Survey
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
Type LGPG111 Digital Integrated Generator Protection Relay Features ● An optimum mix of generator protection functions ● Applicable to a wide range of generators ● User configurable scheme logic ● An alternative setting group ● Wide operative frequency range ● Display of measured values ● Fault, event and disturbance recording ● Integral testing to aid commissioning ● Remote serial communications ● Power-on diagnostics and selfmonitoring ● Eight optically isolated logic inputs for monitoring external plant. Introduction The LGPG111 is a multi-function relay which integrates a number of common generator protection functions and associated scheme logic into a single relay case. Models Available LGPG111 Incorporating 14 separate generator protection functions (see Figure 2). 2 Figure 1: Relay Type LGPG111 Application The LGPG111 can be applied to a wide range of generators. Each of its protection functions can be enabled or disabled to suit individual requirements. This approach avoids the need for application-specific relay versions, and simplifies the tasks of relay specification, evaluation and project planning. The integrated scheme logic eliminates much panel engineering work by reducing the need for auxiliary relays and associated external wiring. Contacts from external protection and plant monitoring equipment can be connected to any of the eight optically-isolated inputs. This allows external information to be incorporated into the relay’s userconfigurable scheme logic. The optically-isolated inputs and relay outputs may be labelled in the software for local or remote monitoring. These functions can be recorded in the alarm and event recording facilities. The protection functions provided by the LGPG111 relay are as shown in Figure 2. Functions Generator differential (87G) The generator differential function is for the protection of phase to phase or three-phase stator windings faults which normally involve high fault currents, so that fast fault clearance is required. This function works on a per phase basis and has a dual slope bias characteristic as shown in Figure 3: the lower slope provides sensitivity for internal faults, whereas the higher slope provides stability under through fault conditions, especially if the generator CTs saturate. Stator earth fault (51N) The stator earth fault function is current operated and can be typically set to cover up to 95% of the stator windings. It is generally used on resistively earthed generators, but can also be used to respond to current in the secondary circuit of an earthing transformer loaded with a resistor. A time-delayed low set element and an instantaneous high set element are provided. Neutral displacement (59N) The neutral displacement function is voltage operated and is used for detecting stator winding earth faults on generators which are earthed via a distribution transformer. Two timer output elements are provided. Sensitive directional earth fault (67N) When two or more generators are connected in parallel directly to a busbar, the sensitive directional earth fault function is used to discriminate between internal and external earth faults. A dedicated single-phase CT input is available for the operating current, which can accept the residual current from three line CTs or current from a dedicated core-balance CT. The polarising signal for the directional decision is either the voltage signal applied to the neutral voltage VT input or the current signal applied to the stator earth fault current input. The stator earth fault, neutral displacement and sensitive directional earth fault functions all have third harmonic rejection built in by means of a software filter. Voltage dependent overcurrent (51V) The voltage dependent overcurrent function is used for system backup protection and can trip the generator circuit breaker, if a fault has not been cleared by other protection after a certain period of time. The voltage dependent function can be either voltage controlled or voltage restrained. When voltage controlled, the timing characteristic is changed from a load to a fault characteristic when the voltage drops below a set level. It is mainly used for generators connected directly to the busbar. 