Survey
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
Heat Transfer Shubber Jawad Heat Transfer The original purpose of a building is to provide shelter and to maintain a comfortable or at least liveable internal temperature. Other purposes include security, privacy and protection from wind and weather. To feel comfortable in a thermal sense, a human has to be able to release a well-defined amount of Heat. If this gets difficult, a person will either feel cold or hot. The human body operates as a chemical reactor that converts chemical energy of food and respiratory oxygen into mechanical work and heat. Heat output can vary from about 100 W for a sedentary person to 1000 W for an exercising person. To maintain body temperature within a narrow band, the heat produced by an occupant must be released to the indoor environment. If too much heat is lost, room temperature should be increased or warmer clothes be worn. The heat transfer on the human skin, the indoor temperature and the heat transfer through the building envelope are factors that influence thermal comfort. Heat Loss of a Building According to the Second Law of Thermodynamics, heat transfer is only possible in the direction from a higher temperature to a lower one. It becomes zero if temperatures are equal. The heat loss through an envelope should therefore be proportional to the difference (Tinside – Toutside), or to a positive power of it for small differences. For a simple formula, a linear dependence on temperature difference is sufficient. Accepting further that heat loss grows linearly with surface area A, one finds: q= AU (Tinside – Toutside) The constant of proportionality, U, is the Overall Heat Transfer Coefficient in W/(m2K). The equation above suggests three ways to reduce heat loss: 1) As the heat loss is proportional to the inside-outside temperature difference, the set-point for the indoor temperature can be reduced during the heating season; 2) The insulation of the envelope can be improved to reduce the overall heat transfer coefficient U; and 1 Heat Transfer Shubber Jawad 3) If possible, the surface area should be reduced without changing the enclosed volume. A spherical igloo would be optimal, but a cubical shape is still better than an elongated building with many wings. The opposite is true for the design of heat exchanger surfaces or fin-tubes, where the effective surface should be maximized. Modes of Transport Heat In building heat transfer, many different types of energy transport are effective. Often, heat is transported by different modes to or from the same place. Energy that reaches a point via different paths and modes may be added up for the heat balance. For instance, the heat loss of a human body is the sum of convection, radiation, and latent heat released by sweating and so forth. Primary heat transport modes are: Conduction: In Conduction, heat transfer takes place due to a temperature difference in a body or between bodies in thermal contact, without mixing of mass. Convection (heat conveyed as internal thermal energy of mass that is displaced by mean or turbulent motion); Radiation (heat transfer by electromagnetic waves such as infrared or visible light). Heat transfer through a wall can be calculated as q = U A ΔT (1) where q = heat transfer (J/s, W) U = overall heat transfer coefficient (W/m2 oC) A = wall area (m2) ΔT = (T1 - T2) = temperature difference over wall (oC). U and R-values The overall heat transfer coefficient - the U-value - describes how well a building element conducts heat or the rate of transfer of heat (in watts or Btu/hr) 2 Heat Transfer Shubber Jawad through one unit area (m2 or ft2) of a structure divided by the difference in temperature across the structure. U-value (or U-factor) is a measure of the rate of heat loss or gain through a construction of materials. The lower the U-factor, the greater the material's resistance to heat flow and the better is the insulating value. U-value is the inverse of R-value. The overall U-value of a construction consisting of several layers can be expressed as U=1/∑R (2) Where:U = heat transfer coefficient (Btu/hr ft2 oF, W/m2 oC) R = the resistance to heat flow in each layer (hr ft2 /Btu or, m2 oC /W) The R-value of the single layer can be expressed as: R=1/C=s/k (3) where C = layer conductance (Btu/hr ft2 or, W/m2 oC) k = thermal conductivity of layer material (Btu in/hr ft2 or, W/m oC) s = thickness of layer (inches, m) Note - in addition to resistance in each construction layer - there is a resistance from the inner and outer surface to the surroundings. U = 1 / Ri + R1 + R2 + R3 + ….. + Ro (4) where Ri = thermal resistivity surface inside wall (m2 oC /W). R1.. = thermal resistivity in the separate wall/construction layers (m2 oC /W). Ro = thermal resistivity surface outside wall (m2 oC /W). 3 Heat Transfer Shubber Jawad Condensation in buildings Condensation happens in buildings when warm, moist air comes into contact with cooler surfaces that are at or below the dew point, such as windows, and water condenses on those surfaces. When air cools, it is less able to 'hold' moisture, that is, the saturation water vapour density falls, and so the relative humidity rises. When the relative humidity reaches 100%, the air will be saturated. This is described as the dew point. If the air continues to cool, moisture will begin to condense. Condensation can occur on surfaces, or can be interstitial condensation occurring between the layers of the building envelope, typically as a result of air diffusing from the warm interior of the building to the cool exterior and reaching its dew point within the building fabric. This interstitial condensation, when trapped within the structure by impervious materials is often erroneously referred to as rising damp. Condensation affects the performance of buildings, causing problems such as: Mould growth which is a cause of respiratory allergies. Mildew. Staining. Slip hazards. Damage to equipment. Corrosion and decay of the building fabric. Poor performance of insulation. 