Download Engineering Guide - IEC61850

Document related concepts
no text concepts found
Transcript
(QJLQHHULQJJXLGH
,(&6WDWLRQ
-RRSZEXMSR
JVSQ
%&&
Engineering guide
IEC 61850 Station
About this manual
Document No: 1MRK 511 193-UEN
Issued: July 2006
Revision: -
© Copyright 2006 ABB. All rights reserved.
COPYRIGHT
WE RESERVE ALL RIGHTS TO THIS DOCUMENT, EVEN IN THE EVENT THAT A PATENT IS
ISSUED AND A DIFFERENT COMMERCIAL PROPRIETARY RIGHT IS REGISTERED. IMPROPER
USE, IN PARTICULAR REPRODUCTION AND DISSEMINATION TO THIRD PARTIES, IS NOT
PERMITTED.
THIS DOCUMENT HAS BEEN CAREFULLY CHECKED. HOWEVER, IN CASE ANY ERRORS ARE
DETECTED, THE READER IS KINDLY REQUESTED TO NOTIFY THE MANUFACTURER AT THE
ADDRESS BELOW.
THE DATA CONTAINED IN THIS MANUAL IS INTENDED SOLELY FOR THE CONCEPT OR
PRODUCT DESCRIPTION AND IS NOT TO BE DEEMED TO BE A STATEMENT OF GUARANTEED PROPERTIES. IN THE INTERESTS OF OUR CUSTOMERS, WE CONSTANTLY SEEK TO
ENSURE THAT OUR PRODUCTS ARE DEVELOPED TO THE LATEST TECHNOLOGICAL STANDARDS. AS A RESULT, IT IS POSSIBLE THAT THERE MAY BE SOME DIFFERENCES BETWEEN
THE HW/SW PRODUCT AND THIS INFORMATION PRODUCT.
Manufacturer:
ABB Power Technologies AB
Substation Automation Products
SE-721 59 Västerås
Sweden
Telephone: +46 (0) 21 34 20 00
Facsimile: +46 (0) 21 14 69 18
www.abb.com/substationautomation
Contents
Chapter
Chapter 1
Page
Introduction ..................................................................... 1
Introduction to the IEC 61850 Station Engineering guide.................... 2
About the complete set of manuals for an IED ............................... 2
About the IEC 61850 Station Engineering guide ............................ 3
Intended audience .......................................................................... 3
Related documents......................................................................... 4
Revision notes ................................................................................ 4
Chapter 2
IEC 61850 station engineering ....................................... 5
Station engineering in IEC 61850 ........................................................ 6
Engineering process in IEC 61850 ................................................. 6
Designation model of IEC 61850 ......................................................... 9
IEC 61346 designation model used for IEC 61850....................... 12
Substation Configuration description Language (SCL)...................... 14
The Substation section ................................................................. 16
The communication section .......................................................... 20
The IED section ............................................................................ 22
Signal engineering ........................................................................ 24
Buffered Report Control Block (BRCB) ................................... 25
GOOSE Control Blocks (GoCB) .............................................. 29
Chapter 3
IEC 61850 Station configuration tasks ........................ 31
IEC 61850 Station configuration tasks............................................... 32
Chapter 4
PCM 600 and CCT tool set for station engineering.... 35
PCM 600 and CCT tool set for station engineering ........................... 36
PCM 600 views and windows ............................................................ 37
PCM 600 the toolbar and the mouse ............................................ 41
PCM 600 options for operation .......................................................... 44
PCM 600 access .......................................................................... 44
Connectivity package support for PCM 600 ...................................... 50
PCM 600 Set up communication link per IED 670............................. 52
PCM 600 Set up communication link per Generic IEC 61850 IED 52
CCT views and windows.................................................................... 53
The toolbar and the mouse........................................................... 56
Spreadsheet features ................................................................... 57
CCT Column visibility control........................................................ 61
CCT options and features.................................................................. 64
Execution mode ............................................................................ 65
Logger options .............................................................................. 65
Contents
Navigator structure options........................................................... 66
Chapter 5
Set up a project in PCM 600 ......................................... 69
Set up a project in PCM 600 .............................................................. 70
Managing projects in PCM 600 ......................................................... 71
Chapter 6
Set up a project in CCT ................................................. 75
Managing projects in CCT ................................................................. 76
Import/export station.SCD files .......................................................... 79
Import station.SCD file.................................................................. 79
Export station.SCD file.................................................................. 80
Import/export ied.ICD files ................................................................. 81
Import ied.ICD file ........................................................................ 81
Import of a client IED via CCT into a station project ..................... 82
Export ied.ICD file......................................................................... 83
Chapter 7
Station configuration with PCM 600 ............................ 85
Set up a substation for IEC 61850 ..................................................... 86
Naming conventions for IEC 61850 .............................................. 87
PCM 600 selection of an IED........................................................ 89
PCM 600 Generic IEC 61850 IED ................................................ 91
Set up communication for IEC 61850 ................................................ 94
Import/Export station.SCD files ......................................................... 96
ied.CID file generation for IED 670 ............................................... 98
Chapter 8
Signal engineering with CCT........................................ 99
IEC 61850 Attribute Editor ............................................................... 100
Data set engineering........................................................................ 102
Predefined DataSet .................................................................... 105
BRCB engineering ........................................................................... 106
GoCB engineering ........................................................................... 113
About this chapter
Chapter 1
Introduction
Chapter 1 Introduction
About this chapter
This chapter explains concepts and conventions used in this manual and provides information
necessary to understand the contents of the manual.
1
Introduction to the IEC 61850 Station
Engineering guide
Chapter 1
Introduction
1
Introduction to the IEC 61850 Station Engineering
guide
1.1
About the complete set of manuals for an IED
The user’s manual (UM) is a complete set of five different manuals:
Application
manual
Technical
reference
manual
Installation and
commissioning
manual
Operator´s
manual
Engineering
guide
en06000097.vsd
The Application Manual (AM) contains application descriptions, setting guidelines and setting
parameters sorted per function. The application manual should be used to find out when and for
what purpose a typical protection function could be used. The manual should also be used when
calculating settings.
The Technical Reference Manual (TRM) contains application and functionality descriptions
and it lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The technical reference manual should be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal
service.
The Installation and Commissioning Manual (ICM) contains instructions on how to install
and commission the protection IED. The manual can also be used as a reference during periodic
testing. The manual covers procedures for mechanical and electrical installation, energizing and
checking of external circuitry, setting and configuration as well as verifying settings and performing directional tests. The chapters are organized in the chronological order (indicated by
chapter/section numbers) in which the protection IED should be installed and commissioned.
The Operator’s Manual (OM) contains instructions on how to operate the protection IED during normal service once it has been commissioned. The operator’s manual can be used to find
out how to handle disturbances or how to view calculated and measured network data in order
to determine the cause of a fault.
The IED 670 Engineering guide (EG) contains instructions on how to engineer the IED 670
products. The manual guides to use the different tool components for IED 670 engineering. It
also guides how to handle the tool component available to read disturbance files from the IEDs
on the basis of the IEC 61850 definitions. The third part is an introduction about the diagnostic
tool components available for IED 670 products and the PCM 600 tool.
2
Introduction to the IEC 61850 Station
Engineering guide
Chapter 1
Introduction
The IEC 61850 Station Engineering guide contains descriptions of IEC 61850 station engineering and process signal routing. The manual presents the PCM 600 and CCT tool used for
station engineering. It describes the IEC 61850 attribute editor and how to set up projects and
communication.
1.2
About the IEC 61850 Station Engineering guide
The Engineering guide IEC 61850 Station contains the following chapters:
•
•
•
•
•
•
•
1.3
The chapter “IEC 61850 station engineering” is not an introduction to the
IEC 61850 standard, but gives a short definition and task description for those
parts of the standard needed to do station engineering and process signal routing.
The chapter “IEC 61850 Station configuration tasks” gives a description of the
principle tasks and steps to do station and signal engineering.
The chapter “PCM 600 and CCT tool set for station engineering” presents the
two tools used for IEC 61850 station engineering. It illustrates views and windows and describes CCT options and features. It also describes how to set up a
communication link between PCM 600 and the IED.
The chapter “Set up a project in PCM 600” describes how to set up and manage
a project in the PCM 600 tool.
The chapter “Set up a project in CCT”describes how to set up and manage the
CCT tool and the import/export procedure of files.
The chapter “Station configuration with PCM 600” describes how to set up a
substation for IEC 61850 and how to set up communication for IEC 61850, in order to fulfil the IEC 61850 requirements for signal engineering.
The chapter “Signal engineering with CCT” describes the IEC 61850 attribute
editor, how the data objects in IEC 61850 are configured to data sets and engineering of the different control blocks.
Intended audience
General
This manual addresses system engineers, project engineers involved n the engineering process
for a project, installation and commissioning personnel, who use technical data during engineering, installation and commissioning, and in normal service.