87G Generator differential 51N 59N Stator earth fault Neutral displacement 67N Sensitive directional earth fault 51V 32R Voltage dependent overcurrent Reverse power 32L 46 Low forward power Negative phase sequence 40 Field failure 27 59 Under voltage Over voltage 81U 81O Under frequency Over frequency 60 Voltage balance 60 27 59 81U 81O 32R 32L 40 87G 51V 67N 46 51N 59N Figure 2: Protection functions provided by LGPG111 Differential current Trip Is1 Percentage bias K2 Percentage bias K1 No Trip Is2 Maximum mean bias current Figure 3: Generator differential bias characteristic Current pick-up level I> Current pick-up level I> KI> KI> Vs Voltage level Vs2 Voltage controlled mode Vs1 Voltage level Voltage restrained mode Figure 4: Voltage dependent overcurrent functions When voltage restrained, the current pick-up level is proportionally lowered as the voltage falls below a set value, producing a continuous variation of timing characteristics. This is applicable to generators connected to the busbar, each via a step-up transformer. A voltage vector compensation feature is also available to determine the HV phase-phase voltage signals where a Yd1 or a Yd11 step-up transformer is used. The timing characteristic can either be definite time or IDMT. The effects of the voltage level on the current pick-up level for both functions are shown in Figure 4. 3 Reverse power (32R) and low forward power (32L) Reverse power protection is used to detect loss of the prime mover. Low forward power protection can be applied to steam turbine generators where sequential shutdown is preferable, under less urgent operations, to avoid over-speeding. Both are balanced conditions, therefore a single phase measurement is sufficient. For this function, the relay calculates VIcosθ for the A-phase. In order to provide the required sensitivity, a special current input is used for both of these functions. A compensation angle setting is also available to compensate for phase error of the generator’s CT and VT signals. A delayed drop-off timer is included in the timing logic which acts as an integrating timer. This allows the relay to trip within the predetermined time delay, under pulsating power conditions. t tMAX K tmin I2>> I2 Figure 5: Negative phase sequence tripping characteristic X R –Xa Negative phase sequence (46) Negative phase sequence function is for the detection of sustained unbalanced load conditions. Under such circumstances double frequency eddy currents are induced in the rotor of a generator and can cause rapid overheating. The function has a thermal replica curve which simulates the effects of pre-fault heating due to low levels of standing negative phase sequence current I2. When the I2 value is well above threshold, the thermal replica approximates to a t = K/I22 characteristic, where K is the generator’s per-unit current thermal capacity constant in seconds. The tripping characteristic is shown in Figure 5. When high values of K are selected and the negative phase sequence currents measured are near to the threshold, the operating time may be too slow. In this case, a maximum time setting tMAX is available to provide a safe trip time. When I2 is high, the operating time may become too fast and cause loss of discrimination with other power system protection under fault conditions. To reduce this risk, the inverse characteristic is provided with 4 Xb Figure 6: Field failure protection characteristic an adjustable minimum operating time setting tMIN. A separate thermal capacity constant setting Kreset is also provided for use when the generator is cooling, due to a reduction in I2. This is to cater for rotor components with differing cooling time constants. An independent alarm element with a definite time output is available for pre-trip warning purposes. Field failure (40) Severe loss of excitation caused by field failure can cause a high value of reactive current to be drawn from the power system which can endanger the generator. The field failure protection provided by this relay is a single phase impedance measuring element with an offset mho characteristic, as shown in Figure 6. An integrating timing arrangement, identical to that for the power functions, is also provided. This allows the relay to trip within the predetermined time delay even though the impedance measurement may temporarily fall outside the mho characteristic, eg. under pole-slipping conditions. Under voltage (27) and over voltage (59) An under voltage element and a 2-stage over voltage element are provided. They are primarily used for backing up the speed control governor and the automatic voltage regulator. When severe over voltage occurs, the high set of the over voltage element can be set to provide fast operation. Both elements are 3phase devices. Under frequency (81U) and over frequency (81O) Two under frequency elements and one over frequency element are provided. The underfrequency elements are used to detect overloading of the generator caused by various system disturbances or operating conditions. The overfrequency element is used to back-up the speed control governor if overspeeding occurs. Voltage balance (60) The voltage balance function is provided to detect VT fuse failure. It compares the secondary voltages of two sets of VTs (or