4 Heat Transfer Shubber Jawad Example 1: Compute (U) value and temperature at inner at outer face for a brick wall with a thickness of (105) mm if inside air temperature is 22 ºC and outside air temperature is 2 ºC , Kbrick = 1.2 W/m ºC, Rsi = 0.123 m2 ºC /W, Rso= 0.053 m2 ºC /W. Ans. R= s / k Rbrick = = 0.0875 m2 oC /W U=1/∑R = 3.795W/m2 oC = Rate of heat loss (q) = U A ΔT A= 1m2 ΔT= (Tout-Tin) = (2-22) = -20 oC q = 3.795(1) (-20) = -75.9 W/m2 Note:- (-) sign refers to heat losing Heat at inner face of brick = -75.9 = (ΔT1) ΔT1= - 9.336 oC = (T2- T1) T2 = (-9.336+ 22) = 12.664 oC Heat at outer face of brick = -75.9 = (1) (ΔT2) ΔT2= - 6.64 oC = (T3- T 2) T3 = (-6.64+ 12.664) = 6.024 oC For checking q = -75.9 = (1) (ΔT3) ΔT3= - 4.023 oC = (T4- T 3) T4 = (- 4.023+6.024) ≈ 2 oC…………….. o.k or 5 Heat Transfer q = -75.9 = Shubber Jawad (1) (ΔT3) ΔT3 = - 4.023 oC = (T4- T 3) T4 = (- 4.023 - 2) = 6.023 oC …………….o.k Example 2: A brick wall with a thickness of 105 mm covered from inside by wooden sheet with a thickness of 25 mm, Kbrick = 1.2 W/m ºC, Kwood= 0.09 W/m ºC, Rsi = 0.123 m2 ºC /W, Rso= 0.053 m2 ºC /W. inside temperature is 22 ºC and outside temperature is 2ºC. If dew point of inside air is 5 ºC, at which position of the wall the condensation may happen? Ans. R= s / k Rbrick = = 0.0875 m2 oC /W Rwood = = 0.277 m2 oC /W U=1/∑R= 1.847 W/m2 oC = q= U A ΔT = 1.847(1) (2-22) = - 36.94 W/m2 Heat at inner face of wood = -36.94 = (ΔT1) ΔT1= -4.543 oC T2= 22 - 4.543 = 17.457 oC>5 oC no condensation will happen Heat at outer face of wood = -36.94 = (ΔT2) ΔT2 = -10.232 oC = (T3- T2) T 3 = (-10.232+17.457) = 7.22 oC >5 oC no condensation will happen Heat at outer face of brick = -36.94 = (ΔT3) ΔT3 = - 3.232 oC = (T4- T 3) T4 = (-3.232+ 7.22) = 3.987 oC < 5 oC condensation will happen 6 Heat Transfer Shubber Jawad Example 3: A building with inner air temperature of 20 oC and outer air temperature of 5 oC has a wall with area of 20 m2 consist of the following layer: 1- Outer layer of brick with a thickness of 120 mm and K= 0.84 W/m ºC. 2- Insulating layer with a thickness of 50 mm and K= 0.026 W/m ºC. 3- Inner layer of brick with a thickness of 120 mm and K= 0.84 W/m ºC. 4- Inner finishing layer of plaster with a thickness of 10 mm and K=0.5 W/m ºC. If Rsi = 0.123 m2 ºC /W and Rso= 0.055 m2 ºC /W, compute the following:A- The value of heat transferred for each 1 m2 of wall, gain or loss in heat will happen for the building? B- The temperature of inner face for inner brick layer. C- Insulating layer thickness required to reduce transferred heat to a quarter of its value. Ans. R= s / k R brick = = 0.142 m2 oC /W = 1.923 m2 oC/W R insulating = R plaster = = 0.02 m2 oC/W U=1/∑R= 0.415 W/m2 oC = 1- q= U A ΔT = 0.415(1)(5-20) = - 6.225 W/m2 (-) sign refers to heat losing 2- q = -6.225 = (1)(T2-T1) (T2-20) Heat at inner face of plaster (T2) = 19.23 oC 7 Heat Transfer q= (1) (T3-T2) -6.225 = (1) (T3- 19.23) Shubber Jawad The temperature of inner face for inner brick layer (T3) = 19.1 oC 3- = 1.556 Watt/m2 (heat transferred to a quarter) q = U (A) (Tout-Tin ) = 1.556 = U (1) (5-20) U = 0.1037 = R insulating= 9.155 W/m2 oC 9.155 = t = 0.238 m = 238 mm Thermal Comfort in Buildings BS EN ISO 7730 defines thermal comfort as '…that condition of mind which expresses satisfaction with the thermal environment', i.e. the condition when someone is not feeling either too hot or too cold. An environment can be said to achieve 'reasonable comfort' when at least 80% of its occupants are thermally comfortable. This means that thermal comfort can be assessed by surveying occupants to find out whether they are dissatisfied with their thermal environment. The human thermal environment is not straight forward and cannot be expressed in degrees. Nor can it be satisfactorily defined by acceptable temperature ranges. It is a personal experience dependent on a great number of criteria and can be different from one person to another within the same space. The thermal comfort variables used here are defined as follows: Dry Bulb Temperature of Air (DBT) The temperature of the air measured by the ordinary thermometer is called as the dry bulb temperature of air, commonly referred as DBT. When ordinary 8 Heat Transfer Shubber Jawad thermometer is exposed to the atmosphere, it indicates the dry bulb temperature, which is nothing but the atmospheric temperature. Wet Bulb Temperature of Air (WBT) The wet bulb temperature of air is also measured by the ordinary thermometer, but the only difference is that the bulb of the thermometer is covered by the wet cloth. Temperature of the ordinary air measured by the thermometer when it is covered by wet cloth or wick is called as the wet bulb temperature, commonly referred to as WBT. When the air comes in contact with the wet cloth it absorbs some moisture and gives up some heat, sue to which the temperature of the air reduces. This reduced temperature measured by the thermometer is called as the wet bulb temperature. Figure 1- below shows sling thermometer. Figure 1- Sling psychrometer and its usage. Air motion encourages evaporation from the moist cloth, lowering the wet-bulb temperature below the surrounding air temperature, whereas the dry-bulb temperature stays constant at the surrounding air temperature. (At 100% RH, WB and DB temperatures will be equal.) 9 Heat Transfer Shubber Jawad The Dew point Temperature (DP) The Dew point temperature is the temperature at which the air can no longer "hold" all of the water vapor which is mixed with it, and some of the water vapor must condense into liquid water. The dew point is always lower than (or equal to) the air temperature. If the air temperature cools to the dew point, or if the dew point rises to equal the air temperature, then dew, fog or clouds begin to form. At this point where the dew point temperature equals the air temperature, the relative humidity is 100%. Relative Humidity (RH) Relative humidity is the amount of water vapor (vapor pressure) that is in the air. It is a percentage of how much moisture the air could possibly hold. The amount of vapor that can be contained in the air increases with temperature. The higher the percentage of relative humidity, the more humid (moist) the air feels, while a lower percentage usually feels drier. Saturation occurs when air is holding the maximum amount of water vapor possible at the existing pressure and temperature. Saturation is equal to 100% relative humidity, resulting in precipitation Specific Humidity or Humidity ratio (HR) or (MC) Is the ratio of the mass of water vapour to the mass of dry air in a given volume of mixture, measured by Kg water vapour/Kg dry air Enthalpy The total heat in the mixture measured above zero degree Fahrenheit and including the latent heat of water vapour. British Thermal Unit (BTU) Is the amount of heat required to raise the temperature of one pound of water to one degree Fahrenheit. Sensible Heat Is the energy required to change the temperature of a substance with no change in substance phase. 10 Heat Transfer Shubber Jawad Latent heat Latent heat is the energy absorbed by or released from a substance during a phase change from a gas to a liquid or a solid or vice versa without changing in its temperature. Environmental factors Effecting on Thermal Comfort 1- Air temperature The temperature of the air that a person is in contact with, measured by the dry bulb temperature (DBT). 