Requirements
The system engineer must have a thorough knowledge of protection and/or control systems, protection/control equipment, protection/control functions and the configured functional logics in
the IED 670 devices. The installation and commissioning personnel must have a basic knowledge in the handling electronic equipment.
3
Introduction to the IEC 61850 Station
Engineering guide
1.4
Chapter 1
Introduction
Related documents
Documents related to the PCM 600 and CCT tool set
Identity number
Connection and Installation components
1MRK 013 003-BEN
Test system, COMBITEST
1MRK 512 001-BEN
Accessories for IED 670
1MRK 514 012-BEN
Getting started guide IED 670
1MRK 500 065-UEN
SPA and LON signal list for IED 670
1MRK 500 075-WEN
IEC 61850 Data objects list for IED 670
1MRK 500 077-WEN
Generic IEC 61850 IED Connectivity package
1KHA001027–UEN
Protection and Control IED Manager PCM 600 Installation sheet
1MRS755552
Engineering guide IED 670 products
1MRK 511 179–UEN
Latest versions of the described documentation can be found on www.abb.com/substationautomation
1.5
4
Revision notes
Revision
Description
-
First release
About this chapter
Chapter 2
IEC 61850 station engineering
Chapter 2 IEC 61850 station
engineering
About this chapter
This chapter gives a short definition and task description for those parts of the IEC 61850 standard which are needed to do station engineering and process signal routing. A reference to the
IEC 61850 parts and clauses is given where needed. The reason for this chapter is to have the
common platform about the tasks and the used wording. It can and will not be an introduction
to the standard.
5
Station engineering in IEC 61850
1
Chapter 2
IEC 61850 station engineering
Station engineering in IEC 61850
The way of engineering and configuring a station according to IEC 61850 standard is described
in part 6 of the standard. The title of this part is: “Configuration description language for communication in electrical substations related to IEDs”
This chapter contains some explanations about the definitions made by the standard. They may
be requested to get a better understanding and as a reference when the different engineering steps
made with the tools PCM 600/CCT are described. It is expected, recommended that the reader
has a general knowledge about the IEC 61850 standard and especially of the parts 6 and 7.
1.1
Engineering process in IEC 61850
IED Capablity
ied.ICD
System Sepcification
stat.SSD
System
Configurator
Station
DB
Vendor B
IED
DB
Vendor A
Vendor C
Substation Configuration
stat.SCD
ied.ICD
IED
Configurator
Vendor A
IED
Configurator
Vendor B
IED
Configurator
Vendor C
Configured IED
ied.CID
IED
HSI
Vendor A
IED
Control
Vendor C
SA
Gateway
IED
Protection
Vendor B
IED
Control
Vendor C
IED
NCC GW
Vendor B
IED
Protection
Vendor B
Substationn
en06000105.vsd
Figure 1:
6
IEC 61850–6: Station engineering process
Station engineering in IEC 61850
Chapter 2
IEC 61850 station engineering
The standard defines two tools and four file types for station engineering. The above figure
shows these tools and files in their relation. In the ideal situation from top down the engineering
process and the used tools and files have the following relation:
•
•
•
•
System Configurator tool (SC)
- Import a station.SSD file when available. If not continue with the next step
- Import the ied.ICD files of the products which will be used
- When no station.SSD file is available, configure the primary equipment
(Busbar, Transformer, Apparatus, connections etc. to voltage level and bays.
Make a single line diagram of the station. Remark: This step and the next one
is not direct needed to do signal engineering in a station for IEC 61850 based
communication. A minimum configuration of the plant structure is requested
only.
- Place the Logical nodes to the primary equipment they belong to within a
bay.
- Configure the communication with their subnetworks.
- Place the physical IEDs in the communication subnetwork and define the access points per IED
- Place the IEDs with their Logical devices and Logical nodes in the plant
structure
- Do signal engineering. Configure DataSets, Control Blocks and link the
communication path between server and clients or between servers
(GOOSE).
- Export the complete station configuration in the station.SSD file for further
use by the various IED Configurator tools
IED Configurator tool (IC)
- Import the station.SCD file and extract the information valid and used for
each used IED.
- Do additional engineering steps when necessary (vendor specific)
- Check for received GOOSE messages and do GOOSE signal marshalling
when necessary
- Prepare the ied.CID file and download the file to the IED
- Precondition in this case: The IED is fully engineered to its function in the
project. The ied.ICD file was exported with the complete configuration to the
SC tool as described above.
SSD file = System Specification Description file
- This file describes the single line diagram of the substation and the required
Logical nodes. It is expected that the utility is able to support the project with
such a file.
ICD file = IED Capability Description file
- This file describes the full capability in Logical nodes and Logical devices of
an IED without any relation to the substation and communication organization. This is the basis for the SC tool about the volume and capability of the
selected IED for signal engineering. This file is possible in two principle
variants. First it is a general description without a direct project specific configuration and programming. This file describes the general capability. Second it is the ied.ICD file of the full engineered IED according to project
7
Station engineering in IEC 61850
•
•
•
8
Chapter 2
IEC 61850 station engineering
specification and requirements. In this case the volume of available Logical
nodes and therefore signals will be the final one. Which variant is used must
be clarified within the project.
SCD file = Station Configuration Description file
- An SCD file is given when the substation and communication section contains configured values. This file contains all IEDs, a communication configuration section and a substation section.
CID file = Configured IED Description file
- The CID file contents is not part of the standard. It is vendor specific. It
should contain the result of the engineering process on IED and station level.
As it can be seen there are various possibilities in which order the engineering
will be done. Especially the bay level IED for protection and control may need in
most cases project specific adaptations and configuration, which has influence on
the volume of used Logical nodes and therefore data objects. The concept allows
to re-import an extended ied.ICD file and to add or delete signals in the station.
The tools have to support this concept.
Designation model of IEC 61850
2
Chapter 2
IEC 61850 station engineering
Designation model of IEC 61850
The description in the following sections will reference to an example station. This is relevant
for the description of the object designation and signal addressing requirements.
A substation of any size consists of buildings, a lot of primary equipment, substation control
equipment and a lot more. Each item has a name and will be identified by explaining to which
part it belongs to. The rules will differ from country to country and by each utility.
=DeStat (DemoStation)
=E1 (e.g. 135 kV)
=Q1
=Q2
=Q3
=- WA1
=- WA2
=-QB1
=-QB2
=-QB1
=-QB2
=-QB1
=-QB2
=-QA1
=-QA1
=-QA1
=-QB9
=-BI1
=-BU1
=-QB9
=-BI1
=-BU1
=-QB9
=-BI1
=-BU1
=-QC9
=E1.Q1
=-SB1
IED
Control
=-QC9
=-FP1
IED
Protection
=-QC9
=E1.Q2
=-SB1
=-FP1
IED
Control
IED
Protection
=E1.Q3
=-SB1
IED
Control
=-FP1
IED
Protection
=-WH1 (station bus, optical)
IED
NCC
Gateway
=AA1
=-SA1
en06000108.vsd
Figure 2:
Example station for object designation
9
Designation model of IEC 61850
Chapter 2
IEC 61850 station engineering
The IEC 61850 standard is based on the hierarchical addressing and designation model in a station. It follows in this way the structure of the substation equipment independent of IED structure and organization.
This designation and addressing model is also visible in the IEC 61850 telegrams because the
address is presented in MMS as an ASCII string, so the address can be seen directly in a readable
form.
The above figure shows a virtual example station. The identification is based on the IEC 61346
concepts. Reasons to use the IEC 61346 model:
•
•
•
•
•
the IEC 61346 has the task to define structuring principles and reference designations.
the standard is international in the same way as IEC 61850 is
the standard has made a concept which can be used in all industrial systems independent of a language, project etc.
the standard use only single characters per level which makes the total designation very short and therefore saves bytes to be transmitted.
by using this designation model in IEC 61850 it allows to use an easy project independent identification.
The designation of a Logical node and its signals (DO) is needed to identify it to the primary
object etc. The hierarchical order in a substation is the path to identify the LN.
10
Chapter 2
IEC 61850 station engineering
Designation model of IEC 61850
Station = DeStat
=Q1
=E1
=-QB1
CSWI
=-QB2
=-QA1
XCBR1
FC = ST
Pos
stVal
q
RBRF
LD1
t
=-QB9
origin
LD2
PTRC
=P
=B
MMXU1
PDIS
=-BI1
=-BU1
PTEF
PTOC
RREC
=-QC9
en06000110.vsd
Figure 3:
IEC 61850: Object identification model based on IEC 61346 (FuncName)
The designation path to get the position of the circuit breaker as an example would be:
•
•
DeStat => E1 => Q1 => LD1 => QA1 => XCBR1 => Pos => stVal
in IEC 61850 = DeStat.E1Q1/LD1QA1XCBR1.Pos.stVal
and for the operate signal of the time overcurrent protection:
•
•
DeStat => E1 => Q1 => LD2 => P => PTOC => Op
in IEC 61850 = DeStat.E1Q1/LD2P.PTOC.Op
11
Designation model of IEC 61850
Chapter 2
IEC 61850 station engineering
The above model of designation identification is possible when the station configuration is based
on the “FuncName” method in IED 61850. This is specified in the Header section of the SCL
file. The standard identifies these object or signal designations as the technical key. The standard
recommends to use the IEC 61346 based designation model, but it is not a must. But a similar
naming structure is requested when an existing identification concept has to be used.
