Download Leaky Feeder Manual

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
[email protected]
www.pbegrp.com
PH +61 7 3890 8113
FAX +61 7 3890 7489
PBE Australia
2/1631 Wynnum
Rd Tingalpa
Queensland 4173
AUSTRALIA
Leaky Feeder System Manual
VHF and UHF
Leaky Feeder System
Manual
Copyright © PBE Australia Pty Ltd (ABN 11 156 073 871), All rights reserved. No section or element of this document may be
removed from this document, reproduced, electronically stored or transmitted in any form without the written permission of PBE
Australia.
The information contained in this document produced by PBE, is solely for the use of the client(s) for the purpose for which it has
been prepared and PBE undertakes no duty to, nor accepts any responsibility to, any third party who may rely upon this information
contained in this document.
11/07/12
Date
D
Rev no
MAN-41-00001
Document number
SL
Prepared
JF
Approved by
PBE Leaky Feeder System Manual
Table of Contents
1.
INTRODUCTION ........................................................................................................................................ 4
1.1
1.2
1.3
WARNINGS AND WARRANTY.................................................................................................................. 4
COMPLIANCE .......................................................................................................................................... 5
FREQUENCY ALLOCATION .............................................................................................................................5
2.
GLOSSARY .................................................................................................................................................. 6
3.
SYSTEM OVERVIEW ................................................................................................................................ 8
3.1
COMMUNICATIONS RACK ..................................................................................................................... 10
3.2
HEAD END UNIT ................................................................................................................................... 10
3.2.1.
Head End Combiner (VHF: 02-00144, UHF: 03-00145, UHF: 03-00146) ............................... 10
3.3
LEAKY FEEDER POWER SUPPLY ........................................................................................................... 10
3.4
BASE RADIO EQUIPMENT...................................................................................................................... 11
3.4.1.
Voice Channels ........................................................................................................................... 11
3.4.2.
Data Channels ............................................................................................................................ 11
3.4.3.
Telephone Interconnect Unit....................................................................................................... 11
3.4.4.
Voice Message Alerting .............................................................................................................. 11
3.5
ABOVE GROUND ANTENNA SYSTEM .................................................................................................... 12
3.6
AUDIO BRIDGE (02-00138)................................................................................................................... 12
3.7
SURGE ARRESTER (24-00001) .............................................................................................................. 12
3.8
REPEATER (VHF: 05-00074, UHF: 05-00086) ..................................................................................... 13
3.9
ISOLATOR (VHF: 24-00007, UHF: 24-00017)...................................................................................... 13
3.10
MODEL 1925 POWER SUPPLY (FOR IS SYSTEMS ONLY) ........................................................................ 13
3.11
MODEL 1953 AND 1955 BATTERY BACKUP UNIT (FOR IS SYSTEMS ONLY) .......................................... 13
3.12
UNDERGROUND COMPONENTS................................................................................................... 15
4.
LAYOUT ..................................................................................................................................................... 16
4.1
COMPONENT LAYOUT .......................................................................................................................... 16
4.1.1.
Head End Combiner ................................................................................................................... 16
4.1.2.
Amplifiers .................................................................................................................................... 16
4.1.3.
Single Branch Units .................................................................................................................... 16
4.1.4.
Dual Branch Units ...................................................................................................................... 17
4.1.5.
Power Couplers .......................................................................................................................... 17
4.1.6.
Joiner Boxes................................................................................................................................ 18
4.1.7.
Termination Boxes ...................................................................................................................... 18
4.2
LAYOUT INSTRUCTIONS ....................................................................................................................... 18
4.3
POWERING THE SYSTEM........................................................................................................................ 19
4.4
UNPLANNED TOPOLOGY CHANGES ...................................................................................................... 19
4.5
EXAMPLE LAYOUT DIAGRAM .......................................................................................................................20
5.
INSTALLATION ....................................................................................................................................... 21
5.1
INSTALLATION GUIDELINES .................................................................................................................. 21
5.2
COMMUNICATIONS RACK INSTALLATION ...................................................................................................21
5.2.1.
Head End Combiner Mounting ................................................................................................... 21
5.2.2.
Head End Combiner Connections............................................................................................... 21
5.3
LEAKY FEEDER CABLE INSTALLATION .......................................................................................................22
5.3.1.
Catenary recommendations ........................................................................................................ 23
5.4
DISTRIBUTION EQUIPMENT (COMPONENTS) .......................................................................................... 24
5.4.1.
General Component Connection ................................................................................................. 24
5.4.2.
Head End Combiner Connection or Isolation Barrier Connection (for IS systems only) ........... 27
6.
TUNING (FOR GEN-3 AMPLIFIERS) ................................................................................................... 29
6.1.1.
6.1.2.
7.
Order of Tuning .......................................................................................................................... 29
Configuration of Amplifier Attenuator Settings .......................................................................... 29
MAINTENANCE ....................................................................................................................................... 32
7.1
MINECOM WEEKLY MAINTENANCE CHECKLIST ........................................................................................32
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 2 of 42
PBE Leaky Feeder System Manual
7.2
7.3
7.4
7.5
7.6
8.
FAULT FINDING ...................................................................................................................................... 34
8.1
8.2
8.3
8.4
9.
OPERATIONAL TRAINING...................................................................................................................... 32
MAINTENANCE TRAINING .................................................................................................................... 33
SYSTEM DRAWING ............................................................................................................................... 33
DOCUMENTATION ................................................................................................................................ 33
TEST EQUIPMENT REQUIRED ................................................................................................................ 33
IDENTIFY THE LOCATION OF THE FAULT .....................................................................................................34
HEAD END COMMUNICATIONS RACK FAULT..............................................................................................34
RADIO FAULT................................................................................................................................................34
SYSTEM FAULT .............................................................................................................................................34
PREVENTATIVE MAINTENANCE ....................................................................................................... 36
9.1
PROGRAM MAINTENANCE .................................................................................................................... 36
9.1.1.
Communications Rack ................................................................................................................ 36
9.1.2.
Down Line System ....................................................................................................................... 36
9.1.3.
Portable Radios .......................................................................................................................... 36
9.1.4.
Vehicle and Desktop Radios ....................................................................................................... 36
9.2
TEST EQUIPMENT REQUIRED ................................................................................................................ 37
10. AFTER SALES SERVICE ........................................................................................................................ 38
11. INDEX ......................................................................................................................................................... 39
12. APPENDICES ............................................................................................................................................ 40
12.1
APPENDIX A - MINE-WIDE SYSTEM TUNING (AMPLIFIER ATTENUATOR SETTINGS) .................................40
12.1.1.
Order of Tuning (for Gen-2 Amplifiers)...................................................................................... 40
12.1.2.
Configuration of Amplifier Attenuator Settings (for Gen-2 Amplifiers)...................................... 40
12.1.3.
Unplanned Topology Changes (for Gen-2 Amplifiers) ............................................................... 41
12.2
APPENDIX B - MINECOM SYSTEM DESIGN GUIDE DWG-41-00005-01 ................................................ 42
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 3 of 42
PBE Leaky Feeder System Manual
1. INTRODUCTION
The PBE Leaky Feeder System Manual contains procedures and information for authorized
personnel to work with a PBE VHF or UHF Leaky Feeder underground communications
system and all their components. PBE part numbers are listed in parentheses.
This document provides maintenance personnel with adequate information on the PBE Leaky
Feeder Systems and equipment to properly install, operate, and maintain the system, using
minimal test equipment.
This document relates to non-intrinsically safe systems only. PBE produces a separate
intrinsically safe communications system with appropriate documentation, and products.
1.1 Warnings and Warranty
Before using the PBE Leaky Feeder System ensure you have read this manual and any
accompanying operating manuals or datasheets for all components in the system.
To comply with PBE guidelines you must:

Install the system in accordance with the PBE System Design Guide
(DWG-41-00005-01 - Appendix B).

Avoid intermingling the PBE Leaky Feeder cable with any other electric cable,
where possible.

Maintain 2.5 m spacing between leaky feeder cable and blasting circuits.