2- Air velocity The velocity of the air that a person is in contact with (measured in m/s). The faster the air is moving, the greater the exchange of heat between the person and the air (for example, draughts generally make us feel colder). 3- Radiant temperature The temperature of a person surroundings (including surfaces, heat generating equipment, the sun and the sky). 4- Relative humidity (RH) The higher the relative humidity, the more difficult it is to lose heat through the evaporation of sweat. Criteria for thermal comfort In winter 22.2 ºC (72ºF), and relative humidity (30%-60%) In summer 25.5 ºC (78ºF), and relative humidity (30%-60%) The design temperature for room air conditioning depends on the types of human activiy Living room (20-21) ºC bedroom (13-16) ºC kitchen 16 ºC offices 20 ºC 11 Heat Transfer Shubber Jawad shops 19 ºC classroom ºC 17. Air Conditioning Heating, Ventilating and Air Conditioning (HVAC), generally means the provision of an acceptable thermal environment within buildings. It includes heating, cooling, humidifying, dehumidifying, filtering, and distribution of air at suitable conditions for the maintenance of human comfort or for the undertaking of a particular process. In order to design an air conditioning system the appropriate heating, cooling, and other environmental loads must first be calculated and a variety of other factors such as initial and running costs, plant room and distribution space, control requirements etc. must be assessed. In practice, there are a wide variety of air conditioning systems available and selection is often dictated by factors other than the air conditioning loads. Air Conditioning Psychrometrics Comfort conditions are maintained within a building by supplying conditioned air at an appropriate state to overcome the incident heating and cooling loads. The required state will have specified conditions of temperature and moisture content and the processes required to achieve that supply state can be evaluated by air conditioning psychrometrics. The changes in psychrometric properties of a sample of air as it passes through an air conditioning system can best be visualized by use of a psychrometric chart which, for a given barometric pressure, presents the psychrometric properties of moist air over a range of conditions. The standard psychrometric chart as Figure 2. Any point on the chart is defined by two psychrometric properties and from the chart all other properties of the state point can be determined. A schematic representation of the various air conditioning processes is given in Figure 3. 12 Heat Transfer Shubber Jawad Figure 2- The standard psychrometric Figure 3- Schematic representation of air conditioning processes. 13 Heat Transfer Shubber Jawad 14 Heat Transfer Shubber Jawad 15 Heat Transfer Shubber Jawad Example 1: Design the capacity of AC for a house with 6 persons according to the data given below:1- Outdoor air DBT 95 ºF, WBT 75 ºF, indoor air DBT 75 ºF, WBT 58 ºF, mixing air DBT 76 ºF. 2- Ventilating air 20 cfm/person, daily change temperature (low) 3- Windows, regular single glass inside shading, 130 ft2 west in direction, 145 ft2 north in direction, 200 ft2 east in direction. 4- Wood door 88 ft2 , walls, masonry brick plastered 190 ft2 , ceiling 4 inch concrete insulation light 2848 ft2, metal door 44 ft2 (U = 0.42). 5- Lighting and kitchen 2500 Watt, use temperature swing factor of 0.75. Ans. Calculating of heat gain:1- RSH=300 × 6= 1800 Btuh 2- Windows use table (10-4): Area HTM RSH (Btuh) E 200 89 17800 W 130 89 11570 N 145 31 4495 3-walls use table (10-3) = 190× 9.7= 1843 Btuh. 4- Ceiling use table (10-3) = 2848× 2.4= 6835 Btuh. 5- Metal door = 44× 0.42 × (95-75) = 369.6 Btuh. 6- Wood door = 88× 14 = 1232 Btuh. 7- Ventilating = 120 cfm × 22 = 2640 Btuh. 8- Light and kitchen = 2500 × 3.41= 8525 Btuh. ∑RSH = 1800+ (17800+11570+4495) + 1843+6835+369.6+1232+2640+8525 = 57109.8 Btuh × 0.75 = 42832.35 Btuh. 16 Heat Transfer Shubber Jawad RLH= 90 × 6= 540 Btuh SHR = SHR= = 0.98 Exterior air or ventilation air (Q1) =20 × 6 = 120 cfm. Mixing air (Q3) = exterior air (Q1) + returned air (Q2) DBT mixing air= [ ( ) DBT mixing air = 76 ºF = (( ( )] [ ( ) ) ( ( ( ) ( ( )] ) )) Q3 = 2400 cfm Q2 = 2400-120 = 2280cfm. WBT mixing air= [ WBT mixing air = ( ( ) ) ( ) ( )] [ ( ) ( ( ) ( )] ) = 58.85 ºF. From psychrometric chart:For mixing air DBT= 76 ºF and WBT= 58.8 ºF ΔT= E = 25.7 Btu/lb = 17.84 = DBT of A.C = 75-17.84 = 57.16 From psychrometric chart:DBT of A.C = 57.16 , SHR= 0.98 WBT of A.C= 46.4 ºF, E =18.4 Btu/lb Btuh (A.C) = 60 × 0.074 × Q3 × (E before A.C-E after A.C) = 60 0.074 (25.7-18.4) = 77788.8 Btuh 1 ton = 12000 Btu A.C = = 6.5 ton 17 Heat Transfer Shubber Jawad Example 2: If total room sensible heat gain (RSH) = 90000Btuh, latent heat gain (RLH) = 300 Btuh/person, sensible heat ratio 0.75, ventilation rate 1500 cfm, outdoor air DBT= 95 ºF, WBT =75 ºF, indoor air DBT= 75 ºF, WBT =62.5 ºF, A.C air DBT= 60 ºF and E =22.5 Btu/lb, find the following;1- No. of persons in the room. 2- Ventilating rate / person. 3- Quantity of air returned. 4- Capacity of A.C required. Ans. SHR = , RLH= 30000 Btuh. 0.75 = RLH = latent heat/ person No. of persons No. of persons = 30000/ 300 = 100 person. Ventilation rate/ person = 1500/ 100 = 15 cfm/ person. Total air quantity required (Q3) = = ( = 6000 cfm. ) Quantity of air returned (Q2) = 6000-1500 = 4500 cfm. DBTmixing air= [ ( DBTmixing air = WBTmixing air= ( [ WBTmixing air = ) ) ( ( ( )] [ ( ) ) ) ) ( ( ( ) ( ( )] ) = 80 ºF ( )] [ ( ) ) ( ( ) ( ) = 65.62 ºF. From psychrometric chart E = 30.5 Btu/lb. Btuh (A.C) = 60× 0.074× Q3× (E before A.C-E after A.C) Heat to be removed = 60× 0.074 6000 (30.5 – 22.5) = 211392 Btuh. Capacity of A.C = (211392/ 12000) = 17.62 ton. 18 )] Heat Transfer Shubber Jawad Mechanism of cooling and heating 19 Heat Transfer Shubber Jawad 20 Electric Services Shubbar Jawad Electric services Ohm's Law deals with the relationship between voltage and current in an ideal conductor. This relationship states that: The potential difference (voltage) across an ideal conductor is proportional to the current through it. The constant of proportionality is called the "resistance", R. Ohm's Law is given by: V=IR where V (volt) is the potential difference between two points which include a resistance R(Ohm's ). I (ampere) is the current flowing through the resistance. Question A source of 6.0V is connected to a purely resistive lamp and a current of 2.0 amperes flows. What is the resistance of the