2.1
IEC 61346 designation model used for IEC 61850
Basics of the IEC 61346 standard:
•
•
•
•
three different views are defined
- the functional view (identified by =)
- the product view (identified by -)
- the location view (identified by +)
to separate two levels in a row the character “.” is used. It is allowed to leave the
“.” out, when the last character is a digit and the first character of the next level
is a letter.
the transition from one view to another is visible when both identification signs
are used in the sequence from > to. E.g. =-QA1 indicates this is a transition from
functional view “=” to product view “-”. The functional view is here the bay Q1
and the product is the circuit breaker QA1.
each level is represented by one character. A second character is used to identify
a type within a level, e.g. QB = HV switching equipment of type disconnector,
QA = circuit breaker and QC = grounding disconnectors.
The IEC 61346 defines the rules etc. and gives explanations how to organize the structure and
the use of the characters but it does not give a model for each industrial area. This has to be done
by working groups.
For the substations for electrical energy distribution the German community of interest “IG
EVU” has taken this task. Member of the IG EVU are beside others the main vendors and the
main utilities of Germany. The papers are available and free of charge via Internet “www.igevu.de”. The documents can be found on the page “Veröffentlichungen”.
The following extracts of the designation trees shows the position of the used elements.
12
Chapter 2
IEC 61850 station engineering
Designation model of IEC 61850
Function Level 2 and 3
A
B
C
D
E
F
G
H
J
K
L
M
N
etc...
Objects for overall control
Switchgear > 420 kV
Switchgear 380 ... 420 kV
Switchgear 220 ... 380 kV
Switchgear 110 ... 220 kV
Switchgear 60 ... 110 kV
Switchgear 45 ... 60 kV
Switchgear 30 ... 45 kV
Switchgear 20 ... 30 kV
Switchgear 10 ... 20 kV
Switchgear 6 ... 10 kV
Switchgear 1 ... 6 kV
Switchgear < 1kV
AA Central control system
en05000647.vsd
Products Level 3 and 4
A
B Detection equipment
BI Current transformer
BU Voltage transformer
F Protective equipment
FA Surge arrester
FP Protective relay
Q HV switching equipment
QA Circuit breaker
QB Disconnector
QC Earthing switch
S Controlling equipment
B Control unit
W Transporting equipment
A Busbar
Signal and control cable,
H
data bus (optical)
en05000646.vsd
Figure 4:
Extracts of IEC 61346 designation trees
13
Substation Configuration description
Language (SCL)
3
Chapter 2
IEC 61850 station engineering
Substation Configuration description Language
(SCL)
The SCL language is based on XML.
It is of course not needed to know the XML file in its details and do any step which requests
XML knowledge, but the organization of the information within the SCL files (ied.ICD and/or
station.SCD) might be of interest. Especially to know where the engineering additions like
DataSets and Control Blocks belongs to.
The SCL XML file is defined in five sections or descriptions, which are specified in IEC
61850–6 clause 9. These sections are:
•
•
•
•
•
the Header
the Substation description (section)
the Communication description (section)
the IED description (section)
the Data Type Templates
The first two sections can be seen as tasks to organize the IEDs within the substation and to establish the communication. These tasks are done by the PCM 600 tool. The Logical nodes as part
of the IED are logically linked to the substation section by PCM 600. The signal engineering
task and routing of the signals is the task of the CCT tool. Its precondition is that PCM 600 has
done the complete organization on the two sections substation and communication.
The DataSets and Control Blocks configured by the CCT tool are located in the IED section because they are logically defined as part of the Logical nodes (see IEC 61850–7–2 clause 9). The
CCT needs the correct configured communication section when it comes to GOOSE engineering.
The Data type templates section is requested to give the correct content description of each Logical node type to all user of the information. These are the clients. Each IED and vendor may
have/has its own Logical node type definitions.
14
Substation Configuration description
Language (SCL)
Header
Header
Chapter 2
IEC 61850 station engineering
FuncName
or
IEDName
Id
ToolId
Nam eStructure
Substation
VoltageLevel
Bay
IED
LD
LN
IED
LD
LN
Station
LNode
Communucation
Subnetwork
Connected AP
IED Nam e
AccessPoint
Address
GSE
IED Nam e
AccessPoint
Address
GSE
IED
Services AccessPoint
Server
Authentication
LDevice
LN0
LN
DataSet
DOI
DAI
Report Control
GOOSE Control
Inputs
SettingControl
IED
DOI
DataTypeTemplates
LNodeType
DO
DOType
DOType
DA
SDO
DAType
DAType
BDA
Enum Type
Enum Type
en06000111.vsd
Figure 5:
IEC 61850: Principle structure of the SCL XML file
Figure 5 shows a principle structure of the SCL XML file with its five sections. The arrows show
the link between the different sections given when an IED is integrated in the substation structure and/or in the communication structure. All available Logical nodes of an IED are linked to
the substation section.
15
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
A reference to the GoCB is included in the communication section when the GoCB is configured.
The above graphical presentation of the XML file is a standard view of XML editors. It gives a
better picture about the structure of the XML contents.
3.1
The Substation section
The substation description in IEC 61850–6 clause 9 describes the organization of the primary
equipment in a single line diagram on one side. On the other side it describes the used LNs belonging to a bay. The second part is of interest for the signal engineering.
In part 6 clause 8.4 of the standard the object and signal designation rules are described. The
identification for the signals are therefore also used in the telegrams defined in IEC 61850–8–1
is named “Technical key”. The technical key is used within the SCL description to identify and
reference objects. See chapter 2, section 1 "Station engineering in IEC 61850" about the concept
based on IEC 61346. PCM 600 generates an “SCL Technical key” independent of the naming
given by the project. The PCM 600 generated technical key is based on the definitions given in
IEC 61346 and for electrical substations. When a project is using its own naming model this will
be used by the SCL description as technical key. PCM 600 allows to select the version which
should be used in the SCL files when exporting a station.SCD file.
Signal identification in the communication system
The signal identification rules used by IEC 61850 are described in part 7–2 clause 19.2. and used
in part 6 clause 8.4.2
The signal designation consists of four parts:
1. a user defined part identifying the Logical device LD in the process (LDName)
2. a function related part to distinguish several LNs of the same class within the
same LD/IED (LN-Prefix)
3. the standardized LN class name and the LN instance number, which distinguishes
several LNs of the same class and prefix within the same LD/IED
4. a signal identification inside a LN consisting of data and attribute name as defined in IEC 61850–7–3 and IEC 61850–7–4
16
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
en06000112.vsd
Figure 6:
Elements of the signal identification as defined in IEC 61850–7–2
The above figure is taken from the standard IEC 61850–6 (figure 5).
The standard defines two options how to use part 1 and part 2 above:
1. Function related naming
• identified in the SCL header with NameStructure = FuncName
2. Product related naming
• identified in the SCL header with NameStructure = IEDName
Within one SCL project only one option can be used.
17
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
Function related naming
1
Substation
LDCL1
LN
LN
LN
LN
LDCL2
LN
LN
LN
LN
VL1
2
3
Bay1
LD1
Bay2
4
LN
LN
LN
LN
LD1
5
6
LD1
LN
LN
LN
LN
LD2 > LNs
VL2
Bayx
LN
LN
LN
LN
LD2 > LNs
2
3
Bay1
LD1
Bay2
4
LN
LN
LN
LN
Bayy
LD1
5
6
LD1
LN
LN
LN
LN
LN
LN
LN
LN
LD2 > LNs
LD3 > LNs
Elements of signal identification IEC 61850-7-2
LNName
LDName
LN Prefix
LN class
LN instance no
6
Substation section
1
2
3
IED section
Substation section
4
5
Signal naming using functional naming
Figure 7:
en06000099.vsd
IEC 61850–6: Function related naming
The part 1 = LDName of signal identification is build out of the objects Substation (1), Voltage
level (2), bay (3) and the LD (4). The LN Prefix in this case is an additional element which belongs to the LDName part. It identifies the equipment or sub-equipment object in the primary
18
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
structure. The typical example is the circuit breaker QA1, when the LN classes XCBR, CSWI
and CILO are used. It has to be regarded that in this model the IED is not included and the naming is based in the process objects only.