from two separately fused circuits of a single VT) and can be used to block possible incorrect tripping of those protection functions whose performance may be affected by the apparent loss of voltage such as when a VT fuse ruptures. Configuration Integrating timer facility Time integration is required for the power function to allow for reciprocating load conditions where the measuring element may pick up briefly and periodically. The same feature is also provided for the field failure function for pole-slipping conditions. Time integration allows the function to operate within its predetermined operating time. To implement timing integration, an additional delayed drop-off timer is provided. Once the protection measurement element has picked up, the relay will operate after the set time delay, provided that the time interval when the element drops off is within the setting of the delayed drop-off timer tDO. The protection scheme logic for a generator set normally involves a large number of protection functions combined together to drive a few common trip outputs. Some blocking and interlocking logic may also be required. In order to accommodate different generator applications, the scheme logic is flexible and reconfigureable. The LGPG111 scheme logic is in the form of logic arrays with an architecture commonly found in programmable logic array devices, having an internal AND-OR structure shown in Figure 7. The OR functions allow one or more of the AND function outputs to control each output relay, whilst the AND functions provide blocking or interlocking for two or more inputs, or just a through connection for one input. There are 32 inputs to the scheme logic: 19 from the protection functions, 8 optically-isolated inputs and a selection of inverted inputs to allow blocking logic to be created. The scheme logic controls a total of 15 output relays and has 32 selectable AND functions. Frequency tracking The relay tracks the power system frequency and continuously adjusts its internal sampling clock to exact multiples of the system frequency. This provides correct measurements and operation of the protection functions during start-up and run-down of the generator set when the generator unit is operated at abnormal frequency. The operating frequency range is from 25Hz to 70Hz for the differential function and from 5Hz to 70Hz for the other protection functions. The input and output matrices allow the desired connections to be created. Each intersection of the matrix represents a programmable interconnection. By designing the appropriate interconnections and then entering the information into the relay, Timer held facility Both the overcurrent function, the low set element of the stator earth fault function and the neutral displacement function are provided with a timer held facility. The purpose is to enable faster clearance of recurrent intermittent faults, for example, selfsealing insulation faults. This facility allows the relay timer to hold its value when the current drops off, provided that the drop-off period is less than the tRESET timer setting. This adjustable reset facility also enables closer co-ordination with electromechanical induction disc relays. Scheme logic From protection elements and status inputs Output matrix AND AND AND Input matrix OR OR OR To output relays Figure 7: Block diagram of the scheme logic 5 through the scheme logic settings, the required tripping logic can be configured. The presence of the optically-isolated inputs to the scheme allows external devices such as rotor earth fault relay, temperature sensing devices and mechanical relays to be connected to the scheme, so that the tripping facilities, together with the alarm and remote communication facilities, can be utilised. The optically-isolated inputs and relay outputs used in a scheme may be allocated to any function required by the application. The relay has a facility to label each of these by providing an identifier. The identifiers are used during the configuration of the scheme logic, by the input and output status displays and by the event, fault and disturbance recording systems. Alternative setting group The relay provides an alternative setting group which consists of all the protection and scheme logic settings. It can be used during start-up or rundown of generators or during changes in power system configuration. This setting group can be selected by either energising the appropriate optically-isolated inputs, or via the relay settings menu. Ancillary Functions Measurements The magnitudes of all 17 analogue inputs to the relay are available for display. Other derived quantities are also available. This provides such information as the three-phase, residual and earth currents, the phase to phase voltages, differential