1
University of KwaZulu-Natal
School of Engineering
Power Systems 1 (ENEL 3PS H2)
Symmetrical Faults on Three-Phase Systems
Background
Because of the size and nature of practical power systems, faults are an operational fact of life – these may take the
form of open circuit or short circuit conditions and may be symmetrical (e.g. all three phases short circuited to
ground) or asymmetrical (e.g. one phase short circuited to ground or to another phase).
In the case of short circuit faults in particular, the currents that flow as a result of the fault depend on the internal
voltages of the synchronous generators in the system and the amount of impedance between these generators and the
fault.
Short circuit currents can exceed normal rated current by an order of magnitude or more, and if allowed to persist
can cause serious equipment damage (both thermal damage due to the heating associated with the large fault
currents and mechanical damage due to the high magnetic forces on conductors, windings and busbars carrying fault
currents).
Power system faults are detected and removed (cleared) by protective relays and circuit breakers respectively. The
power system engineers must therefore be able to calculate the prospective short circuit currents in each part of the
system in order to be able to design the necessary relay protection schemes and to determine the required current
interruption capability of the circuit breaker.
Per Unit System and Percentage Quantities
For fault (and other) calculations in power systems, the system variables and parameters are usually expressed in per
unit or percentage of some specified base value.
Both the per unit and percentage systems are methods of normalizing the variables and parameters of the system
such that they become dimensionless ratios. This has the advantage of greatly simplifying the calculations,
particularly in the presence of transformers.
Example:
Consider the example of an ideal transformer 6.6 kV / 380 V with 6000 V applied to its HV (primary) winding:
The voltage output from the LV (secondary) winding is then (6000x380)/6600 = 345.45 V.
The ratio of primary applied voltage to the rated voltage is 6000/6600 = 0.91 or 91%
Likewise the ratio o f actual secondary voltage to its rated value is 345.45/380 = 0.91 or 91%
Thus, in per unit, there is no change in the magnitude of the voltage from the primary side to the secondary side of
the transformer (the same is true for the magnitude of the primary and secondary currents when expressed in per
unit).
This is the main advantage of the per unit system for the analysis of the power systems: it effectively removes all the
different voltage levels from the analysis and greatly simplifies the manner in which transformers appear in the
analytical model of the system.
The per unit system also allows for greater insight into the system and allows for easier detection of obvious errors,
both in the value of the system parameters and during the calculations of system behavior. For example:
2
ο‚·
ο‚·
Similar ratings of machines have similar per unit values of the same parameter;
Because of the transformation in voltage levels from one part of the system to another, normal operating
currents (in amps) in one part of the system may be larger than fault currents (in amps) in another part of
the system at higher voltage.
Per unit values have an advantage over percentage values in that the product of two values expressed in per unit is
also in per unit; by contrast, the product of two values in percentage must be divided by 100 to obtain an answer in
percentage.
Advantages of pu System
1.
2.
3.
4.
5.
6.
The ordinary parameters (current , impedance, losses etc.) vary considerably with the variation of physical size,
terminal voltage, power rating, etc., while the per unit parameters are independent of these quantities over a
wide range of the same type of apparatus. In other words, the per unit impedance values for apparatus of like
ratings lie within a narrow range.
The chance of confusion between line and phase values in three-phase balanced system is reduced. A per unit
phase quantity has the same numerical value as the corresponding per unit line quantity regardless of the threephase connection whether star or delta.
The impedances of machines are specified by the manufacturers in terms of per unit values.
The per unit impedance referred to either side of a single phase transformer is the same.
The per unit impedance referred to either side of a three-phase transformer is the same regardless of the threephase connections whether they are delta-delta, star-star, or delta-star.
The computational effort in power systems is very much reduced with the use of per unit quantities. Usually, the
per unit quantities being of the order of unity or less can easily be handled with a digital computer. Manual
calculations are also simplified. Per unit quantities simplify theoretical deductions and give them more
generalized forms.
Base Value
In order to express each variable in the system in per unit, we need to know the base value of that variable.
By definition, base or unit impedance (in ohms) is that value of impedance which will have unit volt drop across it
when unit current flows through it.
From the above definition, the base value of a component in the system is defined in terms of its rated current and
rated voltage, and hence in terms of its rated kVA. Because the kVA and line-to-line voltage ratings of a component
are most readily available, the base values of current and impedance are typically calculated from these rated values.
Hence,
πΌπ‘π‘Žπ‘ π‘’ =
π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’
A where π‘˜π‘‰π‘π‘Žπ‘ π‘’ is the rated line voltage in kV, and π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’ is the total three phase kVA rating.