lamp? V=IR R=V/I R = 3.0 Power Factor In AC circuits, the power factor is the ratio of the real power that is used to do work and the apparent power that is supplied to the circuit. Electrical Power formulas in Single Phase AC Circuits Real Power(watt) = V x I x (PF) where PF = cos Φ = power factor (0.7 - 0.95) For pure resistive load: PF = cos Φ = 1 21 Electric Services Shubbar Jawad resistive loads converts current into other forms of energy, such as heat inductive loads use magnetic fields like motors. apparent power= KVA = V x I / 1000 Electrical Power formulas in Three Phase AC Circuits P(watt) =√3 x V x I x PF , √3=1.732 KVA = V x I x 1.73/1000 *Where I = Current in Amperes (A) V = Voltage in Volts (V) P = Power in Watts (W) R = Resistance in Ohm (Ω 22 Electric Services Shubbar Jawad Example: An operating three phase motor has voltages measured with a voltmeter on each phase of 400 volts, amperage measured on each phase with an ammeter are 14.1, 13.9, and 13.8 amps, power factor was measured as 0.82 compute power and KVA. Voltage = (400+400+400) / 3 = 400V Ampacity =(14.1 + 13.9 + 13.8) / 3 = 13.9A Power = (400V x 13.9A x 0.82 x 1.732) / 1000 = 7.89 Kwatts KVA=(400V x 13.9A x 1.732) / 1000= 9.63 KVA Typical load connection on 3-phase 240/400 Volts system Single phase connection : phase to neutral 240V (2-wires) Single phase connection : phase to phase 400V (2-wires) Single phase connection : (240/400)V (3-wires) Three phase connection : phase to phase 400V ( 3wires) Three phase connection: (240/400)V (4wires) 23 Electric Services Shubbar Jawad Show the connection of the following appliances 1 - single phase 240V motor 2- 3- phase 400V motor 3- heater single phase 400V 4- air conditioner (240/400)V 3- phase 5- air conditioner (240/400)V single phase 24 Branch Circuit Shubbar Jawad Branch Circuits The portion of the wiring system extending past the final overcurrent device. These circuits usually originate at a panel and transfer power to load devices. Any circuit that extends beyond the final overcurrent protective device is called a branch circuit. This includes circuits servicing single motors (individual) and circuits serving many lights and receptacles (multi wire). Branch circuits are usually low current (30 amps or less), but can also supply high currents. The purposes of this division are:a) To prevent danger in the event of a fault by insuring that the fault current needed to operate the protective device is reasonably low. b) To enable parts of the installation to be switched off for testing and maintenance without effecting others. c) To prevent a fault on one part from shutting down the complete installation. A basic branch circuit as shown below is made up of conductors extending from the final overcurrent protective device to the load. Some branch circuits originate at safety switches (disconnects), but most originate at a panel board. The following are several branch circuit classifications: 25 Branch Circuit Shubbar Jawad • Individual branch circuit—A branch circuit that supplies a single load. • Multi outlet branch circuit—A branch circuit with multiple loads. • General purpose branch circuit—A multi outlet branch circuit that supplies multiple outlets for appliances and lighting. Circuits of Socket Outlets Plugs and socket outlets conforming with BS1363 & BS546 are of the following sizes:- 2; 5; 13; 15, 30 Amp ( The 13 A size is always fused ) The above sizes are very widely used for domestic and commercial installations. In addition, other sizes ( 16, 32, 63, 125 amp.) conforming to BS4343 are available for industrial applications. The ring and radial circuits are both used for providing power supply to socket outlets. The following guidelines must be taken into account: Floor area served should not exceed the values indicated on diagrams for the type of circuit used. Circuit breaker (or fuse) and wire sizes depend on the circuit used and shall be as given on diagrams. A separate circuit (ring or radial) should be provided for the kitchen. If two or more ring circuits are installed in the same location, the socket outlets should be reasonably shared among them. Various appliances can be individually protected by a fuse of a suitable rating (2, 3, 5, or 10 amp.) installed in the plug. Such a fuse will protect the plug, the flexible cord and the appliance connected to it. Permanently connected appliances with a relatively high power demand (such as water heaters, window-type air conditioners, split-unit type air conditioners, electric cookers, etc, should not be connected to a ring or radial circuits, they must be supplied by their own separate circuits. 26 Branch Circuit Shubbar Jawad 27 Branch Circuit Shubbar Jawad Various authorities have given recommendations concerning the appropriate number of socket outlets to be installed in various locations:- Location Number of outlets Kitchen 4-5 Living Room 3-4 Dining Room 1-2 Master Bedroom 3-4 Single Bedroom 2-3 Landing/Stairs/Hall 1-2 Garage 1 Store/Workroom 1 Lighting Circuits Circuits intended to provide power supply to lighting fixtures are called Lighting Branch Circuits. Circuits supplying lighting fixtures with some other small appliances such as electric clocks, time stamps, bell transformers, shaver sockets, ceiling & exhaust fans, etc…, are ALSO called Branch Circuits. NEC permits loading of a circuit to its ampere rating, However, it is a better design practice to limit the circuit loading to 80% of its rating. When a lighting branch circuit is protected by 7.5 or 10 amp. CB or Fuse, the wire size that should be used in 1.5 mm2 PVC insulated copper conductor. When a lighting branch circuit is protected by 15 or 20 amp. CB or Fuse, the wire size that should be used is 2.5 mm2 PVC insulated copper conductor. 28 Branch Circuit Shubbar Jawad In all cases the lighting branch circuit must be assumed to require the connected load, but with a minimum of 100W for each light-point outlet (0.46 amp. Per outlet). Branch-Circuit Rating A branch circuit is sized for the load it will supply. Sizing the circuit for additional future loads is good practice. The rating of a branch circuit depends on the rating of the overcurrent device protecting the circuit. Branch circuits serving only one device can have any rating, while a circuit supplying more than one load is limited to ratings of 15, 20, 30, 40, or 50 amps. Fractions of an Ampere. Except where the calculations result in a major fraction of an ampere (0.5 or larger), such fractions are permitted to be dropped (NEC 2017) . Conductor Size and Ampacity The amperage rating of branch-circuit conductors must be greater than the maximum load the circuit will provide. Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size shall have an allowable ampacity not less than the noncontinuous load plus 125 % of the continuous load, or the conductor operate at 80% of their rating at continuous loading (NEC 2017). Continous Load: A load where the maximum current is expected to continue for 3 hours or more like electric space heating equipments, air conditioners, refrigerators, motors (NEC 2017). Overcurrent Protective Device (OCPD) Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads for non-motor loads, the rating of the overcurrent device (circuit breaker or fuse) shall not be less than the non-continuous load plus 125 percent of the continuous load. OCPD for motors Motors except Hermetically Sealed 250% of motor full load current (NEC430-52) Motors Hermetically Sealed, air conditioners and heat pumps not exceeding 175%225% of motor full load current NEC 440.22-2017. Fig 3.5 contains circuit breaker standard size. 29 Branch Circuit Shubbar Jawad Example 1: Load Furnace 5 KW works for 4 hours continuously, I phase, 220V, find current, KVA, PVC wire size, circuit breaker size, P.F. = 1.0 I = KW/ KV = 5KW/.23KV = 22.7 Amp Wire Size Wire Size = Load/ 0.8 = ampacity = 22.7 Amp /0.8 = 28.375 Amp Or 22.7 × %521 =28.375 Amp from (table C.52.1 of IEC 60364-5-52), use (2× 6 mm2), 2pvc wire in conduit Circuit Breaker Sizing CB =22.7× %521 =28.375 Amp Next higher CB size is 32 Amp. see Fig 3.5 Example 2 Load: Unit Heater 10 KW, 400 V, 3 phase, find I, PVC wire size, circuit breaker size I= 10×1000/(400√3)= 14.43 Amp Wire Size: 14.43 A× 1.25 = 18 Amp (table C.52.1 of IEC 60364-5-52), Use 3×4 mm2 , 3pvc wire in conduit Circuit Breaker = 14.43 A× 1.25 = 18 Amp, so use 20 Amp. 3 pole Example 3 Branch circuit includes a 9 Amp. microwave with a 4 Amp. Refrigerator, find PVC conductor size and circuit breaker size. Circuit ampacity= ( 9 × 100% + 4 × 125%)= 14 Amp. From (table C.52.1 of IEC 60364-5-52), use 2× 2.5 mm2, 2pvc wire in conduit 30 Branch Circuit Shubbar Jawad Circuit breaker rating = ( 9 × 100% + 4 × 175%)= 16 Amp., From Fig 3.5 use 16 Amp. circuit breaker. Example 4: Load: Motor 3 HP( I = 17A), 1 phase, 230V find PVC wire size, circuit breaker size Wire Size = 17A× 1.25= 21.5A From (table C.52.1 of IEC 60364-5-52), use (2× 4 mm2), 2pvc wire in conduit CB size = (I)( 2.5) NEC 430-52 CB Size = (17 A) (2.5) = 42.5A USE next size up 50A circuit breaker. Example5: For an air-conditioning unit with a three phase, 230-volt, (15 amps), what is the required size of the branch-circuit wire and overcurrent protective device? Solution: This load must be increased by 125% for the conductor ampacity: Conductor ampacity = 15 A × 1.25= 18.75 A From (table A.52.4 of IEC 60364-5-52), use (3×4 mm2), 3pvc wire in conduit Circuit Breaker = 15 A × 1.75 = 26 Amp so use next size up 32 Amp. 3 pole Example 6: a branch circuit consist of 3KW electric space heating and 20 Amp. air conditioner find PVC wire size and circuit breaker required. Ampacity of electric space heating = 3000/220 = 13.6 Air conditioner ampacity is larger than electric space heating ampacity, so omit electric space heating The ampaciy of wire= (1.25×20) =25 Amp. From (table C.52.1 of IEC 60364-5-52)), use (2× 6 mm2), 2pvc wire in conduit. CB size = (1.75×20) =35 Amp., from fig 3.5 use 40 Amp. CB 31 Branch Circuit Shubbar Jawad Voltage Drop of Cables The impedance of circuit conductors is low but not negligible: when carrying load current there is a voltage drop between the origin of the circuit and the load terminals. The correct operation of a load (a motor, lighting circuit, etc.) depends on the voltage at its terminals being maintained at a value close to its rated value. It is necessary therefore to determine the circuit conductors such that at full-load current, the load terminal voltage is maintained within the limits required for correct performance. Maximum voltage drop limit Typical values of maximum allowable voltage-drop for LV installations are given below in table G25. Table. G25: Maximum voltage-drop between the service-connection point and the point of utilization (IEC60364-5-52 table G.52.1) These voltage-drop limits refer to normal steady-state operating conditions and do not apply at times of motor starting. The value of 8 %, while permitted, can lead to problems for motor loads; for example: a- In general, satisfactory motor performance requires a voltage within ±5 % of its rated nominal value in steady-state operation, b- Starting current of a motor can be 5 to 7 times its full-load value (or even higher). If an 8 % voltage drop occurs at full-load current, then a drop of 40 % or more will occur during start-up. In such conditions the motor will either:32 Branch Circuit Shubbar Jawad 1- Stall (i.e. remain stationary due to insufficient torque to overcome the load torque) with consequent over-heating and eventual trip-out 2- Or accelerate very slowly, so that the heavy current loading (with possibly undesirable low-voltage effects on other equipment) will continue beyond the normal start-up period. Finally an 8 % voltage drop represents a continuous power loss, which for continuous loads will be a significant waste of (metered) energy. For these reasons it is recommended that the maximum value of 8 % in steady operating conditions should not be reached on circuits which are sensitive to under-voltage problems (see Fig. G26). Calculation of Voltage Drop Voltage drop can be calculated by using Figure G28, which gives, with an adequate approximation, the phase-to-phase voltage drop per km of cable per ampere, in terms of: 1- Kinds of circuit use: motor circuits with cos ϕ close to 0.8, or lighting with a cos ϕ close to 1. 2- Type of circuit; single-phase or 3-phase 33 Branch Circuit Shubbar Jawad Voltage drop in a cable is then given by: ΔU=K x IB x L ΔU is Voltage drop in volts K is given by the table, V/A/Km IB is the full-load current in amps, L is the length of cable in km. The column motor power “cos ϕ = 0.35” of Figure G28 may be used to compute the voltage drop occurring during the start-up period of a motor. The % of voltage drop can be calculated as follow:Phase/phase:- ΔU% = ˟100% Phase/neutral:-ΔU% = ˟ 100% Balanced 3-phase: (3 phases (with or without neutral)): ΔU% = ˟100% Where: Un: phase-to-phase voltage Vn: phase-to-neutral voltage Example1: A single-phase lighting circuits 240 V, of 1.5 mm2 c.s.a. copper 25 m long, and passing 15 A. Examine the adequacy of wire for this circuit. Ans. From Figure G28, K= 32 V/A/Km ΔU= K x IB x L= 32 x 15 x (25/1000) = 12 V phase to neutral ΔU% = ˟ 100% = ˟ 100% = 5% < 3% not ok, use next larger wire For 2.5mm2, K= 19 V/A/Km ΔU= 19 x 15 x (25/1000) = 7.125 V phase to neutral 34 Branch Circuit ΔU% = Shubbar Jawad ˟ 100% = 2.9% < 3% ok, use 2.5 mm2 wire Example 2 A 3-phase 4-wire copper line of 70 mm2 c.s.a. and a length of 50 m passes a current of 150 A. The line supplies 3 single-phase lighting circuits, each of 2.5 mm2 c.s.a. copper 20 m long, and each passing 20 A. as shown in figure. It is assumed that the currents in the 70 mm2 line are balanced and that the three lighting circuits are all connected to it at the same point. What is the voltage drop at the end of the lighting circuits? Ans. 1-Voltage drop in the 4-wire line: Balanced 3-phase: ΔU% = ˟100% Figure G28 shows K=0.59 V/A/km ΔU line = 0.59 x 150 x 0.05 = 4.4 V phase-to-phase which gives: = 2.54 V phase to neutral. 