Not modify or replace any PBE approved component with any other non- PBE
component.
To comply with MSHA guidelines you must also:

install the system in accordance with the PBE System Design Guide (S19…
Appendix A).

not intermingle the battery backup supply cable with Leaky Feeder cable or any
other electric cable.

de-energize the Model 1925 power supplies located on the surface when
underground mine power is de-energized.

charge the battery of the Model 1955 or 1953 backup battery supply on the
surface or in an area where permissible equipment is not required (fresh air).

locate the Leaky Feeder cable and all series connected components of the
system greater than eight feet from blasting circuits.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 4 of 42
PBE Leaky Feeder System Manual
1.2 Compliance
The PBE 01-20001, 01-20002 and S01-01 (previously 0200156, 02-00149, 03-00041) amplifiers comply with Part 15 of the
FCC Rules. Operation is subject to the following two conditions (1)
this device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that
may cause undesired operation.
MSHA Approval 23-A090003-0 for VHF systems
MSHA Approval 23-A090001-0 for UHF systems
Commonwealth of Pennsylvania Approval BFE23-10 for 01-20001,
01-20002 and GEN-2 UHF Leaky Feeder system
Commonwealth of Pennsylvania Approval BOTE for GEN-2 VHF
Leaky Feeder system
European Conformity approval for S01-01 (previously 02-00156, 0200149, 03-00041)
C-Tick approval for S01-01 (previously 02-00156, 02-00149, 0300041)
Canadian Standards Association (CSA) approval for S01-01
(previously 02-00156, 02-00149, 03-00041)
1.3 Frequency allocation
End-users are responsible for organizing all frequency allocation requirements. PBE assumes
end-users have already obtained current and appropriate licenses from their local authorities.
Please contact PBE or your local distributor if you have any questions regarding frequencies.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 5 of 42
PBE Leaky Feeder System Manual
2. GLOSSARY
AGC: Automatic Gain Control
Attenuation: gradual loss in intensity of a signal through a medium
Audio Bridge: a configurable switching matrix that selectively merges audio between
devices or channels
AWG: American Wire Gauge
Audio Bridge: a configurable switching matrix that selectively merges audio between
devices or channels
Bandwidth: range of radio frequencies
Base Station: non portable radio that can transmit with a high duty cycle (located in
the Communications Rack)
BDA: Bidirectional Line Amplifier
BNC: type of RF coaxial cable connector
dB: decibel
Downlink: the frequency that a duplex radio channel receives on (transmitted by
repeater)
Duplex: (a radio channel) when transmitting is on one frequency (uplink), but receives
on a different frequency (downlink). Used in conjunction with a repeater that receives
the uplink audio in real time and re-broadcasts it on a separate downlink frequency.
Voice Message Alerting: a device which plays a pre-recorded audio message onto a
desired radio channel in response to an external input
E & M ports: Ear and Mouth port – standard interface (found on repeaters, audio
bridges, telephone interconnects, page phone couplers, enunciators, VoIP bridges and
other equipment) for receiving and transmitting audio
Gen-1: First generation PBE amplifier (with attenuator settings common to both uplink
and downlink)
Gen-2: Latest generation PBE amplifier (with local diagnostics, and separate uplink
and downlink attenuator settings)
GEN-3: Third generation PBE amplifier (with remote diagnostics, and separate uplink
and downlink attenuator settings)
Inby: (American mining term) away from the shaft or mine entrance and therefore
toward the working face
Insertion Loss: the ratio of energy that enters a device compared to the energy that
exits a device
IP55: (Enclosure rating) protects against limited dust ingress and low pressure water
jets from any direction.
IS: Intrinsic Safety (Safe operation of electronic equipment in explosive atmospheres.
IS equipment won't ignite flammable methane gas or coal dust.)
MSHA: Mine Safety and Health Administration, an agency of the United States
Department of Labor which certifies IS accreditation.
Non-IS: Non Intrinsic Safety (not intrinsically safe e.g. Hard Rock)
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 6 of 42
PBE Leaky Feeder System Manual
N-T ype: A coaxial cable connector type
Outby: (American mining term) towards the shaft or mine entrance and therefore away
from the working face
PABX: Private Automatic Branch Exchange
Page Phone Coupler: a device which links audio between an existing wired intercom
system and a given radio channel
PLC: Programmable Logic Controller (a computer used to control electronic
processes)
Polyswitch: an electronic component that protects against short circuits
PTT: Push To Talk
Repeater: a device which receives the uplink audio in real time and re-broadcasts it on
a separate downlink frequency. Used in conjunction with duplex radio channels.
RF: Radio Frequency
Rx (RX): Receive
Saddle: PBE Leaky Feeder connector
Trunking: a concept by which a communications system can provide network access
to many clients by sharing a pool of lines or frequencies instead of providing them
individually
Telephone interconnect: a device which connects a given telephone line to a given
radio channel. Depending on configuration can receive and make calls remotely.
Tx (TX): Transmit
Uplink: the frequency that duplex radio channel transmits on (received by the
repeater)
VoIP bridge: a device which (via a TCP/IP computer network) connects audio of one
repeater to another remote repeater(s). A VoIP bridge creates a shared channel
allowing conversations between numerous facilities over very large distances.
VSWR: Voltage Standing Wave Ratio (used to measure the quality of the match of
transmission line between the antenna and the radio).
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 7 of 42
PBE Leaky Feeder System Manual
3. SYSTEM OVERVIEW
The PBE VHF and UHF Leaky Feeder Systems provide a comprehensive and reliable
communications system in underground mining and tunnel environments.
The PBE Leaky Feeder Systems acts as a distributed antenna system which consists of
the following components:













Head End Unit
Communications Rack Power Supply
Base Station Radio Receivers and Transmitters up to 32 channels
Above ground antenna system, to provide surface coverage
Leaky Feeder Cable
Bidirectional Amplifiers
Branch Units (Single and Dual)
Power Couplers
Termination Boxes
Joiner Boxes
Isolation Barrier
In-Line Barriers (IS systems only)
Field radio equipment.
Note: UHF amplifiers and repeaters are not compatible within a VHF system and vice
versa.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 8 of 42
PBE Leaky Feeder System Manual
Figure 1 shows an overview of the sequence of some of the components used in a typical
PBE Leaky Feeder System. Each PBE Leaky Feeder System will be tailored to specific site
requirements to provide the best radio coverage. The spacing, design layout and
components used will differ from this illustration. For a full System Design Guide see
Appendix B.
Figure 1: Overview of a v UHF Leaky Feeder System (IS)
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 9 of 42
PBE Leaky Feeder System Manual
3.1 Communications Rack
The Communications Rack is the hub of the Leaky Feeder
System and contains:








Head End Unit interfacing Leaky Feeder cable and
base radios
Leaky Feeder Power Supply and Battery Backup
Base Radio Equipment
Connections to surface coverage antenna system
Audio Bridge interfacing and controlling the audio
channels
Surge arresters
Repeaters
Isolators.
The above components, along with a circuit breaker panel, are
all housed in a standard or high IP rated rack.
3.2 Head End Unit
The Head End Combiner is the core of each PBE Leaky Feeder System. Its purpose is to
combine the RF outputs and inputs of the receivers. The Head End Combiner provides the
necessary interface between the base radios and the Leaky Feeder cable. See DAT-4100002-01 Head End Combiner Datasheet for details.
3.2.1. Head End Combiner (VHF: 02-00144, UHF: 03-00145, UHF: 03-00146)
Figure 2: Head End Combiner (02-00144)
3.3 Leaky Feeder Power Supply
The Leaky Feeder Power Supply is a critical component of the system, providing a regulated
12 volts DC to power all electronic devices in the system. The HEC works at 12, 24 and 48
V. The power supply is capable of handling large load fluctuations, without
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 10 of 42
PBE Leaky Feeder System Manual
failing. This Power Supply consists of an input AC voltage ranging from 105 - 125 VAC to a
DC voltage rated at 13.8 VDC with a current rating appropriate to the current drain of all
equipment included in the Communications Rack (Head End, base station radios, etc). The
power supply is equipped with a battery backup.
Battery(s) backup are supplied with the Leaky Feeder power supply to provide continuous
operation of the communications system under power failure. The power supply charges the
battery at 13.8 VDC when external power is available and switches automatically during a
power failure.
Figure 3 : Communications Rack Power Supply (example only)
3.4 Base Radio Equipment
The Leaky Feeder communication systems require dual port repeaters individually interfaced
into the Head End Unit. The repeaters can be configured for either conventional use or
trunking use by the addition of a T1810 Trunking Interface unit or similar.
The PBE Head End Unit can be expanded to accommodate from 1 to 32 operational channels,
which can be used for Voice and/or Data operation. Base station radio repeaters are colocated with the PBE Head End Unit in equipment housing, which can be either a 19 inch
rack cabinet, or a standard lock up cabinet. Operating frequencies for the UHF base radio
equipment are 435 - 490 MHz. Operating frequencies for the VHF base radio equipment are
151 – 157.5 MHz base transmit, 170 – 174.5 MHz base receive.
In most situations radio channels would be configured in a talk-through-repeater mode,
whereby all information received at the Head End would be automatically re-transmitted on a
different frequency. The radio channels can be configured as:
3.4.1. Voice Channels
Repeater (Talk-Through-Repeater)
Providing underground-to-underground, underground-to-surface communications (portableto-portable, vehicle-to-vehicle, vehicle-to-portable).
3.4.2. Data Channels
Repeater
Providing underground-to-underground, or underground-to-surface communications.
3.4.3. Telephone Interconnect Unit
This unit provides the interface between the audio connections of a voice radio
transmitter/receiver and a telephone extension of the site’s PABX system, or directly into the
public telephone network.
3.4.4. Voice Message Alerting
This unit provides the interface between the audio connections of a voice radio
transmitter/receiver and a PLC or personal computer to broadcast pre-recorded voice
messages (or alarm) over a voice channel when activated.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 11 of 42
PBE Leaky Feeder System Manual
3.5 Above Ground Antenna System
Surface coverage is dependent on a number of parameters, such as the surrounding terrain,
the height of antenna above ground, the gain of the antenna, the type and size of coaxial
cable used, the power output of the transmitter used (2/5/25/50 watts), etc. The Leaky Feeder
System can provide above ground communications by splitting the inputs and outputs of the
base radio receivers and transmitters, and coupling them to two or more conventional
antennas. Note: All licensing, regulations, and local frequency regulators must be consulted
before working with above ground antenna systems.
PBE individually review each customer’s requirements and recommends the most
appropriate antenna configuration.
Example of the equipment required for a Conventional Antenna System:
 One antenna - one for transmitting and one for receiving (due to the large split
between TX and RX frequencies).
 Low loss coaxial cables from the Communications Rack up to the antenna.
 Transmitter power divider (divides the transmitter output power 24/1 watt).
 24 watts up the antenna to the surface, 1 watt into the Head End Unit.
 Transmitter combiner (combines the output power of two or more transmitters into one
antenna).
Receiver splitter (combines two or more receivers into one antenna).
3.6 Audio Bridge (02-00138)
The Audio Bridge is used for interfacing and control of audio channels. The primary function
of the Audio Bridge is the combining and linking of repeaters, links and other audio sources
at remote sites. The audio wires from each Transmitter and Receiver are wired into the Audio
Bridge. The Audio Bridge is programmed to interlink the audio feeds of two or more of the
voice repeaters when activated by a remote wireless command or manually operated at the
Communications Rack.
This Audio Bridge has four or six independent 4 Wire plus E & M ports. Each of the ports is
provided with input level adjustment and output level adjustment. The E & M lines are fully
configurable for the various combinations of electrical protocol. The selection of these
electrical protocols is accessed via removal of the panel. An LED level meter and individual
LEDs for each Mute and PTT input or output provides a visual interface on the front panel.
3.7 Surge Arrester (24-00001)
Each Leaky Feeder cable should have a Surge Arrester installed immediately before the
Head End Unit to protect the unit from power surges.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 12 of 42
PBE Leaky Feeder System Manual
3.8 Repeater (VHF: 05-00074, UHF: 05-00086)
The Repeater receives audio from one channel in the uplink band and rebroadcasts it
simultaneously on one channel in the downlink band. Duplex radios are programmed to
receive on the downlink and automatically retune to broadcast on the uplink.
Refer to the Tait 7100 Repeater manual for more information.
3.9 Isolator (VHF: 24-00007, UHF: 24-00017)
The Isolator (found with each Repeater) permits the transmission of an RF signal in one
direction and attenuates a signal flowing in the opposite direction.
3.10
Model 1925 Power Supply (for IS Systems only)
Each 1925 (Power Supply) has two
independent 24 V, 1.25 A outputs.
Each of these may be used to power
two amplifiers and 1955 battery
backup units. This allows a total of
four amplifiers to be powered from a
single 120 V single phase source.
MSHA approval requires the two
output cables to maintain a 2”
separation once it leaves the power
supply.
AC power supplying all 1925 DC
power supplies must be de- energized
in a fan-down situation. This includes
any power supplies on the surface
supplying underground components.
3.11
•
•
•
•
•
Figure 4: Model 1925
Model 1953 and 1955 Battery Backup Unit (for IS Systems only)
Intrinsically safe when AC power is de-energized
Eliminates the need for expensive XP enclosures
Lightweight
Utilizes a durable Sure-Seal Interconnect for connection to the line amplifiers designed
for harsh environments
Allows amplifiers to continue operation when there is a break in the Leaky Feeder
cable
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 13 of 42
PBE Leaky Feeder System Manual
The PBE intrinsically safe 1953 and 1955
battery backup devices provide power for all
leaky feeder line amplifiers. They also allow
amplifiers to continue operation during system
maintenance (when depowering individual
section) or when there is a cable fault. For
more information please refer to the PBE
manual.
Figure 5: Model 1955
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 14 of 42
PBE Leaky Feeder System Manual
3.12
UNDERGROUND COMPONENTS
Leaky Feeder Cable
(20-00007)
(20-00008)
(20-00041)
Leaky Feeder Cable is used to
distribute power and RF signals
throughout
an underground
tunnel system.
Datasheet:
DAT-41-00007-02
Bidirectional Line
Amplifier
(02-00149)
(02-00156)
(03-00041)
Bidirectional Line Amplifiers are
used to restore the radio signals
as they pass along the leaky
feeder system.
Datasheet:
DAT-41-00003-01
Single Branch Unit
(02-00030)
Datasheet:
DAT-02-00030-01
Dual Branch Unit
(02-00029)
Datasheet:
DAT-02-00029-01
Power Coupler
Module
(02-00069)
Single Branch Units are used to
split an additional path, tunnel or
level from the main Leaky Feeder
cable.
Dual Branch Units are used to
split two additional paths, tunnels
or levels from the main Leaky
Feeder cable.
Power Coupler Modules are used
to inject power through Leaky
Feeder cable to power amplifiers.
Datasheet:
DAT-02-00069-01
Joiner Box
(02-00039)
Joins two ends of Leaky Feeder
cable together to prevent losses
and damage to the cable.
Datasheet:
DAT-02-00039-01
Termination Box
(02-00048)
Datasheet:
DAT-02-00048-01
MAN-41-00001-D
Termination Boxes are used to
seal the end of the cable and
protects against harsh mine
environments.
PBE Leaky Feeder System Manual
Page 15 of 42
PBE Leaky Feeder System Manual
4. LAYOUT
The PBE Leaky Feeder System acts as a Distributed Antenna System where the Leaky
Feeder Cable, together with a series of line components, can be joined together to provide
flexible mine-wide coverage. PBE products have been designed to be run down the left hand
side of a tunnel but can be installed either way. The PBE Leaky Feeder System has the ability
to scale and grow with a changing environment throughout any mine or tunnel. The system
has been specifically designed with the minimum of DC injection points.
For full details on layout please refer to DWG-41-00005-01 (Appendix B).
4.1 Component Layout
4.1.1. Head End Combiner
The Head End Combiner (HEC) is typically installed in a Communications Rack with other
equipment such as repeaters. The HEC is usually located on the surface or at some central
point within the mine. The HEC must be housed in a weather tight enclosure of building
exceeding IP55 rating. The first amplifier should be placed directly after the Communications
Rack.