and bias currents, negative phase sequence current, phase A active and reactive power plus the phase angle and power system frequency. All measurements can be displayed in either primary or secondary quantities, selectable by the user. Primary display quantities are based on the settings for the CT and VT ratios used by the relay. Event and fault records Up to 100 event records are available, all of them stored in nonvolatile memory. The latest record will automatically overwrite the oldest one. Event records are generated whenever there is a protection function operation, energisation of a status input, operation of an output relay or any hardware failure. Fault records are also stored as events. Out of the 100 event records, up to 50 fault records can be accommodated. Fault records are initiated when user selected relay outputs operate. The record consists of the date and time of the fault, the state of the optically-isolated inputs, relay outputs and protection functions, together with the measurement values during the fault. Disturbance records The internal disturbance recorder can store up to eight analogue channels, together with all the status input and relay output information. The analogue channels are user selectable from the relay’s 17 inputs. The data in the analogue channels can be stored as either raw data or as magnitude and phase data. The raw data is sampled at 12 samples per electrical cycle, whereas the magnitude and phase data are calculated once every 20ms. Thus the duration of a record varies with the data type. For raw data, the duration 6 is 64 electrical cycles, but for magnitude and phase data, the duration is 7.68s. The latter set-up allows long duration events such as pole-slipping to be captured. In either case, each data entry is time stamped. This is particularly useful for the raw data recording, since the sampling interval varies with the power system frequency, due to the frequency tracking. The disturbance recorder can be triggered from selected relay outputs and status inputs. A maximum of two records can be stored in volatile memory. A record remains in the buffer area until it is uploaded to a PC, after which the buffer is released. If the two buffers are full, no further recording can be made. Time synchronisation The clock for event record time tagging has a resolution of 1ms. To provide time synchronisation with other equipment in the generator station, the clock can be synchronised by external clock pulses (0.5, 1, 5, 10, 15, 30 or 60 minute period) from an optically-isolated input. Print functions Several print functions are provided to allow the relay to provide hard-copy documentation, via the front panel parallel port. This consists of the system settings, protection settings, scheme logic settings, event records and fault records. The scheme logic print-out is formatted so that it can be compared directly with the scheme logic diagram. Test features A number of features are provided to enable the relay to be thoroughly tested during commissioning, routine maintenance and fault finding operations: ● The measurement functions allow the analogue input and its associated wiring to be checked. ● Display the on/off states of the status inputs and relay outputs. ● Testing the four indicating LEDs. ● Testing the relay outputs and their associated circuits by operating the relay output contacts. ● Display the operation of each protection function as a percentage of the time-to-trip. This allows the pick-up, progress and operation of each protection function to be checked. ● Testing the set-up of the scheme logic settings by manually entering an input pattern to the scheme, and then examining its logical output. This test can be performed at any time without interfering with the relay’s operation. Power-on diagnostics and self monitoring Power-on diagnostic tests are carried out by the relay when it is energised. These tests include checks on the timer, microprocessor, memory and the analogue input module. Continuous self-monitoring, in the form of watchdog circuitry, memory checks and analogue input module tests, is also performed. In the event of a failure, the relay will either lock-out or attempt a recovery, depending on the type of failure detected. Hardware Description Two relay output modules are provided; each module contains 8 miniature relays. All relays are selfreset. However, a software function is available which allows the user to select outputs to be latched when operated. The relay is housed in a 4U (178mm) high case suitable for either rack or panel mounting. Internally, it consists of a number of plug-in modules which are individually tested and calibrated. The modular hardware architecture is shown in Figure 8. The front panel consists of a 2 x 16 