2- Voltage drop in any one of the lighting single-phase circuits: Figure G28 shows K=19 V/A/km ΔU for a single-phase circuit = 19 x 20 x 0.02 = 7.6 V The total voltage drop is therefore 7.6 + 2.54 = 10.1 V ΔU% = ˟100% = ˟100% = 4.2% < 6% This value is satisfactory, being less than the maximum permitted voltage drop of 6 %. 35 Branch Circuit Shubbar Jawad Example 3 A three-phase 25 mm2 copper cable 50 metres long connected from a LV public power distribution network supplies a 400 V motor taking: a- 100 A at a cos ϕ = 0.8 on Normal service load b- 500 A at a cos ϕ = 0.35 during start-up What is the voltage drop of motor cable at: 1- Normal service load? 2- During start-up? Ans. 1- Voltage drop in Normal service load: Figure G28 shows K= 1.4 V/A/km so that: ΔU for the cable = 1.4 x 100 x 50/1000= 7 V ΔU% = ˟100% = ˟100% = 1.75 % < 5%, ok, it is satisfactory 2- During start-up Figure G28 shows 0.7 V/A/km so that: ΔU for the cable = 0.7 x 500 x 50/1000= 17.5 V ΔU% = ˟100% = ˟100% = 4.37% < 5%, it is satisfactory during motor starting Example 4: Somebody wants to use local generator to supply 6A, 220V single phase 1 ton air conditioner in his house by using of 2.5mm2 copper wire for a distance of 100 meter. Examine the adequacy of wire for this circuit. Assume start-up current 5 x IB. 1- Voltage drop in Normal service load: For 2.5mm2, K= 15.3 V/A/Km ΔU= 15.3 x 6 x (100/1000) = 9.18 V phase to neutral ΔU% = ˟ 100% = 4.17% < 8 % ok, 2-Voltage drop during start-up 36 Branch Circuit Shubbar Jawad For 2.5mm2, K= 6.8 V/A/Km ΔU= 6.8 x ( 6 x 5) x (100/1000) = 20.4 V phase to neutral ΔU% = ˟ 100% = 9.27% < 8 %, not ok, use next larger wire (4 mm2 ) 1- Voltage drop in Normal service load: For 4 mm2, K= 9.6 V/A/Km ΔU= 9.6 x 6 x (100/1000) = 5.76 V phase to neutral ΔU% = ˟ 100% = 2.61% < 8 % ok, 2-Voltage drop during start-up For 4 mm2, K= 4.3 V/A/Km ΔU= 4.3x ( 6 x 5) x (100/1000) = 12.9 V phase to neutral ΔU% = ˟ 100% = 5.8% < 8%, ok, Using of (4 mm2 ) wire it is satisfactory during motor starting. 37 Electrical loads Shubbar Jawad Maximum Demand: It is the greatest of all demands which have occurred during a specified period of time. It is usually expressed in kW, kVA, Amp., etc. Demand Factor :- The ratio of the maximum coincident demand of a system, or part of a system, to the total connected load of the system. Demand factor (in IEC, Max. Utilization factor (Ku)) Demand Factor is express as a percentage (%) or in a ratio (less than 1). Demand factor is always < =1 The lower the demand factor, the less system capacity required to serve the connected load. Example1: an oversized motor 20 Kw drives a constant 15 Kw load whenever it is ON. The motor demand factor is then 15/20 =0.75= 75 %. Example2: if a residence having 6000W equipment connected has a maximum demand of 3300W, then demand factor = 3300W / 6000W = 55%. (1) A Residence Consumer has 10 No’s Lamp of 400 W but at the same time It is possible that only 9 No’s of Bulbs are used at the same time. Here Total Connected load is 10×40=400 W. Consumer maximum demand is 9×40=360 W. Demand Facto of this Load = 360/400 =0.9 or 90%. (2) One Consumer have 10 lights at 60 Kw each in Kitchen, the load is 60 Kw x 10 = 600 KW. This will be true only if All lights are Turns ON the same time (Demand factor=100% or 1) For this Consumer it is observed that only half of the lights being turned ON at a time so we can say that the demand factor is 0.5 (50%). The estimated load = 600 Kw X 0.5 = 300 Kw. 38 Electrical loads Shubbar Jawad Use of demand factors: Feeder conductors should have sufficient Ampere Capacity to carry the load. The Ampere Capacity does not always be equal to the total of all loads on connected branch-circuits. The demand factor permits a feeder-circuit ampere to be less than 100% of the sum of all branch-circuit loads connected to the feeder. This factor must be applied to each individual load, with particular attention to electric motors, which are very rarely operated at full load. Demand factor can be applied to calculate the size of the sub-main which is feeding a Sub panel or a fixed load like a motor etc. If the panel have total load of 250 kVA, considering a Demand factor of 0.8, we can size the feeder cable for 250 x 0.8= 200 kVA. Demand factors for buildings typically range between 50 and 80 % of the connected load. In an industrial installation this factor may be estimated on an average at 0.75 for motors. For incandescent-lighting loads, the factor always equals 1. (2) Diversity factor / (in IEC, simultaneity factor (Ks)) Diversity Factor is ratio of the sum of the individual maximum demands of the various sub circuit of a system to the maximum demand of the whole system. Diversity Factor = Sum of Individual Maximum Demands / Maximum Demand of the System. Diversity Factor = Installed load / Running load. The diversity factor is always >= 1. Diversity Factor is always >1 because sum of individual max. demands >Max. demand. In other terms, Diversity Factor (0 to 100%) is a fraction of Total Load that is particular item contributed to peak demand. 70% diversity means that the 39 Electrical loads Shubbar Jawad device operates at its nominal or maximum load level 70% of the time that it is connected and turned ON. It is expressed as a percentage (%) or a ratio more than 1. If we use diversity value in % than it should be multiply with Load and if we use in numerical value (>1) than it should be divided with Load. Diversity occurs in an operating system because all loads connected to the system are not operating simultaneously or are not simultaneously operating at their maximum rating. Diversity factor is an extended version of demand factor. It deals with maximum demand of different units at a time/Maximum demand of the entire system. Greater the diversity factor, lesser is the cost of generation of power. Example I: One Main Feeder have two Sub feeder (Sub Feeder A and Sub Feeder B), Sub Feeder-A have demand at a time is 35 KW and Sub Feeder-B have demands at a time is 42 KW, but the maximum demand of Main Feeder is 70 KW. Total individual Maximum Demand =35+42=77 KW. Maximum Demand of whole System=70 KW So Diversity factor of The System= 77/70 =1.1 Example-II: A sub-station has three outgoing feeders: 1- Feeder 1 has maximum demand 10 MW at 10:00 am, 2- Feeder 2 has maximum demand 12 MW at 7:00 pm and 3- Feeder 3 has maximum demand 15 MW at 9:00 pm, 4- While the maximum demand of all three feeders is 33 MW at 8:00 pm. Ans. the sum of the maximum demand of the individual sub-systems (feeders) is 10 + 12+ 15 = 37 MW, while the system maximum demand is 33 MW. The diversity factor = 37/33 = 1.12. 