√3 × π‘˜π‘‰π‘π‘Žπ‘ π‘’
And then π‘π‘π‘Žπ‘ π‘’ =
π‘˜π‘‰π‘π‘Žπ‘ π‘’ × 103
√3 × πΌπ‘π‘Žπ‘ π‘’
Ω
Alternatively, if πΌπ‘π‘Žπ‘ π‘’ is not known, then multiplying the numerator and denominator of the above expression by
√3 × π‘˜π‘‰π‘π‘Žπ‘ π‘’ yields
π‘π‘π‘Žπ‘ π‘’ =
(π‘˜π‘‰π‘π‘Žπ‘ π‘’ )2 × 103
π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’
Ω
From the base values so defined, then
3
𝐼𝑝𝑒 =
π‘Žπ‘π‘‘π‘’π‘Žπ‘™ π‘π‘’π‘Ÿπ‘Ÿπ‘’π‘›π‘‘ (𝐴)
𝑉𝑝𝑒 =
π‘Žπ‘π‘‘π‘’π‘Žπ‘™ π‘£π‘œπ‘™π‘‘π‘Žπ‘”π‘’ (𝑉)
π‘π‘Žπ‘ π‘’ π‘π‘’π‘Ÿπ‘Ÿπ‘’π‘›π‘‘ (𝐴)
=
πΌπ‘Žπ‘π‘‘π‘’π‘Žπ‘™
=
π‘‰π‘Žπ‘π‘‘π‘’π‘Žπ‘™
π‘π‘Žπ‘ π‘’ π‘£π‘œπ‘™π‘Žπ‘”π‘’(𝐴)
𝑍𝑝𝑒 =
𝑍Ω
π‘π‘π‘Žπ‘ π‘’
πΌπ‘π‘Žπ‘ π‘’
π‘‰π‘π‘Žπ‘ π‘’
𝐼% = 100 × πΌπ‘π‘’
𝑉% = 100 × π‘‰π‘π‘’
𝑍% = 100 × π‘π‘π‘’
Conversion of Impedance Units
Manipulation of the above expressions for impedance in ohms and per unit yields the following two relationships for
converting impedances between real units (ohms) and per unit
𝑍𝑝𝑒 =
𝑍Ω =
𝑍Ω ×π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’
π‘˜π‘‰π‘π‘Žπ‘ π‘’ 2 ×103
𝑍𝑝𝑒 ×(π‘˜π‘‰π‘π‘Žπ‘ π‘’ )2 ×103
π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’
Choice of Base Values
As seen above, when considering individual pieces of power system plant, the per unit values of parameters and
variables are defined in terms of the kVA ratings of the plant itself. However, in realistic system there will be
components in the system with different kVA ratings, as well as components (e.g. transmission lines and cables) for
which kVA rating is not normally quoted.
When analyzing systems of several components, it is therefore, necessary to convert all per unit values to a common
base, that is to recalculate the per unit values of each component using the same, common values of base kVA. This
common base can be completely arbitrary, but it is more efficient to choose a common value of base kVA that
coincides with the actual kVA ratings of as many pieces of equipment in the system as possible.
When changing from one base to another
𝑍𝑝𝑒 |𝑛𝑒𝑀 π‘π‘Žπ‘ π‘’ = 𝑍𝑝𝑒 |π‘œπ‘™π‘‘ π‘π‘Žπ‘ π‘’ ×
𝑛𝑒𝑀 π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’
π‘œπ‘™π‘‘ π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’
𝑍𝑝𝑒 is not a function of voltage and therefore does not vary from one side of a transformer to another. πΌπ‘π‘Žπ‘ π‘’ and
π‘˜π‘‰π‘π‘Žπ‘ π‘’ are functions of each other and of π‘˜π‘‰π΄π‘π‘Žπ‘ π‘’ .
By contrast, when working in actual units (ohms) impedances are transformed from one voltage level to another as
follows
𝑍𝑝𝑒 |𝑛𝑒𝑀 π‘π‘Žπ‘ π‘’ = 𝑍𝑝𝑒 |π‘œπ‘™π‘‘ π‘π‘Žπ‘ π‘’ × (
𝑛𝑒𝑀 π‘˜π‘‰π‘π‘Žπ‘ π‘’ 2
)
π‘œπ‘™π‘‘ π‘˜π‘‰π‘π‘Žπ‘ π‘’
Three Phase Short Circuits
In such types of faults all the three phases are short circuited to each other and often to earth also. Such faults are
balanced and symmetrical in the sense that the system remains balanced even after the fault. A three phase short
circuit occurs rarely but it is the most severe type of fault involving largest currents. For this reason, the balanced
short circuit calculations are performed to determine these large currents to be used to determine the rating of the
circuit breaker.