4.1.2. Amplifiers
The arrow pointing to the base on each amplifier must point back to the
Communications Rack.
The spacing of the amplifiers will vary depending on the number and type of devices
installed between them.
Amplifiers should be installed the typical distance shown below.
Frequency
UHF (& VHF)
VHF


Minimum
270 m
360 m
Maximum
385 m
550 m
4.1.3. Single Branch Units
The arrow pointing to the base on each Branch Unit must point back to the
Communications Rack.
The cable length between amplifiers must be reduced by:
Frequency
UHF
VHF

Typical
350 m
500 m
Reduction
40 m
90 m
It is possible to install more than one Branch Unit between amplifiers as long as
distances are compensated for. Two Branch Units = 2 X 90 m cable length
reductions or 500 – 180 = 320 m cable distance between amplifiers in a VHF system.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 16 of 42
PBE Leaky Feeder System Manual
AMP


4.1.4. Dual Branch Units
The arrow pointing to the base on the Branch Unit must point back to the
Communications Rack.
The cable length must be reduced by:
Frequency
UHF
VHF
Tunnel
95 m
90 m
It is possible to install more than one Branch Unit between amplifiers as long as
distances are compensated for.
Tunnel
Communications Rack
AMP

Branch 1 & 2
160 m
180 m
AMP


4.1.5. Power Couplers
The arrow pointing to the base on the Power Coupler must point back to the
Communications Rack.
Each leg of a Power Coupler (PC) can support up to the following number of
amplifiers:
System
Voltage
12
24
48
VHF Amplifiers
(500 m spacing)
3 (5)
6 (10)
13* (19)
UHF (& VHF) Amplifiers
(350 m spacing)
4 (7)
7 (13)
15* (23)
*The figures quoted above are the theoretical maximum and may be reduced by system
issues. BDA-4 figures are in parenthesis.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 17 of 42
PBE Leaky Feeder System Manual

PCs should be DC isolated from each other.
4.1.6. Joiner Boxes
Up to four Joiner Boxes can be used between amplifiers.
Tunnel
Tunnel
Communications Rack

Tunnel
4.1.7. Termination Boxes
Termination Boxes must be used at the end of a cable run.
Communications Rack
Communications Rack

4.2 Layout Instructions
A Leaky Feeder System should be designed prior to installation to provide the most effective
communications. Your local dealer or PBE representative can help you with this process;
however the basic ideas are presented below.
1. Create a map where communications are required. Ensure a minimum separation
distance of 20 metres from different tunnel legs is maintained during cable layout at
all times to ensure adequate system performance.
2. On the map add inline devices starting at the Communications Rack and work your
way down the communications path. The first amplifier should be placed at the
Communications Rack. Add amplifiers and branch units as required. Remember to
follow the rules above for shortening cable lengths around branch units.
3. Add power couplers
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 18 of 42
PBE Leaky Feeder System Manual
4.3 Powering the system
The system can be powered in two ways, from the Head End Combiner and/or from a Power
Coupler. Large systems will need to use several Power Couplers. Each Power Coupler can
supply a certain number of amplifiers, stated above. Once the system layout has been
completed go back and insert Power Couplers as required, making sure the maximum number
of BDA per leg isn’t exceeded.
For best performance the Power Couplers should not have a DC connection between them.
To stop this, internal jumpers should be removed from certain points in the system. The last
amplifier to be powered from a Power Coupler should have its jumper removed. BU1, BU2
also have jumpers to block DC.
4.4 Unplanned Topology Changes
While strongly discouraged, a limited number of Branch Units may be inserted into an
existing properly balanced system.



If you believe an unused drive may become viable in the future it is best to add a
Branch Unit inline and adjust the system topology to match at initial design time.
o Insert 3 meters (10 feet) of cable and a Termination Box.
o Think about how you would like to power any amplifiers required from existing
or planned infrastructure. That way correct system balance is always
maintained.
If possible use a Single Branch Unit and make further branches after an amplifier.
Do not run additional amplifiers from the existing system, unless there is excess
power from PC available.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 19 of 42
PBE Leaky Feeder System Manual
4.5 Example layout diagram
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 20 of 42
PBE Leaky Feeder System Manual
5. INSTALLATION
5.1 Installation Guidelines
Connecting the leaky feeder cable to components and peripherals is simple, ensuring easy
assembly underground, as well as ongoing maintenance and system scalability, without the
need for specialized tools or skills.
It is essential to refer to the System Design Guide (DWG-41-00005-01 - Appendix B) when
modifying system topology and for device spacing. Care should be taken when installing a
leaky feeder cable in a mine and strict rules must be followed as to who is authorized to install
or make modifications.
Note: UHF amplifiers and repeaters are not compatible within a VHF system and vice versa.
5.2 Communications Rack Installation
The Communications Rack can be sited either above or below ground in a non-IS
environment.
5.2.1. Head End Combiner Mounting
The Head End Combiner and its ancillary equipment must be protected from the environment
by installing them in an IP rated rack enclosure or in a standard rack in a clean air-conditioned
room.
The Head End Combiner should be installed in the top of the enclosure. The Head End
Combiner is 3RU high and fits into any standard 19 inch rack. See section 5.3 for cable
connection details.
5.2.2. Head End Combiner Connections
To minimize loss from the Head End Combiner only use RG400 coaxial cable or better. Use
high quality BNC connectors to reduce losses and keep the coaxial cables as short as
possible. See section 5.3 for cable connection details.
Arterial Connections
The Leaky Feeder cables are connected to the Head End Combiner using four N-type
sockets. The Leaky Feeder cable must be connected with a ½ inch N-type coaxial plug
(10D-FB or 9005 type).
DC Power Connection DC Power is required for the Head End Combiner to function. It can
be connected via the rear panel using binding post type connectors (banana plugs) to the
correct 12/24 or 48 Volts DC power source. The power source must be suitably rated to handle
the current of the arterial ports. The Head End Combiner is protected by a M205 size 12.5
Amp slow blow fuse. The fuse can be removed with a quarter turn using a flat head
screwdriver.
If the POWER LED above the port on the rear panel is on, DC is present. It is recommended
that DC be switched off to the arterial while the Leaky Feeder cable is being connected.
Unused arterials should be protected with dust covers.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 21 of 42
PBE Leaky Feeder System Manual
RF connections
The Head End Combiner has eight BNC ports for transmitting (BASE TX) on Leaky Feeder
and eight BNC ports for receiving (BASE RX). Unused BNC ports must always be terminated
with 50 ohm terminators.
LOOP
The default configuration is to have the loop IN and OUT ports connected to each other as
shown below. The loop ports can be used to connect Head End Combiners together to
provide more channels, where OUT is the combined BASE TX and BASE RX signal and IN
connects to the arterial ports.
Figure 6: Head End Combiner (02-00144) – rear view
5.3 Leaky Feeder Cable Installation
Leaky feeder cable radiates 360 degrees from the cable and must be installed using the
following guidelines:

Where the leaky feeder cable cannot be supported at least every 3 meters by preexisting fixings, PBE recommend a catenary cable be installed to support it.

Leaky feeder cable shall be installed with a separation of at least 300 mm from
high voltage (>1100 Volts) cables.

VHF leaky feeder cable requires no separation from low voltage cable (<1100
Volts), where the cable is screened or steel wire armored, and is earthed.

UHF leaky feeder cable requires at least 100 mm clearance from low voltage cable
(<1100 Volts), where the cable is screened or steel wire armored, and is earthed.

For best coverage the leaky feeder cable shall be installed at least 4 meters above
the backfilled drive floor.

Where multiple cables are located on the same cable support system or catenary,
the leaky feeder cable must be located on the outside of the bundle so as to be
seen with the naked eye. UHF leaky feeder cable requires at least 100 mm
clearance from any conductive or grounded object.

When it is required to run leaky feeder cable in a cable tray, ensure leaky feeder
is located on the outside (underside) of the cable tray, within clear view. UHF leaky
feeder cable requires at least 100 mm clearance from any conductive or grounded
object.

Minimum bending radius of leaky feeder cable is 100 mm.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 22 of 42
PBE Leaky Feeder System Manual

The leaky feeder cable must be pulled off the drum using pull ropes attached
every 30 m. Alternatively the cable drum may be towed on a suitable trailer and
manually pulled off the drum directly to the final support structure or catenary.

Where a leaky feeder cable enters an inline device, a coil of cable no less than
one meter shall be made such that moisture is not allowed to run down the cable
into the cable gland, and enough cable is available so that terminations can be
made without need to install new cable or joints.

Where shotcreting operations are to be undertaken after leaky feeder installation,
leaky feeder cable shall be re-routed so that no shotcrete is allowed to collect on,
or drip onto, the leaky feeder cable. Leaky feeder cable must not be covered by
shotcrete or mesh for any part of the installation.

Where water is dripping from the backs of the tunnel, the cable must be either redirected to avoid the water, or be protected by a PVC (or similar non conducting)
splash guard which provides a minimum of 25 mm separation between the top of
the splash guard and the top of the radiating coaxial cable.

Where the leaky feeder cable is to be installed into shafts or other vertical rises,
the cable must be secured to a catenary cable (or similar) at intervals of not less
than 1000 mm.
Note: MSHA officials may require shotcreting of the leaky feeder cable in extreme situations
if the cable cannot be re-routed to avoid a specific area. If you must do this consider replacing
the cable with approved shielded coaxial cable (p/n 138-0006-009) prior to shotcreting or
adjust the gain of the inby and outby amplifiers to attempt to compensate for signal loss. If the
affected section is longer than 30 m (100 feet) between two amplifiers it may not be possible
to balance the signal loss.
5.3.1. Catenary recommendations
 Where catenary cable is used to support the leaky feeder cable, the catenary
supports must be installed such that the cable is not more than 150 mm from the
backs.