40 Electrical loads Shubbar Jawad Example III :-Two factories A & B with load curves indicated are supplied by the same feeder. Calculate the load diversity factor between the two factories S( kVA) S (kVA) Factory B 380 Factory A 300 240 200 120 100 0 6 12 18 24 Time (hr) 0 6 12 18 24 Time (hr) Diversity factor = Calculate Size of Electrical cable and CB by Demand & Diversity Factor: The estimated electrical demand for all feeders served directly from the service entrance is calculated by multiplying the total connected loads by their demand factors and then adding all of these together. This sum is divided by the diversity factor to calculate the service entrance demand which is used to determine ampacity requirements for the service entrance conductors. When used Diversity and Demand Factor in an electrical design it should be applied as follows, the sum of the connected loads supplied by a feeder-circuit can be multiplied by the demand factor to determine the load used to size the components of the system. The sum of the maximum demand loads for two or more feeders is divided by the diversity factor for the feeders to derive the maximum demand load. Example-1: Suppose We have four individual feeder-circuits with connected loads of 250 kVA, 200 kVA, 150 kVA and 400 kVA and demand factors of 90%, 80%, 75% and 85% respectively. Use a diversity factor of 1.5. Calculating demand for feeder-circuits 250 kVA x 90% = 225 kVA 200 kVA x 80% = 160 kVA 150 kVA x 75% = 112.5 kVA 400 kVA x 85% = 340 kVA 41 Electrical loads Shubbar Jawad The sum of the individual demands is equal to 837.5 kVA. However, using the diversity factor of 1.5, the kVA = 837.5 kVA ÷ 1.5 = 558 kVA for the main feeder. Example-2: For network shown below Calculate the following;1- Size of main circuit breaker and main feeder PVC wire. 2- Size of sub main circuit breaker and sub feeder PVC wire. Use power factor of 0.8 for all loads. Maximum Demand of Consumer 1 =32 KW x 0.65 =20.8 KW As Diversity of Consumer 1 is 1.5 so, Maximum Demand on sub feeder 1 =20.8 KW/1.5 = 13.86 KW. Sub feeder 1 current = √ Select a 25 A triple-pole circuit breaker for Sub- MDB 1 Select from the table a cable size of (4x6) mm2 for sub feeder 1 Sum of Maximum Demand of Consumer 2 =40 KW x 0.75 =30 KW As Diversity of Consumer Connected on sub feeder 2 is 1.1 so, Maximum Demand on sub feeder 2 =30 KW/1.1 = 27.27 KW 42 Electrical loads Sub feeder 2 current = Shubbar Jawad √ Select a 50 A triple-pole circuit breaker for Sub- MDB 2 Select from the table a cable size of (4x16) mm2 for sub feeder 2 Sum of Maximum Demand of Customer 3 =50 KW x 0.65 =32.5 KW As Diversity of Consumer Connected on sub feeder 3 is 1.5 so, Maximum Demand on sub feeder 3 = 32.5 KW/1.5 = 21.66 KW Sub feeder 3 current = √ Select a 40 A triple-pole circuit breaker for Sub- MDB 3 Select from the table a cable size of (4x10) mm2 for sub feeder 3 Maximum Demand on Main Feeder =13.86 +27.27 +21.66 / 1.3 =48.3 KW Main feeder current = √ Select a 100 A triple-pole circuit breaker for MDB Select from the table a cable size of (4x25) mm2 for main feeder Example-3 A three story residential building to be supplied from a unit substation installed at the electrical room at the ground floor level. Each floor level is composed of three apartments with maximum demand of 15 kW each. The power factor of all building is 0.9. Assume a diversity factor of 1.3 between apartments at each floor level. Assume a diversity factor of 1.4 between loads of various floors. Assume individual floor supply with the sub-main distribution boards 1-Calculate pvc wire and circuit breaker size for each apartment 2-Calculate pvc wire and circuit breaker size for each floor 3-Calculate size of service entrance PVC wire and circuit breaker size for main distribution boards 43 Electrical loads Apartment current = Shubbar Jawad √ Select a 25 A triple-pole circuit breaker for each apartment Select from the table a cable size of (4x6) mm2 for each apartment Total floor kW = Floor current = √ Select a 63 A triple-pole circuit breaker for each floor Select from the table a cable size of (4x25) mm2 for each floor Total building kW = Total building current = √ Select a 125 A triple-pole circuit breaker for main distribution boards Select from the table a cable size of (4x35) mm2 for service entrance pvc wire. Example-4 Calculate size of main circuit breaker and a service entrance PVC Aluminium wire size for a house supplied with 230 V, single phase had a panel board containing the following branch circuits: 1- Lighting circuit (10×40 watt) florescent fixture with power factor of 0.8 and demand factor of 1. 2-Socket outlets (15×13 Ampere) with power factor of 0.8 and demand factor of 0.1 3- Water pump 0.5 hp with power factor of 0.8 and demand factor of 0.75 4- 2 air cooler 500 watt each one with power factor of 0.8 and demand factor of 0.75 5- Oven of 1300 watt with power factor of 1 and demand factor of 1. 6- Water heater 2000 watt with power factor of 1 and demand factor of 1. 44 Electrical loads Shubbar Jawad 7- 2 Air conditioner 3200 watt with power factor of 0.8 and demand factor of 0.75 Assume a diversity factor of 1.4 between loads of various branch circuits. Ans. 1- Max. demand of lighting = [(10 × 40)/0.8] × 1 =320 VA 2- Max. demand of socket outlets=(15 × 13 Ampere)×230×0.1= 4485 VA 3- Max. demand of water pump = [(0.5 × 746 Watt)/0.8] × 0.75= 350 VA 4- Max. demand of air coolers = (2 × 500/0.8) × 0.75= 937.5 VA 5- Max. demand of oven load= (1300/1) × 1= 1300 VA 6- Max. demand of water heater= (2000/1) × 1= 2000VA 7- Max. demand of AC =[ (2 × 3200)/0.8] × 0.75= 6000VA Total Max. demand = 320+4485+350+937.5+1300+2000+6000=15392.5 As diversity factor between branch circuits is 1.4, so Max. demand =15392.5/1.4 =10994.6VA House current= 10994.6/230 = 48 Amp. From fig.3.5 choose 50 Amp. single pole circuit breaker. From table.G21a choose (2×10) mm2, PVC Aluminium wire for service entrance cable. 