The LNName is in this option the LN class and the LN instance (6) only.
Product related naming
Substation
1
LDCL1
LN
LN
LN
LN
LDCL2
LN
LN
LN
LN
VL1
2
3
Bay1
Bay2
A
IED 1
IED 2
B
LD1
IED x
LD1
C
LN
LN
LN
LN
VL2
Bayx
2
LD1
LN
LN
LN
LN
LN
LN
LN
LN
LD2 > LNs
3
Bay1
Bay2
A
IED 4
Bayy
IED 5
B
LD1
LN
LN
LN
LN
IED y
LD1
C
LD1
LN
LN
LN
LN
LN
LN
LN
LN
LD2 > LNs
Elements of signal identification IEC 61850-7-2
LNName
LDName
LN Prefix
IED section
IED section
A
B
LN class
Signal naming using product naming
Figure 8:
LN instance no
C
en06000100.vsd
IEC 61850–6: Product related naming
19
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
The LDName part is build in this option out of the objects IED (A) and LD (B). The link to the
primary process is not given in this model.
The LNName is in this option the LN Prefix, the LN class and the LN instance no (C).
The LN prefix allows in this model to identify several versions of a LN class. For example the
eight different versions the LN class PDIF.
The link between the IED and the primary process (Substation (1), Voltage level (2), bay (3)) is
given in the substation section of the station.SCD file but not in the signal identification in the
telegram. The project may decide how to deal with this matter. The IED name may be extended
with a short form of the three missing levels. The IEDName must be unique in this designation
model.
Remark:
The standard defines the maximum length for the signal naming and for identification parts to
32 ASCII characters each. This has to be regarded for the object identification for part 1 to part
4 (see figure 6). In addition it might be possible that client IEDs have additional restrictions
which have to be taken into account.
Most vendor have to use the LN Prefix to identify their versions etc. Therefore the product related naming model (IEDName) will be used.
3.2
The communication section
The organization of the physical IEDs to the communication network is independent of the substation structure. The IEC 61850 standard defines the communication network with no relation
to an existing media and protocol. The first mapping to an existing media and protocol is done
in IEC 61850–8–1 with:
•
•
Ethernet as medium
MMS (Manufacturing Message Specification) protocol as defined in ISO 9506–1
and IOS 9506–2.
The IEC 61850 standard describes in part 7–2 the Abstract Communication Service Interface
(ACSI) in a media and protocol independent form. Part 8–1 specifies the mapping of this ACSI
to the existing MMS.
The communication section in the SCL file describes the minimum of what is needed to identify
how information is routed between the IEDs in a project. This is.
•
•
•
•
•
•
20
the used subnetworks
the IEDs connected to the different subnetworks
the access points per IED to the subnetworks
the address
the IP address of the LAN network is as an exception also part of the address elements
and, extended during signal engineering and routing, the link to the GoCB message in transmission direction.
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
IED
(client)
IED
(client)
- Access Point (AP)
- Address
- GSE; GoCBs
- Access Point (AP)
- Address
- GSE; GoCBs
Communication
Communication
Subnetwork
AP
AP
Communication
Communication
Communication
- Access Point (AP)
- Address
- GSE; GoCBs
- Access Point (AP)
- Address
- GSE; GoCBs
- Access Point (AP)
- Address
- GSE; GoCBs
IED
(server)
IED
(server)
IED
(server)
en06000101.vsd
Figure 9:
IEC 61850–6: Communication network
Figure 9 shows the contents of the communication section. Additional information about the
server etc. is part of the IED.
The link to the IEDs is done by PCM 600 when the IED is placed and the link to the subnetwork
established. The list of “Connected AP” in the communication section of the SCL file includes
all IEDs with their APName.
A station as shown in figure 3 the station uses two voltage levels with a set of bays and IEDs per
bay. The communication network can be done in several ways for this station. The most typical
variants are shown in figure 10.
21
Substation Configuration description
Language (SCL)
Client
IED 1
Chapter 2
IEC 61850 station engineering
Client
IED 2
Subnetwork 1
IED 1
IED 2
IED x
IED 4
VL 1
IED 5
IED y
VL 2
Client
IED 1
Client
IED 2
Subnetwork 1
Subnetwork 2
IED 1
IED 2
IED x
VL 1
IED 4
IED 5
IED y
VL 2
en06000103.vsd
Figure 10:
Communication section: Possible network configuration examples
Both variants fulfil the requirements and performance. Variant 2 may be used, when the availability question is discussed. In this case only one voltage level of the station is lost when a subnetwork fails. The client IEDs must be able to handle two access points.
3.3
The IED section
The IED section describes the complete IED as it is needed for IEC 61850 communication and
signal engineering. The Data Type Template part of an IED may be seen as part of the IED, even
when separated in its own section. The ied.ICD files includes the description of the LNs, their
Data Type Templates and the used/supported services. The structure of the IED section follows
the definitions made in the IEC 61850 standard.
There are two basic IED types which are used:
•
22
station level IEDs
- IEDs located on station level and dealing with the information transmitted
from/to the bay IEDs are identified as client IEDs. They are represented by
Logical nodes of group “Information (I)”. This are the LNs = ITCI, IHMI and
Chapter 2
IEC 61850 station engineering
Substation Configuration description
Language (SCL)
•
ITMI. They are the receiver of information in monitoring direction and sender of commands (control). These LNs have no data objects. They are only
used to do the link of the report control blocks (BRCBs) from the server
IEDs.
bay level IEDs
- all IEDs on bay level are server IEDs.
Signal engineering is done within the server IEDs.
Subnetwork
AP
IED
Server
SB1.LD1
Logical
Node
LLN0
LPHD
Data
SXCBR1
Mod
SCSWI1
Beh
SXSWI1
Health
SCSWI2
NamePlt
Data
Attribute
SXSWI2
Pos
ctlVal
SCSWI3
Loc
stVal
SXSWI3
OpCnt
q
SCSWI4
BlkOpn
t
SXSWI4
BlkCls
Origin
SCSWI5
CBOpCap
ctlModel
CVMMXU1
Control
en06000104.vsd
Figure 11:
Organization of LDs, LNs, DOs and DAs in an IED
The above figure is a short summary about the logical organization of the signals below the IED.
•
•
•
A server represents the communication interface to the subnetwork (Ethernet).
one or more Logical device(s) are connected to a server
a set of Logical nodes belong to a LD
23
Substation Configuration description
Language (SCL)
•
•
•
•
Chapter 2
IEC 61850 station engineering
the LN LLN0 is a special LN per LD and contains the DataSets, the various control blocks, inputs (from GOOSE messages) etc.
The LN LPHD is a special LN per LD and contains data objects which describe
the status of the physical device (the IED)
each Logical node represents a function and contains a number of data objects
(DO)
each DO is represented by a number of data attributes (DA)
The data objects are representing information signals which may be routed to station level IEDs.
So the signal engineering task is to select the requested signals (DOs) and link them to the client
IEDs as receiver. The control services are not directly engineered. They are included in the data
objects which handle both directions the command (control) and the response (monitoring). So
when routing the DO in monitoring direction the control is then also known by the clients.
The organization of the IED from LD down to DAs can be viewed in the CCT tool. This organization concept has to be taken into consideration when DataSets are configured.
The number of data objects and data attributes per DO is defined by the used LN type in this
IED. The contents is taken from the Data Type Templates which belong to an IED type.
3.4
Signal engineering
DataSets
IEC 61850 has defined DataSets and report control blocks for signal transmission in monitoring
direction. DataSets are also used for GOOSE messages in horizontal direction. Which data objects or single data attributes should be collected in a DataSet is not specified and can be done
to rules which may be defined in a project. The following figure shows a DataSet where all position information of the apparatuses of a bay are put into one DataSet.
The vendor of an IED can define DataSets as defaults which are part of the IED and always
available. They need to be linked to the client IEDs only when you want to use them as they are.
The vendor has to declare when these DataSets can be modified to projects need or not.
24
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
LD1
DATA-SET
LLN0
LD1/LLN0.AppPos
LPHD
LD1/SXCBR1.Pos FC=ST
SXCBR1
Pos
LD1/SXSWI2.Pos FC=ST
SCSWI1
SXSWI1
LD1/SXSWI1.Pos FC=ST
Pos
LD1/SXSWI3.Pos FC=ST
LD1/SXSWI4.Pos FC=ST
SCSWI2
SXSWI2
Pos
SCSWI3
SXSWI3
Pos
SCSWI4
SXSWI4
stVal
q
Pos
SCSWI5
t
Origin
CVMMXU1
en06000106.vsd
Figure 12:
IEC 61850–7–2: Example of a DataSet
General rules for DataSet configuration:
•
•
•
•
All data objects or their data attributes which are signals in monitoring direction
can be selected for a DataSet
only those data attributes of a data object can/will be selected which have the
same function constraint (FC).
data objects with different FC can be selected for a DataSet. For example DOs
with FC = ST and DOs with FC=MX can be member in one DataSet.
a single data attribute can be selected when it is specified with a trigger option.