When a VHF leaky feeder cable is mounted on a catenary support it must not be
closer than 50 mm from the backs.

When a UHF leaky feeder cable is mounted on a catenary support it must be
installed such that the cable is not less than 100 mm from the backs. If the
catenary cable is conductive then the Leaky Feeder cable needs to be separated
by a further 100 mm from the catenary wire.

Catenary supports shall be installed at intervals of at least every 20 meters.
Spacing will decrease for bends and curves, but should not be less than 1 meter.

Catenary cable shall be stainless steel and shall have a minimum diameter of
3.5 mm (0.14 inch). The catenary cable shall be tensioned so that there is no
visible sag in the cable.

While maximum cable support separation is 3 meters (10 feet) when strapped to
a solid support, this is not always the case when a catenary wire is used. The
Leaky Feeder needs to be supported every 1.5 m (5 feet) when strapped to a
catenary wire to avoid it sagging when routed around corners or changes in height.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 23 of 42
PBE Leaky Feeder System Manual
5.4 Distribution Equipment (Components)

Distribution devices are to be installed on the cable support structure, or catenary.

The top cover of the device shall be installed so as to be seen easily from the
ground.

Amplifiers are to be installed with the Base pointing to the cable coming from the
Head End. Generally amplifiers are spaced every 500 meters (1640 feet) for a
VHF system using 5/8 inch mine quality coaxial cable and 350 meters (1148 feet)
for a UHF system.

When installing branches, ensure that the arrow on the circuit board is pointing to
the cable coming from the Head End. Also ensure that the opposite end of the
arrow is pointing to the main leg continuing through the branch unit. The main line
shall go straight through the device.

Leaky Feeder cable loops of at least 1 m are required on all terminations of
distribution devices (see Figure 7). Loops are to be secured to the cable support
structure or catenary with cable-ties.
Figure 7: Service loop

After the cable has been terminated into the distribution device, secure the cable
approximately 300 mm back from the device.

Lid screws and gland nuts should be manually tightened; mechanized tools should
not be used.

Where distribution devices are to be installed in shafts, a shield must be installed
over the device so as to protect the device from falling debris. The shield must
also cover the cable entry points of the device.

Each Power Coupler Complete is connected to a power supply. When installing a
Power Coupler ensure the local 1925 power supply has its AC inputs isolated.
Refer to the Section 5.3 General Component Connection for cable preparation
methods.
5.4.1. General Component Connection
There are two types of connections required with the PBE Leaky Feeder cable; one for
connecting Leaky Feeder cable to the Head End Unit and one for most of the other
components. They are described separately below.
The following instructions should be used for connecting most components (except for the
Head End Unit, covered below) within the PBE Leaky Feeder System:
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 24 of 42
PBE Leaky Feeder System Manual
Strip the Leaky Feeder cable to the dimensions outlined in the figure below.
Figure 8: Slicing dimensions
Separate the outer braid into two sets, eight conductors per side, and twist tightly together.
Figure 9: Twist braids into 2 strands
Place the gland nut, any plastic washers, and the rubber compression seal onto the cable and
insert the cable through the gland. Align the center conductor to fit into the center brass block
of the device. Ensure that the white center dielectric is hard up against the center brass block.
Figure 10: Attach to brass block
Tightly wrap each strand of outer conductors around the threaded studs of the ground
block, one each side of the cable.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 25 of 42
PBE Leaky Feeder System Manual
Figure 12: Tightly wrap conductors around studs
Tighten the two screws on the center block to clamp the center conductor into place. Place
the top ground block into place, and tighten the nuts onto the wrapped outer conductors to
clamp them onto the threaded studs.
Figure 13: Place the top ground block into place
Figure 14: Typical installation without shielding (terminal block not shown)
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 26 of 42
PBE Leaky Feeder System Manual
Figure 15: Typical installation with shielding (terminal block not shown)
5.4.2. Head End Combiner Connection or Isolation Barrier Connection (for IS
systems only)
When installing an Isolation Barrier, ensure that the ‘blue end’ is facing the hazardous area
and that the ground screw is properly grounded.
The following instructions should be used for connecting Leaky Feeder cable to the Head
End Combiner:
1. Strip the Leaky Feeder cable to the dimensions outlined in the figure below.
Figure 16: Slicing dimensions
2. Using a NP-10DFB, slide the clamp nut, metal washer, plain gasket, and metal
ferrule over the stripped cable as shown in Figure 17 and 18.
Figure 17
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 27 of 42
PBE Leaky Feeder System Manual
Figure 18
3. Fold back the cable braid over the ferrule, taking care not to overlap the braid
conductors. Trim off surplus braid.
4. Fit the male pin contact onto the centre conductor. Hold the cable and contact tightly
together and crimp/solder.
Figure 19
5. Press the sub-assembly into the body as far as possible and engage, then tighten the
clamp nut.
Figure 20
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 28 of 42
PBE Leaky Feeder System Manual
6. TUNING (for GEN-3 amplifiers)
As the topology of the mine changes over time, it becomes necessary to expand
communications coverage. Due to differences in cable and tunnel geometry, as well as cable
variance, it may be necessary to slightly adjust amplifier gains as new amplifiers are installed.
Note: It is recommended that DC is disconnected before working on equipment.
 Always use your PBE System Design Guide (S-19…) when expanding your
coverage to ensure proper device to device spacing.
 Due to differences in cable and tunnel geometry, as well as cable variance, it may
be necessary to slightly adjust amplifier gains as new amplifiers are installed.
6.1.1. Order of Tuning
When tuning a new system, identify the Main Routes of the mine.


The main decline or tunnel is a good place to start.
You should be able to identify the longest routes within a mine, and the sub
branches that feed from it.
The tuning (of amplifier gain adjustment) is dependant not only on the receiving amplifier but
also the transmitting amplifier.



It is therefore important to tune the main legs first, and any compromises to be
made on the shorter legs.
It is generally better to make a series of slight attenuator adjustments in several
places than a single large change in one place.
However, when connecting a new drive to a previously balanced main drive, the
main drive’s balance has priority.
6.1.2. Configuration of Amplifier Attenuator Settings
Downlink
Tuning of the downlink band is useful for future observations and fault finding the system.
Full tuning of the downlink band is optional, but recommended. Alternatively, please follow
the Minimum Tuning Procedure below.
Team Setup
Downlink tuning is performed starting from the closest amplifier to Head End and then
moving to each consecutive amplifier away from the Head End.

A single person is able to tune the downlink band.
Initial Device Setup
 Set the downlink attenuator settings of all amplifiers to no attenuation (0)
Minimum Tuning Procedure
 Whilst within view of the amplifier diagnostic LEDs, key up a mobile handset to
activate the downlink repeater.
 Ensure that all amplifiers have any one of the “Downlink AGC” LED lit during a
downlink transmission.
Full Tuning Procedure
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 29 of 42
PBE Leaky Feeder System Manual
The downlink band is perfectly balanced if all amplifiers have the +6 dB“Downlink RF
Power” LED lit.

Whilst within view of the amplifier diagnostic LEDs, key up a mobile handset to
activate the downlink repeater:
LED status
Attenuation
0 or +3 dB
Decrease the downlink attenuator setting.
+9 or +12 dB
Increase the downlink attenuator setting.
 Repeat this procedure until the +6 dB “Downlink AGC” LED lights.
 Repeat this procedure for each amplifier.
Caution on adjusting the attenuator settings
 Any adjustment will not be recognized until there is a quiet period. There should
not be any other in-band data or voice communications during the adjustment.
Uplink
Due to the variability of uplink signal powers and the lack of a mechanism to keep the uplink
amplifiers in AGC, it is necessary to tune the uplink band to minimize noise build-up during
periods of no data or voice communications.
Team Setup
Uplink tuning is performed from the furthest amplifier (away from Head End) and then
moving back towards the Head End.