45 Lighting Design Shubbar Jawad Zonal Cavity Method for Lighting Design The Zonal Cavity Method (sometimes called the Lumen Method) is the currently accepted method for calculating average illuminance levels for indoor areas, unless the light distribution is radically asymmetric. It is an accurate hand method for indoor applications because it takes into consideration the effect that inter-reflectance has on the level of illuminance. Although it takes into account several variables, the basic premise that footcandles are equal to luminous flux over an area is not violated. The basis of the Zonal Cavity Method is that a room is made up of three spaces or cavities. The space between the ceiling and the fixtures, if they are suspended, is defined as the “ceiling cavity”; the space between the work plane and the floor, the “floor cavity”; and the space between the fixtures and the work plane, the “room cavity.” Once the concept of these cavities is understood, it is possible to calculate numerical relationships called “cavity ratios,” which can be used to determine the effective reflectance of the ceiling and floor cavities and then to find the coefficient of utilization. Foot-candle:- is a unit of lighting which measures the intensity of light in relation to its source. The unit foot-candle is defined as the amount of illumination the inside surface of a one-foot-radius sphere would be receiving if there were a uniform point source of one candela in the exact center of the sphere. Alternatively, it can be defined as the illuminance on a one-square foot surface of which there is a uniformly distributed flux of one lumen. 46 Lighting Design Shubbar Jawad Illuminance:- is a measure of how much luminous flux is spread over a given area. (measured in lumens) Basic steps in any calculation of illuminance level: Step 1: Cavity ratios for a rectangular space may be calculated by using the following formulas: Where: hcc = distance in feet from luminaire to ceiling hrc = distance in feet from luminaire to work plane hfc = distance in feet from work plane to floor L = length of room, in feet W = width of room, in feet 47 Lighting Design Shubbar Jawad Step 2: Effective cavity reflectances must be determined for the ceiling cavity and for the floor cavity. These are located in Table (28.7) under the applicable combination of cavity ratio and actual reflectance of ceiling, walls and floor. The effective reflectance values found will then be ρcc (effective ceiling cavity reflectance) and ρfc (effective floor cavity reflectance). Note that if the luminaire is recessed or surface mounted, then CCR = 0 and ρcc = selected ceiling surface reflectance. If the floor is the working plane, then FCR = 0 and ρfc = selected floor surface reflectance. Step 3: With these values of ρcc, ρfc, and ρw (wall reflectance), and knowing the room cavity ratio (RCR) previously calculated, find the coefficient of utilization in the luminaire coefficient of utilization (CU) table (28.9). Note that since the table is linear, linear interpolations can be made for exact cavity ratios and reflectance combinations. The coefficient of utilization found will be for a 20% effective floor cavity reflectance. Thus, it will be necessary to correct for the previously determined ρfc. As the following: 1-For %01> ρfc >30% effective floor cavity reflectance, divided standard CU value by the appropriate factor from table (28.8). 2-For ρfc <30% effective floor cavity reflectance, multiply standard CU value by the appropriate factor from the table (28.8). 48 Lighting Design Shubbar Jawad Step 4: Computation of the illuminance level is performed using the standard Lumen Method formula. No. of luminaires = For large areas, a much more useful figure is the area illuminated per luminaire: area per luminaire = Where:fc = Foot candle CU= Coefficient of utilization. MF= The total light loss factor. MF = LLD× LDD LLD = lamp lumen depreciation table (28.10) LDD = luminaire dirt depreciation figure (28.26) Step 5: Check S:MH ratio. MH = mounting height (height from work surface to light source). S = Max. space between luminaire centres. SR (spacing ratio) = The solution considered correct if calculated is less than given selected type of luminaire, if not select another type of luminaire. Example 1: a typical classroom with a dimension of 25×20×12 ft, a required footcandles = 70, final reflectance: ceiling 80%, wall 50%, floor 10%. Use type 49 for Lighting Design Shubbar Jawad 32, 30 in stem mounting, fluorescent type 40 watt, T12, 4 ft with an initial lumen output= 3250 per lamp. Working plane at 30 in AFF. Ans. hcc= 2.5 ft (30 in stem mounting) hfc= 2.5 ft (30 in AFF) hrc= 12-2.5-2.5=7 ft CCR= 5hcc = 5(2.5) FCR= 5hfc = 5(2.5) RCR= 5hrc = 5(7) =1.1 =1.1 = 3.2 From table 28.7 ρcc=65%, ρw= 50% (given), ρfc = 11% from table 28.9, type 32, using ρw= 50% and ρfc=20%, we must double interpolate for RCR and ρcc ρcc RCR RCR 70 0.5 0.45 Interpolating first for RCR of 3.2 CU (70) = 0.5 - 0.05(0.2) = 0.49 CU (50) = 0.42- 0.04(0.2) = 0.41 For RCR = 3.2, ρw = 50 ρcc 70 50 CU 0.49 0.41 50 50 0.42 0.38 Lighting Design Shubbar Jawad Interpolating for ρcc = 0.65, we have CU = 0.49 - (0.08) = 0.49 – 0.02 = 0.47 Final CU = 0.47 for ρfc = 20% For ρfc = 11% since 01 %> ρfc >30%, divided standard CU value by the appropriate factor from table (28.8) which is 1.044 So, corrected CU = = 0.45 From table 28.10 LLD = 0.86 From fig. 28.26 LDD = 0.86 (12 months, dirty, category II) So, MF = 0.86 0.86 = 0.74 Area / luminaire = = 31ft2 = No. of luminaires = SR (spacing ratio) = = 16 luminaires == = 0.89 < 1.5, then ok. 51 Lighting Design Shubbar Jawad Example 2: A typical classroom with a dimension of 25×20×12 ft, a required footcandles = 70, final reflectance: ceiling 80%, wall 50%, floor 10%. Use type 33, the luminaire is recessed, fluorescent type 40 watt, T12, 4 ft with an initial lumen output= 3250 per lamp. Working plane at 30 in AFF. Ans. hcc = 0 ft (recessed or surface mounted) hfc = 2.5 ft (30 in AFF) hrc= 12-2.5 = 9.5 ft CCR= 0 FCR= 5hfc = 5(2.5) =1.1 RCR= 5hrc = 5(9.5) = 4.3 Since CCR= 0, then ρcc= 80% From table 28.7 ρw= 50% (given), ρfc = 11% From table (28.9) for type 33, by interpolating CU = 0.39, for ρfc= 20% For ρfc = 11% 52 Lighting Design Shubbar Jawad since 10%< ρfc >30%, divided standard CU value by the appropriate factor from table (28.8) which is 1.05 So, corrected CU = = 0.37 From table 28.10, LLD = 0.86 From fig. 28.26 LDD = 0.73, (12 months, dirty, category IV) So, MF = 0.86 0.73 = 0.63 = 22 ft2 Area / luminaire = No. of luminaires = SR (spacing ratio) = = 23 luminaires == = 0.53 < 1.2, then ok. 53