For example the data attribute stVal of the data object Pos can be selected as a
member of a DataSet, because it is specified with the trigger option data change
detected (dchg).
The description of the DataSets with name and the list of data object members (FCDAs = Functional Constraint Data Attributes) is included in the SCL file in the IED section in the Logical
device subsection. As specified in IEC 61850–7–2 clause 9, the DataSets are part of a Logical
node. They are most likely included in the LLN0.
3.4.1
Buffered Report Control Block (BRCB)
To be able to transmit the signals configured in a DataSet a BRCB must be configured which
handles and specifies how the events will be transmitted to the clients.
25
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
The contents of a BRCB is listed in IEC 61850– 7–2 in clause 14, table 23. The BRCB contains
a lot of attributes which are of interest to handle and secure the communication between the client and the server and may be set once as default in a project. Others are of application interest
in the way events are handled in a project.
•
•
•
•
•
Buffer time
- This parameter describes how long the report should wait for other expected
events before it will send the report to the client. When it is known, that additional events will be generated as a follow up it is useful to wait for example 500 ms for additional events stored in the report. This feature reduces the
number of telegrams transmitted in case of a burst of changes. But on the other side it increases the overall transaction time for events from IED input to
presentation on HSI which is normally defined to be one second!
Trigger options
- The data attributes know three different trigger options (dchg, qchg, dupd).
Within the BRCB the two other can be defined (integrity and general interrogation). The attribute Trigger option is a multiple choice and allows to
mask the supported trigger options in this BRCB.
Integrity period
- When integrity is selected in the trigger option attribute, it is needed to define
an integrity period to force the transmission of all data listed in the DataSet.
This is done by the attribute Integrity period. This feature can be used as a
background cycle to ensure that the process image in all partners is the same.
Nobody is perfect and someone in the long chain from the contact up to the
NCC may have lost an event. The background cycle can repair it.
General interrogation
- A general interrogation is only done on request from a client. Not all Data-sets may contain information which is needed for a general update of the
client. For example data with T(ransient) = TRUE are not part of a GI. When
the BRCB attribute general interrogation is set to TRUE a GI request from
the client will be handled. The report handler will transmit all data defined in
the Data-set with their actual values. The IEC 61850 standard defines that all
buffered events shall be transmitted first before the GI is started. A running
GI shall be stopped and a new GI shall be started, when a new GI request is
received while a GI is running.
Purge buffer
- This BRCB attribute can be used by a client to clean the event buffer from
old events. The events are discarded on request of the client. This feature can
be used to delete old events not transmitted to the client due to stopped communication. After the link is reestablished the client can decide to clean the
buffer or to receive the history.
Trigger Options
IEC 61850 has defined in total five different TrgOp. Three of them belonging to data attributes
and marked per data attribute in the column TrgOp of the CDC tables in part 7–3. The other two
belonging to the configuration of control blocks. The five trigger options are:
•
26
dchg = data-change
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
-
•
•
•
•
The classical trigger. Whenever a process value has changed its value either
binary or a measurement a transmission is done. How it is detected and how
the Logical node is informed is not part of the standard.
qchg = quality change
- Looking to the possibilities of the quality data attribute type (q) any changes
in the quality description will be transmitted.
dupd = data value update
- This trigger option give the possibility to define that a transmission should
be done on a condition which can be controlled by the application.
integrity
- This trigger will force the transmission of all process values defined in the
Data-set when a timer value (the integrity period) expires. It can be used for
example to do a process signal update in the background (e.g. every 15 minutes).
general interrogation
- This trigger is forced by the clients (= station level IED; NCC gateway, station HMI, ...). Normally a GI is asked for, when the client and the server start
or restart a session. When the client is able to receive the actual values and
when the Logical device has scanned all process values at least once, an image of the actual process signal status can be transmitted to the client.
Link BRCB to a client LN
The BRCB has to know to whom the events shall be transmitted. This is the signal routing engineering step. The IEC standard 61850–6 describes that this is given by including the LN of the
client IED in the ReportBlockEnabled option.
The selected client IED with the corresponding LN (e.g. ITCI) is included in the SCL structure
of the Report Control description of the IED section.
CCT is doing it when the client LN is linked with the name field of the BRCB by the
drag-and-drop method.
The description of the BRCB with selected DataSet, configured parameters and selected IEDs
is included in the SCL file in the IED section in the LN0 structure for the LD where this LN0
belongs to.
27
Substation Configuration description
Language (SCL)
IED
HSI
Client 1
IED
NCC GW 1
IHSI1
Client 2
ITCI1
Chapter 2
IEC 61850 station engineering
IED
NCC GW m
Client m
ITCI2
Subnetwork
Server 1
LLN0
DATA-SET
LD1/LLN0.AppPos
IED 1
LD1/SXCBR1.Pos FC=ST
LD1/SXSWI1.Pos FC=ST
LD1/SXSWI2.Pos FC=ST
LD1/SXSWI3.Pos FC=ST
LD1/SXSWI4.Pos FC=ST
en06000107.vsd
Figure 13:
28
Link BRCB to a client LN
Substation Configuration description
Language (SCL)
Data-set
Data-set
LN
LN
LN
LN
Receive
Data-set
LN
LN
LN
Receive
Send
Receive
Receive
Send
Receive
Receive
GOOSE Control Blocks (GoCB)
Send
3.4.2
Chapter 2
IEC 61850 station engineering
LN
LN
LN
LN
LN
LN
LN
LN
Subnetwork
Comm.
Comm.
GSE
Server
Server
LD1
LD1
GoCB
GoCB
GoCB
Input
Input
Input
DataSet
DataSet
DataSet
GSE
GoCB
GoCB
GoCB
LN0
Input
Input
Input
DataSet
DataSet
DataSet
LN0
en06000109.vsd
Figure 14:
IEC 61850: Principle operation of GOOSE messages
The Generic Object Oriented Substation Event (GOOSE) class model is used to distribute input
and output data values between IEDs on bay level (in horizontal direction) through the use of
multicast services. GOOSE messages bypass the server and enables a fast transmission from
publisher to one or several subscribers (receivers).
29
Substation Configuration description
Language (SCL)
Chapter 2
IEC 61850 station engineering
GOOSE messages are unidirectional, send only messages which request an application specific
method to secure that sender and receiver of the message operates safely. This implies that the
receiver of the GOOSE message distributes also GOOSE messages and close the loop for communication (request — respond on application level). The return message is not a must. It depends on the application in which way a confirmation may be done.
The GOOSE message concept will be used for all application functions where two or more IEDs
are involved. Typical example is the station-wide interlocking procedure.
The very simplified figure above shows the GOOSE concept for three IEDs which interchange
GOOSE messages between each other.
To send GOOSE messages a GoCB must be defined and a DataSet is needed which contains the
data objects of single data attributes to be send.
A GOOSE message is forced to be transmitted when a trigger change is detected for a data attribute. All members of the Data-set will be copied in the send buffer with their actual value and
the message is sent. All subscriber which knows the address of this GOOSE message will receive the telegram. The GOOSE message includes sequence number etc. to verify that all messages are received.
The concept what has to be done in case of a lost message etc. is part of the application and not
described in the standard.
The DataSet for GOOSE messages are configured in the way described above.
A GoCB has to be defined per GOOSE-DataSet.
GOOSE messages bypass the server and send direct from the communication part on the Ethernet. This is identified for the communication in the SCL communication section in the GSE element, where the name of the GoCB is listed under the ConnectedAP.
Link GoCB to an IED
The IEDs which should receive this GOOSE message must be known and they have to be informed in the engineering state that they will receive GOOSE messages. This is given when the
external Reference, the name of the IED and the member of the DataSet is included in the LN0
under the structure of the LD of the receiving IED. This part is identified as “Inputs”.
The IEDs which shall receive the GOOSE are selected by CCT. CCT is doing it when the IED
itself (the IED icon) is linked with the name field of the GoCB by the drag-and-drop method.
30
About this chapter
Chapter 3
IEC 61850 Station configuration
tasks
Chapter 3 IEC 61850 Station
configuration tasks
About this chapter
This chapter describes the principle tasks and steps to do station and signal engineering according to IEC 61850–6 definitions. It gives an overview about the corresponding steps to be done
by PCM 600 and CCT.