A two-person team is required, one amplifier apart, both walking one amplifier
towards the Head End after each adjustment.
The first person stands 10 m past the furthest amplifier, away from the Head End,
ensuring he can still see the amplifier.
The second person stands at the next amplifier towards the Head End.
Initial Device Setup
 Set all uplink attenuator settings of all amplifiers to default (6).
Aim

The second person needs to adjust the uplink attenuator setting such that when
an uplink transmission is active, the “Uplink AGC” LED just turns on.
Test Method
 The first person keys up a mobile handset (for approx 10 seconds) so that the
second person can observe the state of their ‘Uplink AGC’ LED.
 When keyed up, the first person should see his “Uplink AGC” LED flash.
 Once the transmission completes, the second person will adjust the uplink
attenuator settings depending on their observation of the ‘Uplink AGC’ LED.
LED
OFF
ON
FLASHING
MAN-41-00001-D
Attenuation
attenuation needs to be decreased by one
step
attenuation should be increased by one step, to
ensure that it is at the highest setting for the
LED to be active.
attenuation should be increased by two steps.
PBE Leaky Feeder System Manual
Page 30 of 42
PBE Leaky Feeder System Manual




This process is repeated until the second person has adjusted the uplink attenuator
settings such that his “Uplink AGC” LED just comes on when the first person keys
up.
If the LED never comes on, then the uplink attenuator setting should be left at the
minimum attenuation setting (0).
Once tuning is achieved, re-seal the amplifiers and both men move up one amplifier
towards the Head End (maintaining one amplifier spacing).
This procedure is repeated until the second person reaches a previously calibrated
amplifier (usually on a main leg).
Caution on adjusting the attenuator settings
 Any adjustment will not be recognized until there is a quiet period. Therefore, it is
important that the second person wait for the first person to stop transmitting before
adjusting the uplink attenuator settings. There should not be any other in- band data
or voice communications during the adjustment.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 31 of 42
PBE Leaky Feeder System Manual
7. MAINTENANCE
A fully installed PBE system will operate indefinitely with the correct maintenance
procedures. The PBE Leaky Feeder System has been designed and developed for ease of
operation and maintenance in an underground mining environment. This section describes
the procedures that should be adopted by site management to ensure that the system
operates as designed during its lifetime.
The amplifier’s Local Diagnostics LEDs indicate the current state of the amplifier for ease of
maintenance.
The Sections on Layout and Installation should be consulted before making any changes to
the system. They describe how to design, install or make changes to the Leaky Feeder
System.
7.1 PBE Weekly Maintenance Checklist
Check
Test
Result
Amplifier Operation
Visually inspect the line
voltage and amplifier current
lights on all PBE Amplifiers
on site
LINE VOLTAGE should
indicate NORMAL or HIGH
Battery Supply
Operation
Visually inspect the PBE
1953 and 1955 units on site
DC IN should be green
Battery Backup Test
Remove AC power from all
1925 power supplies for 15
minutes and use the Leaky
Feeder System to
Communicate with miner at
the working section
Voice communication
should remain during the
battery back up test
AMP CURRENT should
indicate NORMAL or HIGH
BATTERY OUT should be
green
Note for IS systems: To maintain optimum battery backup capacity it is strongly
recommended to replace the 1953 or 195 and Communications Rack rechargeable
batteries with manufacturer approved batteries every two years.
The Leaky Feeder System must be installed and maintained to the MSHA approved system
diagram.
7.2 Operational Training
Training in the operation and maintenance of the system is critical to the successful ongoing
operation of the system. If site personnel are to use the PBE Leaky Feeder System
successfully, they must understand how it works. All new personnel commencing work should
cover the PBE Leaky Feeder System procedures as part of their induction training.

Training should include:

Operation of portable radios, vehicle radios, mini base stations, etc.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 32 of 42
PBE Leaky Feeder System Manual

Knowing where the radios will and will not work; all staff should be aware of the radio
coverage area.

Procedures for the use of the system: who to call in the case of an emergency, how to
report a fault in the system, warnings with respect to use of radios in the vicinity of electric
detonators, fuel dumps, gaseous areas, magazine, etc.
7.3 Maintenance Training
The training of maintenance staff should commence with the installation of the system.
Maintenance staff will learn more quickly and have a better chance of retaining that
knowledge if they are involved in the initial installation of the system. Training should be a
combination of both classroom and hands-on learning.
7.4 System Drawing
An accurate up to date system drawing with cable distances should be kept by the shift
maintenance engineer in charge of the system. The drawing should allow maintenance staff
to mark any changes to the system design (i.e. cable breaks, new branches and new power
centers). It should be the responsibility of the engineer in charge to check that the work has
been carried out correctly and amend the master copies of the system drawing when
necessary.
It is important that the manufacturer/supplier of the system be supplied with the up-to-date
system drawing when you contact them. This will allow them to assist/advise site staff in the
event of a fault with the system, ensuring a quick and speedy solution to the problem.
A generic System Design Guide can be found in Appendix B.
7.5 Documentation
Maintenance staff should have access to copies of the system documentation package, with
master copies being held by the engineer in charge. Documentation is available in both hard
copy and soft copy format.
7.6 Test Equipment Required
The test equipment required for troubleshooting the PBE VHF and UHF systems are as
follows:




standard handheld voice radio(s)
one multi-meter
(Optional) spectrum analyzer (Not IS approved, mine specific restrictions will
apply)
a range of approved hand tools, long cable-ties, insulating tape, cleaning rags.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 33 of 42
PBE Leaky Feeder System Manual
8. FAULT FINDING
8.1 Identify the Location of the Fault
Most failures are due to cable and water damage. Use Local Diagnostics or user reports to
determine where to start troubleshooting. When fault finding field equipment PBE recommend
taking spare units to quickly replace faulty or damaged equipment.
When a system fault is reported, i.e. voice coverage is poor (below the 640 level), first
determine that:

the reported fault is as described and that the person’s radio is not faulty or that
their battery is not flat.

the reported fault, affects all communications channels, and not just one single
channel. If it affects only one channel, the problem is most likely with the Head
End Communications Rack.
If the report is poor performance and not system failure, check:

the tuning of the system as per the tuning guide

that the leaky feeder cable is free of obstructions as per the installation guide.
Starting at the Communications Rack work your way through the system until you get to the
point that communications no longer function. Start your fault finding from this point.
IMPORTANT - if the coverage is poor in a lower level, it does not necessarily mean that the
fault is immediately above the area of poor or no coverage. The actual fault may be higher
up (closer to the Head End).
8.2 Head End Communications Rack fault
Available LED not on:
 Main fuse on the Head End has blown
 No power to Head End Combiner
Arterial cluster has no LEDs on:
 Main power switch has not been turned on
 None of the arterial switches are turned on
Fault LED on:
 A short circuit has occurred down the line. Find and repair short circuit before circuit
breaker.
8.3 Radio fault
If only one channel is affected, then the fault will most likely be at the Communications Rack
and not in the Leaky Feeder System.
8.4 System fault
If all radio channels are affected, carry out a systems check of the Leaky Feeder System.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 34 of 42
PBE Leaky Feeder System Manual
Before you start, ensure that:




both of the test portable radios work
radios are tuned to the same radio channel
the batteries must be at least 90% charged
You have an up-to-date system drawing showing the locations of the
devices.
If more than one amplifier has no LEDs on there could be a:

short circuit:
o
Remove DC isolating jumpers and reset Power Coupler to help isolate the
exact location
o
Visual inspection for cable damage and repair with a Joiner Box
o
Open inline devices to check for water logging, recommend replacement of
water logged devices. Always tighten glands to prevent water ingress.