character alphanumeric liquid crystal display (lcd) and a 7 push-button keypad. It provides local access to all of the relay’s features. There are also 4 light emitting diodes for visual indication of the relay’s status, a nonisolated IEC870 serial port for connection to a PC, and a parallel port for connection to a printer. The microcomputer module consists of a powerful 16-bit microcomputer which controls all of the subsidiary modules through a 64-way ribbon cable called the I/O Bus. The processor performs all of the major software functions such as input signal processing, protection algorithms, scheme logic, relay output controls and handling of the operator interface. At the rear of the relay, apart from the normal DC supply and plant connections, there is an isolated IEC870 port and a K-Bus port for permanent connection to a remote PC. The analogue input module consists of 12 CTs, 5 VTs and 6 optically-isolated inputs. The CTs and VTs are used to isolate and condition the analogue inputs from the main transformers connected to the generator. Their output signals are then converted into digital data for further processing. The remote communications module is responsible for handling the communications protocol and for controlling the three communication ports. In addition to the 6 optically-isolated inputs on the analogue module, a further 8 are provided by the status input module, making a total of 14 optically-isolated inputs available to the relay. 6 of these have pre-defined functions, such as clock synchronisation, setting group selection, etc., which leaves 8 inputs to be fed into the scheme logic. All of the optically-isolated inputs operate from an auxiliary supply Vx(2), which is independent of the main auxiliary supply Vx(1). The ratings of Vx(1) and Vx(2) may be different (See Technical Data). Microcomputer I/O bus Power supply Relay outputs Remote comms Status input Analogue inputs Front panel Figure 8: Hardware architecture 7 User Interface Front panel user interface The features of the relay can be accessed through a user-friendly menu system. The menu is arranged so that related items (menu cells) are grouped into individual sections, each of which is identified by a title. The user navigates around the menu by using the arrow keys, first to select a particular section title and then to select an item within it. The front panel liquid crystal display is limited to displaying one menu cell at a time. Software is available with each KITZ to provide access to the relays, to read and change settings. Additional software entitled Protection Access Software and Toolkit is available to give access to the event recorder, together with other additional functions. Each relay is directly addressable via the bus to allow communication with the PC. It should be noted that protection tripping and blocking signals are not routed via the K-Bus. Separate conventional wiring is used for these functions. Remote access user interface The menu can be accessed via the remote communications facility. This allows all of the menu cells in a section to be displayed on the screen of a PC. Changes to the menu cell can be made from the PC keyboard. Relay interconnection Three communication ports are available: the front panel, nonisolated IEC870 port; the rear, isolated IEC870 port; and the K-Bus port. The IEC870 ports use RS232 signal levels and allow point-to-point connection. It is applicable when networking is not required or during commissioning. Alternatively, the relays can be connected via a shielded, twisted pair called K-Bus. Up to 32 relays may be connected in parallel to the bus. K-Bus can be connected through a protocol converter, type KITZ, either directly or via a modem, to the RS232 port of a PC. K-Bus is RS485 based and runs at 64kbits/s. The K-Bus connection is shown in Figure 9. SK1 Figure 9: K-Bus terminals connection arrangement 8 27 and 81U inhibit 51V timer inhibit 51N timer inhibit B25 A7 B26 Vab I —residual A8 A23 B27 Ia—diff A24 A25 B23 A26 A27 G5 A28 A17 G1 Ia—bias G3 A18 A19 A22 A9 Ia—sensitive Setting group select (Part) Integrated Generator Protection Relay G2 G8 Clock synchronising A10 A11 G10 A12 A13 G13 Ib A14 A15 Ic A16 A5 G15 G14 Logic input 10 G19 G18 Ie A6 B19 G20 B20 G23 Ve Logic input 12 G16 G17 Logic input 13 Relay 5 DC supply + Vx(1) – G21 G22 Rear IEC870 port (isolated) G25 G26 G28 9 Figure 10: External connection diagram Type LGPG111 (typical scheme) B8 B9 F8 Relay 9 F2 F7 Relay 10 Relay 7 Ia—diff, Ia—bias, Ib—diff, Ib—bias, Ic—diff, Ic—bias, 87G Generator differential Ia, Ib, Ic 51V Overcurrent 46 Negative phase sequence 40 Field failure (Ia) 81U Under frequency (Ia) 810 Over frequency (Ia) F9 F11 B10 B11 LGPG111 (Part) Integrated Generator Protection Relay Relay 11 F10 F12 Ia—sensitive 