31
IEC 61850 Station configuration tasks
1
Chapter 3
IEC 61850 Station configuration
tasks
IEC 61850 Station configuration tasks
The IEC 61850 standard defines the complete part needed for information communication in a
substation. This can be split into the following parts:
•
•
•
•
•
the definition of data objects and their common data classes with their data attributes
the definition of Logical nodes (LN) as the communication interface for a substation function (e.g. a protection function)
the definition of a basic communication structure for substation and feeder equipment
the practical mapping of the communication to an existing protocol the MMS
the definition of the engineering process for a substation control system in a configuration description language for communication in electrical substations
We refer to the IEC 61850 standards in their actual version as a basis for the engineering tasks
described inhere by using the PCM 600 and the CCT. The main parts which are of interest are
described in a brief form in chapter 2 "IEC 61850 station engineering".
A short form of the complete station and signal engineering sequence can be described as shown
in the following figure.
32
IEC 61850 Station configuration tasks
IEC 61850 Station Configurator
Vendor A
prepare
ied.ICD
files
Vendor B
prepare
ied.ICD
files
Chapter 3
IEC 61850 Station configuration
tasks
Vendor X
prepare
ied.ICD
files
PCM 600
y
y
y
y
y
configure station structure
integrate IEDs
load ied.ICD files
configure communication subnetwork
export station_PCM.SCD file
text
station_PCM.SCD
CCT
y
y
y
y
configure DataSets per IED
configure and link report control blocks
configure and link Goose control blocks
export station.SCD file
station.SCD
Vendor A
prepare
ied.CID
files
Vendor B
prepare
ied.CID
files
Vendor X
prepare
ied.CID
files
IED
IED
IED
en06000207.vsd
Figure 15:
IEC 61850: Station configurator
The procedure can be split into three main parts
1. Configuration of the station structure including IEDs and communication with
PCM 600
• configure the plant structure in voltage levels and bays
• place all bay IEDs from ABB and other vendor (using the Generic IEC 61850
IED as a placeholder) in the bays
• do IED engineering for ABB IEDs with PCM 600 to generate the ied.ICD
files
33
IEC 61850 Station configuration tasks
Chapter 3
IEC 61850 Station configuration
tasks
•
do the similar tasks for the other bay IEDs with their IED engineering tools
and export the ied.ICD files or take the ied.ICD files from a vendors library
• import all other ied.ICD files to their position in the station via Generic IEC
61850 IED.
• check the communication subnetwork that all IEDs are connected to the
same subnetwork
• give each bay IED its IP address
• export the station_PCM.SCD file
2. Signal engineering for the IEC 61850 signals with CCT
• create a project in CCT, if it not already exists for the station
• import the station_PCM.SCD file created by PCM 600
• actually import client IEDs with their ied.ICD file to the station configuration by CCT
• link the client IEDs to the communication subnetwork and define the access
point
• save, close and load the CCT project again; only when client IEDs are added
by CCT first time
• check the pre-configured DataSets for report control blocks for your needs
and for each IED. Generate additional DataSets for RCBs when requested
• generate the needed DataSets for GOOSE messages
• create and configure Buffered Report Control Blocks (BRCB) for each data
set used for vertical communication.
• link each DataSet for vertical communication to a BRCB
• link the IED clients Logical node (ITCI IHMI) to the BRCBs
• create and configure GOOSE Control Blocks (GoCB) for each DataSet configured for GOOSE messages
• link the GOOSE DataSets to a GoCB
• link the IEDs which shall receive the GoCB to the GoCB
• update IEC 61850 data flow (CCT specific function)
• export the station.SCD file for further use by the IED configuration tools
3. Preparation of ied.CID files per IED and download them to the IEDs
• import the station.SCD file to all IED configuration tools for further activities
• for ABB bay IEDs use the PCM 600 for IED engineering
• do signal marshalling with the SMT tool in all ABB IED 670s which are involved to receive GOOSE messages
• download the updated ied.CID file to the IED 670 with the SMT tool
• do similar tasks for all other IEDs with their IED configuration tool
This is a short form of the complete procedure for IEC 61850 with PCM 600 and CCT.
The additional tasks for signal engineering for IEC 61850 in an IED 670 are described in the
'Engineering guide for IED 670 products'.
34
About this chapter
Chapter 4
PCM 600 and CCT tool set for
station engineering
Chapter 4 PCM 600 and CCT
tool set for station
engineering
About this chapter
This chapter explains the presentation of the two tools used for IEC 61850 station engineering.
The PCM 600 and CCT tool.
35
PCM 600 and CCT tool set for station
engineering
1
Chapter 4
PCM 600 and CCT tool set for
station engineering
PCM 600 and CCT tool set for station engineering
PCM 600 and CCT are state of the art tool sets based on Microsoft.net technology.
The two tools are able to do the station configuration tasks as defined by IEC 61850–6. They are
doing it for the IED and subnetwork configuration in a plant structure and in a communication
structure by PCM 600. The signal engineering which is defined by the DataSets, the report control blocks and the GOOSE messages is done with the CCT.
PCM 600 is a tool which supports in itself the tasks needed to do IEC 61850 station engineering
but it is also the platform for several sets of tool components used to support IED engineering
for ABB IED product families. This manual describes the IEC 61850 station configuration task
only.
It is requested to use the IED engineering guide manuals in addition when ABB IEDs are part
of the IEC 61850 based station project.
The description of the PCM 600 is limited in most cases to the part needed for IEC 61850 station
configuration.
The CCT is a tool which is used by ABB as a base product for signal engineering of several protocols. This version of CCT is also limited to the tasks needed to do signal engineering for IEC
61850 protocol. The precondition to use CCT is that the plant structure with the IEDs and the
communication structure is build by PCM 600. See chapter 3 "IEC 61850 Station configuration
tasks" for a description of the general tasks for IEC 61850 station configuration by using PCM
600 and CCT.
36
PCM 600 views and windows
2
Chapter 4
PCM 600 and CCT tool set for
station engineering
PCM 600 views and windows
The PCM 600 tool set runs under the operating system Windows 2000 or Windows XP. It is expected that the user is familiar with the handling and use of the Windows platform. In this chapter only those items are explained and shown which are specific to PCM 600 but still based on
Microsoft windows methods.
When you start PCM 600 and no project is already selected you will get an empty window with
the base menubar and toolbar only. Once you have selected a project, you will be given the possibility to select different views. The start menu of a project may look like the menu shown in
the figure below.
Menubar & Toolbar
Project
Explorer
&
Object
Types
Place for
selected tool
Object
Properties
Output & Logging
en06000028.vsd
Figure 16:
PCM 600: base screen example
37
PCM 600 views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000580.vsd
Figure 17:
PCM 600: base menubar
Possible views:
•
•
•
•
Project Explorer
Object Properties
Output
Object Type
Project Explorer
The Project Explorer window is the skeleton of the project organization. It is used to show the
project in two different structures:
•
•
the plant structure
the communication structure
The plant structure is the most commonly used view and shows the organization of the stations
in the geographical order top down from a defined highest level (e.g. the network control center
(NCC)) down to each IED logically connected to a bay in the station. The plant structure is used
to select the tools per IED.
The communication structure is not needed for normal operation. It is used to view the communication network and links from the PCM 600 to each IED. Only the private communication
from the PCM 600 to each IED is managed and handled by the PCM 600.
To select the communication structure do a right mouse click on the area next to the Plant Structure tab. Select communication and an additional page will be included which shows the communication structure of the PCM 600
en05000562.vsd
Figure 18:
38
Plant structure: select communication structure
PCM 600 views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
Object Properties
The Object Properties window is a standard Microsoft window which allows the user to view
and when needed to modify properties of the selected object. In the PCM 600 frame this window
is used by some tools like GDE to insert the IP address of the IED selected and some other properties like object naming in the HMI picture and so on. It might be necessary to check some properties for communication to adapt and synchronize the communication network. The shown
properties in the object properties window follow the selected object in the Project Explorer or
in a tool.
en05000559.vsd
Figure 19:
PCM 600: Object properties window
Modifications are only possible in cells with their content shown in bold. Renaming of objects
can be done more easily by using the Rename capability in the plant structure, which is made
available by pressing the right mouse button.
Output
The Output window is shown on the bottom array of the PCM 600 screen when selected. It is a
log script which is used by PCM 600 to list all activities, warnings, error messages etc. which
come up during operation of the PCM 600. It might be needed and used when a task does not
operate as expected. The information in the output list may provide a clue as to why it does not
operate etc. The Output view is not needed for normal operation and can be closed.
39
PCM 600 views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000558.vsd
Figure 20:
PCM 600: Output window
Object Type
en05000556.vsd
Figure 21:
PCM 600: Object Type window
The window Object Type can be used to build up a plant structure using drag and drop and selecting the object type from the list of possible objects. It is opened in the same place and then
the Plant Structure is presented. It is selected by clicking on the Object Types tab at the bottom
of the window.
The Object Type window contains some different panes depending on selected structure. For the
plant structure view the two panes are selectable by clicking the menubar General or Transmission IED”.