cable cut:
o
Visual inspection, repair with a Joiner Box.
If one amplifier has no LEDs on:
 replace the amplifier, take it back to workshop for inspection
 if replacement amplifier doesn’t work, check for cable breaks or short circuits towards
the Power Coupler.
If one or more amplifiers LEDs flash on and off:
 most likely too many amplifiers are connected to the one PC. Review layout diagram.
Insert another Power Coupler.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 35 of 42
PBE Leaky Feeder System Manual
9. PREVENTATIVE MAINTENANCE
A preventative maintenance program will reduce the number of system faults caused by the
mine environment, as well as ensuring that any backup systems work when they are required.
Preventive maintenance can take many forms and is dependent on the size of the mine, the
size of system installed and the level of test equipment carried at the mine.
9.1 Program Maintenance
Programmed maintenance takes the form of monthly or quarterly visual and electronic testing
of the various components and a log kept of the results.
9.1.1. Communications Rack
 Test and measure RF Power levels of the Base Radio Transmitters and the Head
End Combiner.
 Batteries need to be replaced every two years.
 Visually inspect all equipment, cables and leads for deterioration.
 Check temperature levels inside the cabinet are <40 degrees C (104 degrees F).
 Check stand-by battery condition and clean battery tops. Measure and log the AC
and DC voltages. It is recommended that the system revert to the stand-by battery
back at least every three months to ensure that the batteries can operate the
system for the required period of time.
 Remove any build up of dust, dirt, insects, etc. inside the enclosure and clean any
vents or filters fitted to the enclosure.
 Log the results of all tests.
9.1.2. Down Line System
 Inspect the leaky feeder cable for damage.
 Ensure that the leaky feeder cable is secured every 3 meters (10 feet).
 Inspect all devices (amplifiers, branches, etc.) for damage, water ingress and
condensation.
 Wipe down all devices.
 Measure and log the DC voltage at every device.
 Log the results of all tests.
9.1.3. Portable Radios
 Test all functions of the portable radio.
 Charge/condition the battery pack.
 Visually inspect the radio, including all attachments, for damage or deterioration.
 Check the antenna for physical damage.
 Clean the radio.
 Test the portable radio to air.
 Log the results of all tests.
9.1.4. Vehicle and Desktop Radios
 Test all functions of the radio.
 Check the antenna for physical damage.
 Carry out VSWR check of the antenna.
 Visually inspect the radio, all leads and connections.
 Clean the radio.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 36 of 42
PBE Leaky Feeder System Manual
 If the radio is fitted with a stand-by battery, operate the radio from the stand-by
battery for at least 4 hours.
 Test to air.
 Log the results of all tests.
9.2 Test Equipment required
The minimum test equipment required is a handheld radio, at least 90% charged radio
battery, and a multi-meter.
Optional test equipment include a communications test set, manufacturers’ test kit(s) for
portable and vehicle radios, laptop, RF Wattmeter, and VSWR meter.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 37 of 42
PBE Leaky Feeder System Manual
10. AFTER SALES SERVICE
The information contained in this manual and the attachments is designed as a guide to assist
site staff in the maintenance and up-keep of the PBE VHF or UHF Leaky Feeder System. As
additional information becomes available it will be sent to you automatically. The information
is normally available in both hard and soft copy format.
Note: Before contacting us, please ensure that you have followed the support processes
listed above. You will need to provide the following information for us to respond to your
request:
1. Your contact details
 Name, Company, Location, etc.
2. Support details
 a clear understanding of the fault condition and description of any attempts
made to fix the problem
 an up-to-date system drawing
 measurements of the voltages of the devices in the area of the fault
 personally visited the area of the fault and verify the fault condition.
For further information, please visit: www.pbegrp.com or contact your local supplier for
servicing requirements.
MAN-41-00001-D
PBE Leaky Feeder System Manual
Page 38 of 42
PBE Leaky Feeder System Manual
11. INDEX
02-00030 ............................................15
02-00039 ............................................15
02-00048 ............................................15
02-00138 ............................................12
02-00144, 03-00145, 03-00146..........10
02-00149 ............................................15
02-00156 ............................................15
03-00041 ............................................15
05-00074 ............................................13
05-00086 ............................................13
20-00007 ............................................15
20-00008 ............................................15
20-00020 ............................................15
24-00001 ............................................12
24-00007 ............................................13
24-00017 ............................................13
Above Ground ....................................12
amplifier ..............................................16
Amplifier ...................................8, 15, 21
Antenna System .................................12
Audio Bridge .......................................12
Base Radio .........................................11
Base station........................................11
Bidirectional Line Amplifiers ............ See
Amplifier
Branch Unit.........................................16
Catenary .............................................23
Communications Rack ...........10, 21, 36
Connecting cable .............................. 24
Connecting components ....................24
Contact ...............................................38
Data channels ....................................11
Distribution Equipment .......................24
MAN-41-00001-D
Downlink Adjustments ....................... 42
Dual Branch Unit................................ 15
Fault finding ....................................... 34
Fault locating ..................................... 34
Head End Combiner .......................... 16
Head End Combiner Connections ..... 21
Head End Unit ................................... 10
Installation ......................................... 21
Isolator ............................................... 13
Joiner Boxes ...................................... 18
LAYOUT ............................................ 16
Leaky Feeder Cable .................... 15, 22
Leaky Feeder Power Supply ............. 10
Maintenance ................................ 32, 36
Portable Radios ................................. 36
Power Coupler ................................... 17
Power Coupler Module ...................... 15
Preventative Maintenance ................. 36
Radio fault ......................................... 34
Repeater ............................................ 13
Service ............................................... 38
Single Branch Unit ............................. 15
Stripping Leaky Feeder cable ............ 27
Surge Arrester ................................... 12
System Drawing ................................ 33
System fault ....................................... 34
Termination Box ................................ 15
Termination Boxes ............................. 18
Test Equipment ........................... 33, 37
Training .............................................. 32
Troubleshooting......... See Fault Finding
Uplink Adjustments ........................... 42
PBE Leaky Feeder System Manual
Page 39 of 42
PBE Leaky Feeder System Manual
12. Appendices
12.1
Appendix A - Mine-wide System Tuning (Amplifier Attenuator Settings)
As the topology of the mine changes over time, it becomes necessary to expand
communications coverage.
 Always use your Minecom System Design Guide (DWG-41-00005-01) when
expanding your coverage to ensure proper device to device spacing.
 Due to differences in cable and tunnel geometry, as well as cable variance, it may
be necessary to slightly adjust amplifier gains as new amplifiers are installed.

Always remember to close all enclosures as you leave each unit to prevent dust
build up.
12.1.1.
Order of Tuning (for Gen-2 Amplifiers)
When designing a system, and later tuning a new system, identify the “Main Routes” of
the mine.
 The main decline or tunnel is a good place to start.
 You should be able to identify the longest routes within a mine, and the sub
branches that feed from it.
The tuning (of amplifier gain adjustment) is dependant not only on the receiving amplifier
but also the transmitting amplifier.
 It is therefore important to tune the main legs first, and any compromises to be
made on the shorter legs.
 It is generally better to make a series of slight attenuator adjustments in several
places than a single large change in one place.
 However, when connecting a new drive to a previously balanced main drive, the
main drive’s balance has priority.
12.1.2.
Configuration of Amplifier Attenuator Settings (for Gen-2
Amplifiers)
As each amplifier is commissioned you should see the following on the Downlink RF
Power display:
 When adjusting downlink AGC, always adjust the amplifiers nearest the Head End
first, as the adjustments have a flow on affect.
1. During downstream communications you should see the Central “0 dB” LED light.
 You can force downstream communications by keying up a portable radio
on a mine wide channel.
2. The “-6 dB” LED should light when no one is communicating.
 If you don’t see this LED light periodically, confirm with someone at the
Head End that none of the repeaters are active (Red TX light).
 (depending on configuration) you are unlikely to hear communications on
any talk group other than your currently selected one.
 A repeater will become active the instant the person at the Head End
starts to speak on a radio.
 If you don’t see both step 1 and step 2, adjust attenuators up or down to achieve
these results.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 40 of 42
PBE Leaky Feeder System Manual

Note for the first one or two amplifiers into a mine, it may not be possible to prevent
the higher “+3 dB” or “+6 dB” LEDs from lighting, so just increase attenuation as far
as possible.
Uplink tuning is performed from the furthest amplifier (away from Head End) and then
moving outby (back towards the Head End).
 A two-person team is required, (one amplifier apart) both walking one amplifier
towards the Head End after each adjustment.
 The first person stands 10 m (33 feet) past the first amplifier (away from the Head
End), where he can still see it.
 When asked, the first person then keys up a portable radio for several seconds.
 While not mandatory, the first person should see the “uplink AGC Active” light
flash.
 It is important that the first person have quiet periods of no transmission, so the
second person can contact them and the amplifiers can calibrate themselves.
 The second person stands at the next amplifier towards the Head End.
 The goal of the second person is to adjust the uplink attenuator settings just
below the level where the “Uplink AGC active” LED comes on.
 Select an uplink attenuator level where the “Uplink AGC Active”
LED glows when the first person is transmitting.
 Then increase the attenuation so it no longer glows while the first
person is transmitting.
 Once this is achieved re-seal the amplifier furthest from the Head End and
both men move up one amplifier towards the Head End (maintaining one
amplifier spacing).
 This procedure is repeated until the first person reaches a previously calibrated
amplifier (usually on a main leg).
Note: the attenuator settings of an amplifier may be determined without opening the
case.
 Disconnecting and reconnecting external power (at Power Couplers) causes the
display to show the settings.
 A quite period (no communications) is required for the amplifiers to re-calibrate
themselves (you may have to wait for this to happen).
12.1.3.
Unplanned Topology Changes (for Gen-2 Amplifiers)
While strongly discouraged, a limited number of branch units may be inserted into an
existing properly balanced system.
 New deposits may be discovered and an unplanned branch may need to be
added.
 If you believe an unused drive may become viable in the future it is best to:
 Add a branch unit inline and adjust the system topology to match at initial design
time.
 Insert 3 meters (10 feet) of cable and a termination box.
 Think about how you would like to power any amplifiers required from existing
or planned infrastructure.
That way correct system balance is always maintained.
 If possible use a single branch unit, and make further branches after an amplifier.
 Do not run additional amplifiers from the existing system, unless there is excess
power from Power Coupler available.
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 41 of 42
PBE Leaky Feeder System Manual
Uplink Adjustments (for Gen-2 Amplifiers)