Symmetrical short circuit current levels (or fault levels) vary from one point of the power system to another; short
circuit levels also vary with the amount of generating plant and with the amount of load on the system at any time.
4
These fault levels are usually expressed in MVA as follows:
𝑀𝑉𝐴 𝑙𝑒𝑣𝑒𝑙 = √3 × π‘†π‘¦π‘ π‘‘π‘’π‘š π‘˜π‘‰ × π‘ β„Žπ‘œπ‘Ÿπ‘‘ π‘π‘–π‘Ÿπ‘π‘’π‘–π‘‘ π‘π‘’π‘Ÿπ‘Ÿπ‘’π‘›π‘‘ × 10βˆ’3
At any given time, the short circuit levels are greatest at the busbars of the largest generating station or possibly at
the busbars of a station forming the junction between several such stations. Conversely, the short circuit levels are
lower at points in the system that are electrically far from the generating stations.
For the safety of switchgear, which has only a limited current interrupting (or rupturing) capacity, fault levels must
be limited; to this end it may be necessary to insert series reactors in lines or busbars and to pay special attention to
the design of generators. However, the use of high speed automatic voltage regulators on generators has become
widespread because of the positive impact these controllers have on transient stability; their use however contributes
to increased fault levels.
Current Limiting Reactors
Fault currents may be large enough to cause damage to the line and other equipment of a power system network.
The interrupting capacities of the circuit breakers to handle such currents would also be very large. Fault current is
limited by the system reactance, which includes the impedance of the generators, transformers, lines and other
components of the systems. Modern generators have reactance large enough to limit the fault currents. However, old
generators have low values of reactance. The fault levels increase with the growth of the interconnected system.
Therefore, if the system is large enough or some of the generators are old, the fault current can be kept within safe
limits by increasing the system reactance. This is done by connecting current limiting reactors at strategic points in
the system. Current limiting reactors are coils used to limit current during fault conditions. Such reactors have large
values of inductive reactances and low ohmic resistances.
Location of Reactors
Current limiting reactors may be connected (a) in series with each generator (b) in series with each feeder (c)
between busbar sections.
Generator Reactors
When the reactors are connected in series with each generator, they are known as generator rectors.
Fig. 1: Generator reactors
The Fig. 1 shows the location of generator reactors. The feeders are connected directly to the busbars. Modern
generators are designed to have sufficiently large reactance to protect them even in dead short circuits at their
terminals. Thus, current limiting reactors may only be used old generators having low values of reactance. Generator
reactors suffer from the following drawbacks.
1.
2.
The full load current flowing in the reactor under normal operation produces a constant voltage drop and
power loss in each reactor.
If a busbar or feeder fault occurs close to the busbars, the voltage at the busbar drops to a low value with
the result that generators may lose synchronism and the supply may be interrupted.
5
Feeder Reactors
When the reactors are connected in series with each feeder, they are known as feeder reactors as shown in Fig. 2.
Fig. 2: Feeder reactors
These are two main advantages of feeder reactors.
(i)
(ii)
If there is a fault on any feeder, the voltage drop in its reactor will not affect the busbar voltage, therefore,
there is a little chance for the generator to loose synchronism.
The fault on one feeder will not affect other feeders.
The feeder reactors have the following limitations:(i)
(ii)
(iii)
There is constant voltage drop and power loss in each reactor during normal operating conditions.
If a fault occurs at the busbars, no protection is provided to generators.
If the number of generators is increased, the sizes of the feeder reactors should also be increased.
Busbar Reactors
Generating station busbars are sectionalized and reactors are connected between sections which is the most common
method of connection of reactors between generator busbars. Two methods of reactor connections are used which
are: (a) ring main system (b) tie-bus system. The ring main system and tie-bus system are shown in Fig. 3 and Fig. 4
respectively.
Fig. 3(a): Ring main system
Fig. 4: Tie-bus system
Fig. 3(b): Ring main system
Under normal operating conditions each generator supplies feeder connected to its own section, and there will be no
current through the reactors. Thus, there is no voltage drop or power loss in the reactor during normal operation. The
busbar reactors localize the faults. For example, if a fault occurs on a feeder, only that busbar section is affected to
which it is connected. The other sections continue to operate normally. In the ring system, the current transferred
between two sections flows through two paths in parallel, whereas in tie-bus system, the current flows through two
reactors in series. However, they carry twice as much current as the ring reactors. The tie-bus system is more
flexible than the ring system. With the tie-bus arrangement extra generator may be added to the system without
addition of extra circuit breakers or increasing the existing reactance.