More details to different views etc. are given in chapter 5 "Set up a project in PCM 600".
40
PCM 600 views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
IED tools
These tools are not used for IEC 61850 station configuration.
Each started IED tool will be visible in the residual screen area surrounded by the three windows
Plant Structure, Object Properties and Output. For normal operation only the Plant Structure is
needed and it is recommended to close the other two windows. More then one tool can be open
at the same time for one IED or for some IEDs in parallel. But only one tool at a time is active.
The tool is selected either by its tool tab or by selecting the IED.
See the IED engineering guide manuals for more derails.
2.1
PCM 600 the toolbar and the mouse
For each IED 670 tool the PCM 600 basic menubar and toolbar is expanded by additional
menu-lists and tool-icons. This is not given and needed for IEC 61850 station configuration. For
more details see 'Engineering guide for IED 670 products'.
The right button of the mouse is supported. Clicking the right mouse button opens a context sensitive menu. This menu presents all possible actions and selections corresponding to the selected
object.
en05000555.vsd
Figure 22:
PCM 600: Conditional selection by the right mouse button
Depending on selection as given in this example the alternative choice could be to select New....
In this case a new window will pop up and it shows the same selection possibilities.
41
PCM 600 views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000554.vsd
Figure 23:
PCM 600: New object selection window
The window keeps open after your selection. Depending on the selected object it will show directly the possible choices.
Save tool engineering results
PCM 600 stores additions and changes in the plant and communication structure direct in its database. This function is not needed for IEC 61850 station configuration.
The PCM 600 stores all changes for which it is responsible directly in the database. This is useful
because these changes are only of type organization and have no influence on IED data. Changes, additions etc. done within a tool are only moved to the project database when they are saved.
This possibility is context sensitive and will be displayed in the PCM 600 base menu bar under
File when a tool has the ability to save.
42
PCM 600 views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
Save tool result
en05000574.vsd
Figure 24:
PCM 600: Save tool result window
Cut, copy, paste, drag and drop
PCM 600 supports these functions where possible and useful. Depending on what it is and where
it is inserted as a copy a request to rename the object may appear. It is indicated as “copy of... ”
until it is given a unique name.
All other possibilities are self explanatory or Microsoft Windows standard.
43
PCM 600 options for operation
3
Chapter 4
PCM 600 and CCT tool set for
station engineering
PCM 600 options for operation
The options can be selected from the menulist Tools>Options. A pop up window will be displayed showing the entry point for the four different options. The four option windows are:
1. Log Configuration
• to organize the log file which is produced during the sessions and shown in
the Output view of PCM 600
2. Category Manager
• allows the definition of user groups with different rights to work with PCM
600 according to their need and task.
3. System Settings
• specifies the basic decision about access rights for PCM 600 by the authentication method
4. User Manager
• is used to edit the list of persons or users which can use PCM 600 when an
authentication method is selected
3.1
PCM 600 access
The set up and the possibilities to organize PCM 600 access can be seen as a branch with three
basic alternatives. For each of the three alternatives you have to set up information in the user
manager and select a user category out of the list described by the category manager.
Changes in the System Settings, Category Manager and User Manager can only be done by a
user of the category type “System Engineer”.
The used alternative is selected in the Authentication. Select the System Settings window to
choose the authentication.
44
PCM 600 options for operation
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000614.vsd
Figure 25:
PCM 600: Set authentication window
Set Data Access Password
This password is used to control access to the MSSQL$PCMSERVER. It is recommended not
to enter a password when several users have access to PCM 600. Only a single user with his own
PC may use this.
PCM 600 must be reinstalled and all projects will be lost if this password is not available!
User authentication
The tasks and action in each branch can be sorted like this:
1. Use Authentication
• NO = no selection. Everybody can use the PC where this PCM 600 is installed.
• YES = Authentication is used. Select the method with one of the two choices:
2. PCM Authentication or
3. Windows Authentication
Select the User manager.
45
PCM 600 options for operation
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000613.vsd
Figure 26:
PCM 600: User profile window
The User Manager window has four input fields. Three of them are used to define the access for
a user for either PCM or Windows authentication. The field Real Name might be used to identify
the user, when the user name is a short version of his name.
The PCM authentication uses the following inputs to identify a user:
•
•
•
User Name
Set Password (optional)
User Category. The user category is defined in the category manager. It belongs
to the user name and is not part of the authentication check.
The Windows authentication uses the following inputs to identify a user:
•
•
•
•
User Name
Windows Account.
User Category. The user category is defined in the category manager. It belongs
to the user name and is not part of the authentication check.
Set Password is not used!
PCM authentication
When the PCM authentication method is used a Login window pops up after start of PCM 600.
The user has to identify himself with his user name and the password when it is used for access
control.
46
PCM 600 options for operation
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000610.vsd
Figure 27:
PCM 600: Login window
Rules to set a password:
•
•
•
•
•
•
•
can not be empty
is at least 8 characters long
contains at least one special character (like ! , \, &, etc.)
starts and ends with an alphabetic character
contains at least one number
contains at least one uppercase character
contains at least one lowercase character
Windows authentication
In the Windows authentication method each user must have a different account on this PC. Only
in this case a selective input is possible. In this case the user has already identified himself to the
PC, when he started Windows. So a separate access control is not needed.
A user can change his password, by entering his old password once, and then the new password
twice. The system engineer can change passwords without knowledge of the old passwords.
47
PCM 600 options for operation
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000617.vsd
Figure 28:
PCM 600: User window with password setting
Category Manager
Different categories of default user are defined for PCM 600:
•
•
•
48
System Engineer
- has access to all tools and functions
- is the only one who can edit user management
Application Engineer
- has access to all tools for engineering the IEDs
- has access to the system monitoring tools to check during commissioning
phase the correct operation of the IED
- has no user management rights
System Monitoring User
- has access to the system monitoring tools to monitor the IEDs during operation
- has no access to the engineering tools
- has no user management rights
PCM 600 options for operation
Chapter 4
PCM 600 and CCT tool set for
station engineering
en05000615.vsd
Figure 29:
PCM 600: Category manager window
49
Connectivity package support for PCM 600
4
Chapter 4
PCM 600 and CCT tool set for
station engineering
Connectivity package support for PCM 600
PCM 600 is a tool which allows the user to include the engineering tool components for product
families of ABB for transmission and distribution. In the way you are using ABB products it
might be that you will have several sets installed using the concept of connectivity packages.
How to install a new product package or to add an additional communication protocol is described in the documentation for PCM 600.
To engineer the ABB IED 670 product family you must have enabled the use of these tools and
protocols in the connectivity package manager. Please check that before you may start the PCM
600.
en05000561.vsd
Figure 30:
Connectivity manager: version selection window
Always use the latest version of a tool package or protocol. This can be easily done in the
menubar Set Latest.
In the above Connectivity Package Manager window the following packages are available
•
50
Generic IEC 61850 IED connectivity Package
- This package is very much needed for IEC 61850 station configuration.
Connectivity package support for PCM 600
Chapter 4
PCM 600 and CCT tool set for
station engineering
-
•
•
•
•
It will be used to include the ied.ICD file of bay IEDs in the station.SCD file.
It will be used, when the DRH tool is used to read the DR files from all IEDs
running the IEC 61850 protocol. See IED engineering guide manual for more
details about the disturbance report handler (DRH).
IEC 61850 Connectivity Package
- This package is needed for IED 670 products, which communicate with
PCM 600 on Ethernet, TCP/IP and using elements of the IEC 61850 protocol.
LON Connectivity Package
- This package is not needed for IED 670 products. It is used for products using LON to communicate with PCM 600.
IED 670 Connectivity Package
- This package is needed in the latest revision to engineer IED 670 products.
It contains the description of the IED 670 products.
SPA Connectivity Package
- This package is not needed for IED 670 products. It is used for products using SPA to communicate with PCM 600.
51
PCM 600 Set up communication link per IED
670
5
Chapter 4
PCM 600 and CCT tool set for
station engineering
PCM 600 Set up communication link per IED 670
The communication between the IED 670 and the PCM 600 is independent of the used IEC
61850 communication protocol within the substation. It can be seen as a second channel for
communication.
When an additional link from PCM 600 to the IED 670 is requested see 'Engineering guide for
IED 670 products'.
The IP address used for the Ethernet channel with IEC 61850 protocol has to be filled in by the
PST tool as part of IED 670 engineering.
5.1
PCM 600 Set up communication link per Generic IEC 61850 IED
A Generic IEC 61850 IED (Gen-IED) can only communicate with the PCM 600 in the same way
as the IED 670 products are when using the IEC 61850 protocol. That is only given for the disturbance file reading from the relays. The DRH tool is responsible for that task. For more details
about the DRH tool see 'Engineering guide for IED 670 products'.