As stated earlier, the main (longer) legs have a higher priority when it comes to
correct system balance.
 You will probably have to decrease the attenuation on the amplifier inby from
the unplanned branch.
 Check the uplink AGC outby of the unplanned branch to see if additional gain
adjustment is required.
 Adjust the uplink AGC in the new drive and make a compromise.
Downlink Adjustments (for Gen-2 Amplifiers)

You will probably have to decrease downlink attenuation (by one stop) for the
amplifier outby from the unscheduled branch.
1. This may cause the higher LEDs on the amplifier outby to light during
downstream communications. This is not ideal, but is the best
compromise when an unscheduled branch needs to be included.
2. The goal is for the “0 dB” LED to light during downlink communications on
both amplifiers inby from unscheduled branch, however, it will still operate
when the other LEDs are on.
3. Once the above step is completed examine both amplifiers inby from
unscheduled branch to verify that they comply with Step 2.
4. You may have to also decrease these attenuation (by one stop) in order
to show the “0 dB” LED light during downlink communications.
5. If necessary, return to the amplifier inby from the branch and reduce the
downlink attenuation again.
6. It is preferable to decrease attenuation slightly in several places rather
than a great deal in one place.
12.2
Appendix B - Minecom System Design Guide DWG-41-00005-01
MAN-41-00001-D
Minecom Leaky Feeder System Manual
Page 42 of 42
2
1
3
4
5
6
7
8
Leaky Feeder Cable
Leaky Feeder cable is available in UHF (blue) and VHF (yellow) in 350 m drums (VHF is also available in 500 m drums). The cable drums are heavy and may require machinery and or multiple personnel to install. Cable strapping intervals should not
exceed 3 m. Leaky Feeder cable must be installed at least 300 mm from high voltage cables. The cable requires line of sight with portable radios and hence must not be installed behind metal piping, behind corrugated iron, steel or other conductive
surfaces. Yellow VHF cable can be strapped or cable-tied directly to a catenary wire. Blue UHF cable must be at least 100 mm from conductive material using spacers or hangers.
A
Joiner Box (JB)
Amplifiers (AMP)
Minecom inline Amplifiers restore radio signals to adequate retransmission levels. Amplifiers obtain DC power from an inline source
(Leaky Feeder cable). This power is initially obtained from the Communications Rack, however after a certain number of amplifiers,
Voltage Power Couplers are used to reintroduce power to the Leaky Feeder system.
The arrow on each amplifier must point back to the Communications Rack (located on the surface or underground). Amplifiers must be
A Joiner Box can be used to join the two ends of a Leaky Feeder cable where there has been a break. As Joiner Boxes introduce
very little loss to the system, up to 4 Joiner Boxes can be used between amplifiers (both 350 m and 500 m cables). The Joiner
Box provides an effective electrical connection with a very low signal loss (<0.5 dB).
Tunnel
AMP
Communications Rack
Communications Rack
Communications Rack
Tunnel
JB
230 m
170m
AMP
Tunnel 150 m
AMP
restore signals. More than one BU2 can used between amplifiers.
Voltage Power Couplers (PC)
AMP
AMP
PC
AMP
AMP
AMP
D
C
29/04/10
16/12/09
BU2
Tunnel
150 m
AMP
Branch 2
Termination Box (TB)
Termination Boxes (TB) are used to terminate the Leaky Feeder cable at all ‘end of runs’. Their main function is to ensure no signal
reflections are experienced in the system. At the same time the unit protects the cable from water and dust ingress as well as DC
and RF isolation.
350 m
Power
Station
TITLE
DWG-41-00005-01
Design
Guide Non IS
Removed
V from VBU System
& updated
images
New Template
AC 240 V In
SL
SL
HM JF 29/04/10
HM JF 16/12/09
D
-180
TB
DC (supplied upstream,
downstream o r both)
PC
110 m
Branch 2
60 m
TB
Communications Rack
AMP
-90
AMP
AMP
OR
AMP
125 m
TB
F
Communications Rack
AMP
E
BU2
Branch 1
60 m
AMP
Voltage Power Couplers (PC) are used to introduce external DC voltage into the Leaky Feeder System. As the leaky feeder cable can
cover many kilometers underground, over distance, voltage must be re-introduced to the system. Although PCs are AC powered, they
only introduce an adequate DC voltage to the system (12/24/48). The arterial distribution of power can be selected at the PC. Upstream
voltage, downstream voltage or both can be selected. Due to differences in amplifiers, system design and configuration, the specific
location and intervals of PCs will vary in all systems. A maximum of 5 amplifiers (4 for VHF) can be powered from a single PC.
NB: DC isolation rules apply.
-180
Tunnel
Branch 1
Branch 1
Communications Rack
D
Communications Rack
AMP
-90
C
AMP
BU1
Tunnel
-90
AMP
Dual Branch Units are used to split the signal into two branches (Branch 1 and 2). The cable that continues down the tunnel (or
decline) is called the ‘Tunnel Branch’. BU2s experience a measurable loss across all legs. Due to the loss associated in signal
splitting, the cable distance in the ‘Tunnel Branch’ will be reduced by approximately 90 m and 180 m in Branches 1 and 2. After
installing a BU2 the maximum physical separation between amplifiers is now reduced to 260 m in the ‘Tunnel Branch’ (maximum
distance 350 m – loss of 90 m = 260 m), 170 m along ‘Branch 1’, and 170 m along ‘Branch 2' (maximum distance 350 m – loss of
180 m = 170 m). Distances must be maintained to ensure the system can compensate for the introduced losses and adequately
Branch 1
150 m
BU1
JB
Tunnel
Communications Rack
110 m
AMP
JB
B
Dual Branch Units (BU2)
Single Branch Units (BU1) are used to split the cable (and signal) into another single branch. A nominal loss of 90 m is experienced on
both ‘tunnel’ and ‘branch’ legs, hence the separation between amplifiers is now reduced by 90 m. As the distance between amplifiers
is normally 350 m, inserting a Branch Unit will reduce the overall amplifier separation to 260 m. It is vitally important to ensure the
cable distance between amplifiers reflects the losses in the Branch Unit. Note: it is possible to install more than one Branch Unit
between amplifiers as long as loss distances are compensated for.
Communications
Rack
AMP
70 m
AMP
Single Branch Units (BU1)
C
50 m
Tunnel
AMP
Tunnel
350 m
AMP
AMP
Tunnel
B
350 m
AMP
Tunnel
installed every 350 meters of UHF cable (350/500 m for VHF). Separation distances greater than 350 m (350/500 m VHF) will result in
amplifiers not restoring the signal to an adequate level, and spacing too closely could potentially amplify noise. Both conditions, over
distance, will exponentially degrade radio signals.
Communications
Rack
A
E
Design
©
201
0
This
dra
win
g
and
all
intel
lect
ual
prop
erty
pert
aini
ng
to it
belo
ngs
to
TR
Pty
Ltd.
The
informati
on or any
part
thereof
contained
in this
drawing
is
confidenti
al and
shall not
be
reproduc
ed or
JF
copied in any form
without TR Pty Ltd
written
approval.
F
REV
DATE
CN
1
DESCRIPTION
2
BY CHK APR
3
DATE
DATE
09/2009
CHKD
SL
DATE
29/04/10
6 Joseph Street, Blackburn North, Vic 3130 Ph +61 3 9896 3000 Fx +61 3 9896 3099
SCALE
TITLE
DOC No.
REV
N\A
Minecom System Design Guide
SIZE
DWG-41-00005-01
A3
SHEET 1 OF 1
4
5
6
7
8
D