32R Reverse power 32L Low forward power F13 F15 Relay 12 F16 F19 F21 F23 Relay 14 F22 D16 D19 F24 D20 D23 F27 F25 Relay 15 F26 Ve 59N Neutral displacement 67N SDEF (polarising) 27 Under voltage 59 Over voltage 81U Under frequency 810 Over frequency 32R Reverse power (Vab) 32L Low forward power (Vab) 40 Field failure (Vab) 60 Voltage balance Vab—comp 60 Vbc—comp F28 D24 D27 51N Stator earth fault 67N SDEF (polarising) Vab, Vbc F20 D14 D15 Ie I—residual 67N SDEF (operating) Relay 13 F18 D10 D13 Voltage balance (Comparison voltages) H3 H4 D28 H13 Power supply failure alarm H5 H6 H14 Case earth Relay 6 G24 G27 F4 F17 Logic input 11 Relay 4 B6 B7 D6 D9 G12 Ia F6 Logic input 7 Logic input 9 Relay 3 B4 B5 F14 G9 G11 F1 D2 D5 Relay 2 Relay 8 F3 Logic input 6 Logic input 8 Note: CT and VT assignments F5 B2 B3 B12 D1 Relay 1 G4 G7 Phase rotation B Relay inoperative alarm G6 LGPG111 Ic—bias C B24 Vbc— comp Ic—diff A20 A21 A B21 B22 Vab — comp Ib—diff Ib—bias Setting group select A B C B28 Vbc B1 Notes: 1. (a) (b) CT shorting links make before terminals disconnect. Short terminals break before (a). 2. CT connections are typical only. 3. SCN = Screen connection for K-Bus. 2 TX 3 RX 1 7 signal ground 1 protective ground K-Bus port 2 SCN 4. The IEC870 port at the front panel is non-isolated and has different connection arrangements. 5. Frequency tracking on Vab, Vbc and Ia only. 6. Logic inputs are rated at Vx(2). 7. SDEF = Sensitive directional earth fault. 10 Input 13 Input 12 Input 11 Input 10 Input 9 –Input 9 Input 8 –Input 8 Input 7 –Input 7 Input 6 –Input 6 60 VB Comp –60 VB–Prot (Blocking) 60 VB–Prot 40 Field Failure 67N Sensitive Dir EF 59N–2 Neutral Disp 59N–1 Neutral Disp 51N>> Stator EF 51N> Stator EF 46>> NPS Trip 46> NPS Alarm 59 Over Voltage 27 Under Voltage 81U–2 Under Freq 81U–1 Under Freq 81O Over Freq 32L Low Forward Power 32R Reverse Power 51V Over Current 87G Generator Diff Logic 0 Logic 1 Logic 2 Logic 3 Logic 4 Logic 5 Logic 6 Logic 7 Logic 8 Logic 9 Logic 10 Logic 11 Logic 12 Logic 13 Logic 14 Logic 15 Logic 16 Logic 17 Logic 18 Logic 19 Logic 20 Logic 21 Logic 22 Logic 23 Logic 24 Logic 25 Logic 26 Logic 27 Logic 28 Logic 29 Logic 30 Logic 31 Ouput Matrix & & & & & & & & & & & & & & & & & & & & & & & & & & & & & & & & Input Matrix EN 8ms pick-up, 8ms drop-off Relays 3, 11 2ms pick-up, 2ms drop-off Relays 4, 5, 6, 7, 12, 13, 14, 15 2ms pick-up, 8ms drop-off Figure 11: Type LGPG111 scheme logic Relay 1 Relay 2 Relay 3 Relay 4 Relay 5 Relay 6 Relay 7 Relays 1, 2, 8, 9, 10 Relay 8 Relay 9 Relay 10 Relay 11 Relay 12 Relay 13 Relay 14 Relay 15 Output Inhibited Note: Speed of the relay outputs are: EN Technical Data Ratings Inputs AC Current In 1A or 5A AC Voltage Vn 100V to 120V Auxiliary voltage Vx(1) (Relay power supply) Auxiliary voltage Vx(2) (Optically isolated status input supply) Nominal dc (V) 24/27 30/34 48/54 110/125 220/250 Operative range (V) 19.2 – 32.4 24 – 40.8 38.4 – 64.8 88 – 150 176 – 300 24/27 30/34 48/54 110/125 220/250 19.2 – 32.4 24 – 40.8 38.4 – 64.8 88 – 150 176 – 300 Note: Vx(2) may be different from Vx(1) Frequency Fn 50/60Hz Burdens AC Current Generator differential <0.05VA per input at In (for 1A relay) <0.20VA per input at In (for 5A relay) Voltage dependent overcurrent, field failure and negative phase sequence Reverse and low forward power Stator earth fault and sensitive directional earth fault <0.05VA per input at In (for 1A relay) <0.22VA per input at In (for 5A relay) <0.15VA at In (for 1A relay) <0.30VA at In (for 5A relay) <0.12VA per input at In (for 1A relay) <0.25VA per input at In (for 5A relay) AC Voltage <0.005VA per input at Vn DC auxiliary voltage (Vx(1)) DC auxiliary voltage (Vx(2)) 15W quiescent, max. 34W operating. Less than 0.32W on average per input Transformer ratios CT ratios 1:1 to 9999:1 in 0.01 steps VT ratios 1:1 to 9999:1 in 0.01 steps CT requirements Generator differential Biased differential settings at Is1=0.05In, k1=0%, Is2=1.2In, k2=150% Vk ≥ 50In (Rct + 2RL + Rr) where maximum through fault current = 10 x In and maximum X/R = 120 Vk ≥ 30In (Rct + 2RL + Rr) where maximum through fault current = 10 x In and maximum X/R = 60 Note: Minimum knee point voltage = 34V 11 Earth fault protection functions Sensitive directional earth fault, using three residually connected line CTs Vk ≥ 6In (Rct + 2RL + Rr) where maximum X/R = 5 and maximum earth fault current = 1 x In Sensitive directional earth fault, using core balance CT Vk ≥ 6NIn (Rct + 2RL + Rr) where maximum X/R = 5 and maximum earth fault current = 2 x In Stator earth fault Vk ≥ 6NIn (Rct + 2RL + Rr) Ancillary protection functions Voltage dependent overcurrent, field failure and negative phase sequence Vk ≥ 20In (Rct + 2RL + Rr) where Vk = Minimum current transformer knee-point voltage for stability