident.
Fire-Lite ® GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR
OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. UNDER NO CIRCUMSTANCES SHALL Fire-Lite® BE LIABLE FOR ANY
LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL OR
CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE
Fire-Lite® PRODUCTS. FURTHERMORE, Fire-Lite® SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF,
OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by FireLite®. No increase or alteration, written or verbal, of the obligation of this warranty is
authorized.
"Fire-Lite" is a registered trademark.
12 Clintonville Road, Northford, CT 06472
Phone: (203) 484-7161
FAX: (203) 484-7118
Technical Publishing
Document WARFBG-C.PM6 04/02/96