In = Relay rated current (1A or 5A) Rct = Resistance of current transformer secondary winding (Ω) RL = Resistance of a single lead from relay to current transformer (Ω) Rr = Resistance of any other protection functions sharing the current transformer (Ω) N = Maximum earth fault current Core balanced CT or earth CT rated primary current Note: N should not be greater than 2. The core balance CT or earth CT ratio must be selected accordingly. Power function For settings >3% Pn Use correctly loaded class 5P protection CT For settings ≤3% Pn Use metering class CT. See table below. Metering CT class recommended for power setting less than 3%Pn Reverse/low forward Power Setting (%Pn) 0.2 0.4 Metering CT Class 0.1 0.6 0.8 1.0 0.2 1.2 1.4 1.6 1.8 2.0 0.5 2.2 2.4 2.6 2.8 3.0 12 1.0 Thermal withstand Continuous withstand CT input 4 x In VT input 400V CT input 100A for 1s (In = 1A) Short time withstand 400A for 1s (In = 5A) Setting ranges Generator differential Basic differential current setting Is1 0.05In to 0.1In in 0.01In steps Threshold for increase bias Is2 1In to 5In in 0.1In steps Bias K1 (Ibias < Is2) 0% to 20% in 5% steps Bias K2 (Ibias > Is2) 10% to 150% in 10% steps Stator earth fault Low set element: Characteristic Standard inverse/Definite time Current setting Ie> 0.005In to 0.5In in 0.005In steps Time multiplier setting TMS 0.05 to 1.2 in 0.05 steps IDMT Operating characteristic t= Definite time setting t> 0.1s to 10s in 0.1s steps Reset timer setting tRESET 0s to 60s in 1s steps 0.14 x TMS (I/Ie>)0.02–1 High set element: Current setting Ie>> 0.005In to 2In in 0.005In steps Time setting t>> 0s to 5s in 0.1s steps Neutral displacement Voltage setting Ve> 1V to 25V in 1V steps Timer 1 setting t1 0.5s to 5s in 0.5s steps Timer 2 setting t2 1s to 10s in 1s steps Timer 2’s reset timer t2RESET 0s to 60s in 1s steps Sensitive directional earth fault Operating current Ires> 0.005In to 0.02In in 0.005In steps Polarising voltage Vp> 1V to 10V in 1V steps Polarising current Ip> 0.005In to 0.02In in 0.005In steps Relay characteristic angle RCA –95° to 95° in 1° steps Voltage dependent overcurrent Functions Voltage controlled/Voltage restrained/Simple Characteristic Standard Inverse/Definite Time Current setting I> 0.5In to 2.4In in 0.05In steps Time multiplier TMS 0.05 to 1.2 in 0.05 steps IDMT Operating characteristic t= Definite time setting t 0s to 10s in 0.1s steps Reset timer setting tRESET 0s to 60s in 1s steps 0.14 (I/I>)0.02–1 x TMS 13 Voltage settings: Vs (for voltage controlled) 20V to 120V in 1V steps Vs1 (for voltage restrained) 80V to 120V in 1V steps Vs2 (for voltage restrainted) 20V to 80V in 1V steps K factor 0.25 to 1.00 in 0.05 steps Voltage vector rotate None or Yd Current pick-up level Voltage Controlled Voltage Restrained I> for V> Vs I> KI> for V≤ Vs KI> + for V > Vs1 I> – KI> (V – VS2) VS1 – VS2 KI> for Vs1≥ V ≥ Vs2 for V < Vs2 Reverse power Power setting –P> 0.2W to 8W in 0.05W steps (for 1A relay) 1W to 40W in 0.25W steps (for 5A relay) Delayed pick-up timer t 0.5s to 10s in 0.5s steps Delayed drop-off timer tDO 0s to 5s in 0.1s steps Low forward power Power setting P< 0.2W to 8W in 0.05W steps (for 1A relay) 1W to 40W in 0.25W steps (for 5A relay) Delayed pick-up timer t 0.5s to 10s in 0.5s steps Delayed drop-off timer tDO 0s to 5s in 0.1s steps Compensation angle θcomp (for both reverse and low forward power) –5° to +5° in 0.1° steps Note: The power settings are single phase quantities. Negative phase sequence trip element Trip threshold setting I2>> 0.05In to 0.5In in 0.01In steps Thermal capacity constant (heating) K 2s to 40s in 1s steps Thermal capacity constant (cooling) Kreset 2s to 60s in 1s steps 2 Operating Characteristic (under no pre-heating condition) t=– Maximum operating time tmax 500s to 2000s in 10s steps Minimum operating time tmin 0.25s to 40s in 0.25s steps K I >> loge 1– 2 I2>>2 I2 Negative phase sequence alarm element 14 Alarm threshold I2> 0.03In to 0.5In in 0.01In steps Alarm timer setting t> 2s to 60s in 1s steps Field failure Mho offset –Xa 2.5Ω to 25Ω in 0.5Ω steps (for 1A relays) 0.5Ω to 5Ω in 0.1Ω steps (for 5A relays) Mho diameter Xb 25Ω to 250Ω in 1Ω steps (for 1A relays) 5Ω to 50Ω in 0.2Ω steps (for 5A relays) Delayed pick-up timer t 0s to 25s in 0.1s steps Delayed drop-off timer tDO 0s to 5s in 0.1s steps Under voltage Voltage setting V< 30V to 110V in 1V steps Timer setting t 0.1s to 10s in 0.1s steps Over voltage Voltage settings V> ,V>> 105V to 185V in 1V steps Timer settings t>, t>> 0s to 10s in 0.1s steps Under frequency Frequency settings F1< ,F2< 40Hz to 65Hz in 0.05Hz steps Timer settings t1, t2 0.1s to 25s in 0.1s steps Over frequency Frequency settings F> 40Hz to 65Hz in 0.05Hz steps Timer settings t 0.1s to 25s in 0.1s steps Voltage balance Voltage setting Vs 5V to 20V in 1V steps Digital Inputs Optically isolated inputs 14 (6 dedicated, 8 available to the scheme logic) Contacts Output relays 10 dual make 2 single make 3 change-over Power supply failure alarm 1 single make 1 single break Relay inoperative alarm 1 change-over Contact rating Make: 30A and carry for 0.2s Carry: 5A continuous Break: dc 50W resistive 25W inductive (L/R = 0.4s) ac 1250VA Subject to maxima of 5A and 300V Durability Loaded contact 10,000 operations Unloaded contact 100,000 operations 15 Communications Language Courier IEC870 port (front/rear) Transmission mode Signal levels Message format Data rate Connection Cable type Cable length Connector Isolation Asynchronous RS232 IEC870 FT1.2 600 – 19200 bits/s Single-ended Screened multi-core 15m 25-way D-type female Front (non-isolated) Rear (1kV rms for 1 minute to case earth and other circuits) K-Bus port Transmission mode Signal levels Message format Data rate Connection Cable type Cable length Connector Isolation Synchronous RS485 HDLC 64 kbits/s Multidrop (32 units) Screened twisted pair 1000m Screw terminals 2kV rms for 1 minute Voltage withstand Dielectric withstand IEC255-5: 1977 Impulse voltage IEC255-5: 1977 Insulation resistance IEC255-5: 1977 2.0kVrms for 1 minute between all terminals and case earth 2.0kVrms for 1 minute between terminals of independent circuits, including contact circuits 1.0kVrms for 1 minute across open contacts of output relays 1.0kVrms for 1 minute between IEC870 rear port and earth 5kV peak, 1.2/50µs, 0.5J between all terminals and all terminals to case earth >100MΩ Electrical environment DC supply interruptions IEC255-11: 1979 AC ripple on DC supply IEC255-11: 1979 High frequency disturbance IEC255-22-1: 1988 16 The relay shall withstand a 10ms interrupt without de-energising The relay will withstand 12% ripple 2.5kV first peak between independent circuits and case 1.0kV first peak across terminals of the same circuit. No additional tolerances are required for the operating time or the relay’s thresholds Electrostatic discharge test IEC255-22-2: 1989 Fast transient disturbance IEC255-22-4: 1992 Class III (8kV) – air discharge Level 3 (6kV) – point contact discharge (IEC801–2: 1991) No additional tolerances are required for the operating time or the relay’s thresholds Class IV (4kV, 2.5kHz) Class III (2kV, 5kHz) No additional tolerances are required for the operating time or the relay’s thresholds Radio frequency interference Radiated immunity IEC255-22-3: 1989 Class III field strength 10V/m Extended frequency range 20MHz to 1000MHz Conducted immunity IEC801-6: 1994 10V rms, 0.15MHz to 80MHz Radiated emissions EN55022: 1994 Class A Conducted emissions EN55022: 1994 Class A EMC compliance 89/336/EEC EN50081-2: 1994 EN50082-2: 1995 Product safety 73/23/EEC EN 61010-1: 1993/A2: 1995 EN 60950: 1992/A3: 1995 Compliance with the European Commission Directive on EMC is claimed via the Technical Construction File route. Generic Standards were used to establish conformity Compliance with the European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards. Atmospheric environment Temperature IEC255-6: 1988 Humidity IEC68-2-3: 1969 Enclosure protection IEC529: 1989 Storage and transit -–25°C to +70°C Operating –25°C to +55°C 56 days at 93% relative humidity at 40°C. IP50 (dust protected) Mechanical environment Vibration IEC255-21-1: 1988 Vibration response Class 2 Vibration endurance Class 2 Shock and bump IEC255-21-2: 1988 Shock response Class 2 Shock withstand Class 2 Bump Class 1 Seismic IEC255-21-3: 1993 Class 2 17 Case The relay is housed in a multi-module MIDOS case as shown in Figure 12. Additional Information LGPG111 Service Manual R5942 Courier Communications leaflet R4113 Information Required with Order Unit type: LGPG111 01 S Case mounting Flush panel Rack 1 2 Vx(1) auxiliary voltage 24V 30V 48V 110V 220V 1 2 3 4 5 Vx(2) auxiliary voltage 24V 30V 48V 110V 220V 1 2 3 4 5 CT rating 1A 5A L M Language English French German Spanish 18 E F G S 483mm Rack details Dimensions to IEC 297 Rack mounting 7 max. 438 31.75 ±0.4 12.7 ±0.4 Removable cover 432 450 min. Hinged front panel Push button projection 10mm max. U Scale U = 44.45 465.1 ±1.6 Tolerance between any two holes within a distance of 1mm ±0.4 10 178 101.6 10 465 483 252 37 Side Front Allow a minimum of 50mm for terminal block and wiring 10.6 7 Fixing hole detail All dimensions in mm Terminal screws: M4 x 8 brass Cheese Head with Lockwashers are provided Panel mounting Mounting screws are not provided 438 Panel cut-out detail 400 200 Removable cover 432 Hinged front panel Push button projection 10mm max. 180.5 191 10 440 178 201 Fixing holes Ø5.4 10 443 Front 37 252 Side Allow a minimum of 50mm for terminal block and wiring Figure 12: Case outlines 19