52
CCT views and windows
6
Chapter 4
PCM 600 and CCT tool set for
station engineering
CCT views and windows
The CCT tool set runs under the operation system Windows 2000 or Windows XP. It is expected
that the user is familiar with the handling and use of the Windows platform. In this chapter only
those items are explained and shown which are specific for CCT but still based on Microsoft
windows methods.
When you start CCT you will get a screen with the different panels but no contents. Once you
have selected a project, you will get the possibilities to select different panels. The typical screen
with an open project may look like shown in the figure below.
Menu- & Toolbar
Project
Navigator
Control
&
Action
IEC 61850
Data Engineering
Properties
Output & Log
en06000033.vsd
Figure 31:
CCT: Base screen example
CCT has different panels (in PCM 600 called views). The wording panel is taken here because
the CCT use it.
Possible panels:
53
CCT views and windows
•
•
•
•
•
•
•
Chapter 4
PCM 600 and CCT tool set for
station engineering
basis and fix is the Menu and Toolbar
Navigator panel
Properties panel
Output panel
Column Visibility Control panel
Actions panel (not used in this CCT version)
the tool panel, which is the IEC 61850 Data Engineering
Project Navigator
The Project Navigator shows the four sections in a SCL project in different levels of details. The
known four sections are:
•
•
•
•
Substation section
- for information only. Only the sequence: Station > Voltage level > Bay is
shown
Communication section
- for information only. Only the configured Subnetworks and their configured
Access points are shown
IED section
- the tree structure can be expanded from > to: IED > LD > LN > DO > DA
including the full extension of complex data objects
- added DataSets, Report Control Blocks (RCB) and GOOSE Control Blocks
are shown below the LN level when enabled to be included (normally below
LLN0).
- the configured Data objects (DO) are listed with all their Data attributes in
the Attribute Editor within the IEC 61850 Data Engineering pane
Data Type Templates
- similar to the IED structure all existing LNodeTypes, DO Types, DA Types
and Enum Types are shown in a tree structure.
- The LN Types and their DOs are listed in the Attribute Editor within the IEC
61850 Data Engineering pane. The structure of DO Types, DA Types and
Enum Types is not shown in the Attribute Editor
Properties
The Object Properties window is a standard Microsoft window which allows to view and when
needed to modify properties of the selected object. Due to the fact, that CCT operates only with
the IED section properties should only be modified for the IED and the level below where useful
and needed to be adopted. It has to be regarded, that most of the properties are under control of
the configuration done by the station configurator PCM 600 or by the vendor of the IED.
This is also valid for changes done for example in the given IED naming. It must be known that
changing the IED name has influence on the substation section which is not supported by the
CCT. The station configurator PCM 600 has control over the station wide naming and addressing rules.
54
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
Remark:
The role of CCT is to do signal engineering and signal routing. The PCM 600 is responsible for
the station configuration and naming within the project. The IEC 61850 Attribute editor may be
used for monitoring and view of Logical nodes and their data objects and data attributes only.
Even when it is possible to modify values, this may be done only in cooperation of the owner of
this value which will be PCM 600 or the vendor of the IED.
Remark
Changes in the Properties may have influences to other SCL sections which are not updated by
the CCT. When doing changes the position and influence of the attribute may be well known.
They may have also influence on the IED configuration, which is vendors responsibility.
Output
The Output window is shown on the bottom array of the CCT screen when selected. It is a log
script which is used by CCT to list all activities, warnings, error messages etc. which come up
during operation of the CCT. It might be needed and used when a task does not operate as expected. The information in the output list may give a hint why it does not operate etc. The Output
view is not needed for normal operation and can be closed.
There are two different views given:
•
•
Out
- shows all messages unfiltered
Log
- shows only those messages with a category that is at least the same as the
threshold defined in chapter 4, section 7.2 "Logger options".
Column Visibility Control (CVC)
The CVC panel is available and can be used when “Report Control Engineering” or “Goose
Control Engineering” is active. It allows to select only those columns which are of interest for
signal engineering, like “Integrity Period”, “BuffTime”, etc.
The list of selections shown when the Attribute Editor is selected are not foreseen for IEC 61850
views.
IEC 61850 Data Engineering
This panel is surrounded by the above described various panels. For normal operation and after
set up the Column Visibility Control the Output panel and the CVC can be closed. The IEC
61850 Data Engineering panel has four different tabs which are used for the different engineering tasks.
•
•
•
•
Attribute Editor
Data Set Engineering
Report Control Engineering
Goose Control Engineering
More details to the different windows in the next sections.
55
CCT views and windows
6.1
Chapter 4
PCM 600 and CCT tool set for
station engineering
The toolbar and the mouse
The toolbar is fix for CCT, because there is only one tool possible the IEC 61850 Data Engineering tool. The toolbar contains the three selection items:
•
•
•
File
- is described in chapter 6, section 1 "Managing projects in CCT".
View
- enables to show a hidden panel again. The various panels are selectable.
- allows to organize all possible panel in their default position again
Tools
- updates all links and writes the object elements for the data organization requested by BRCBs and GoCBs in the IED and communication section.
Called “Update DataFlow”
- does SCL file import and export of station.SCD files (SCL File) or import of
ied.ICD files (ICD File). Export of ied.ICD files is selected in the Project
Navigator with the right mouse button and selected IED.
en06000034.vsd
Figure 32:
CCT: Toolbar with View selected
en06000036.vsd
en06000035.vsd
Figure 33:
56
CCT: Toolbar with Tools selected
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
Right mouse button
The right mouse button is partially only used in the Project Navigator. A general possibility is
given to search for an item below the actual position highlighted.
en06000113.vsd
Figure 34:
CCT: Search window
To find a node, write the name in the field and press return. The search function is not branching
into a lower level for searching.
The other use of the right mouse button is to import / export ied.ICD files in the IED section.
See chapter 6, section 1 "Managing projects in CCT" for more details.
6.2
Spreadsheet features
Based on MicroSoft.net concepts CCT allows the use of some features which may be used in
long lists to search and to filter specific information.
57
CCT views and windows
Allow Grouping
Chapter 4
PCM 600 and CCT tool set for
station engineering
Show filter row
Filter action
Row selection by
text searching
Grouping
Column header
Filter
Pinning
Add a new row
Figure 35:
en06000039.vsd
CCT: Spreadsheet features
The following features are available in CCT:
•
•
in the column header row
- Pinning
- Filtering
- Filtering with included filter bar
- Column sorting
in the spreadsheet
- Grouping
- Adding new rows and sub-rows where applicable
- Sorting
- Text matching search
Pinning
Clicking the symbol in a column header will fix or release the column to be shifted, when the
spreadsheet is moved in horizontal direction. The column will automatically shift to the next
right ascending position of fixed columns, when the columns left from the selected one are not
fixed. So to get a correct sequence of fixed columns start to fix the columns from left to right.
58
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
Filtering
This is the MicroSoft standard method of filtering in a column. Clicking the filter icon pops up
a drop down list with possible choices. The first four choices are standard, the following one is
the list of possible elements in this column. Selecting an element out of the list will mark all rows
where the filter criteria matches in a way as described by the toolbar Filter action selection.
Filter selection possibilities
The Filter Action drop down list in the Toolbar allows to select a variant of how the filtered and
not filtered rows should be marked and made visible:
•
•
•
•
HideFilteredOutRows
1. hides all rows which do not match the filter criteria
DisableFilteredOutRows
1. shows all rows but disables the possibility to make changes (edit) in the rows
which do not match the filter criteria
AppearanceOnly
- will leave all rows visible but colors the rows which do not match the filter
criteria. The color is predefined.
Default
- is the same then “HideFilteredOutRows”
Filter with included filter bar
When the Filter bar icon in the Toolbar is selected an additional row will be blended in below
the column header row. This row enables to select the specific filter criteria from a drop down
list, to enter the filter criteria right from the selection icon, to select an available element out of
the list of elements available in this column and to reset the filter for this column. It is an extended but simple to use choice possibility for filtering.
Column sorting
To sort the sequence of columns to your own criteria can be done by the standard MicroSoft
methods. Select the header element of a column and move it left or right to the position you want
to have it. The position where it will be placed will be shown by two red arrows. In the same
standard way it is possible to adjust the width of a column by selecting the right border of the
column and move it.
Grouping
Grouping allows to sort the rows of a spreadsheet in groups. The different groups which will appear depends on the type and contents of the selected row for grouping.
59
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
en06000046.vsd
Figure 36:
CCT: Grouping of rows in a spreadsheet
Sequence of operation:
•
enable grouping by selecting the Show Grouping icon in the Toolbar
- an additional area above the spreadsheet will appear which allows to build
the grouping in a hierarchical order
•
select a column as grouping criteria and drop it in the grouping area above the
spreadsheet
- the name of the selected column will appear in a new icon and the complete
spreadsheet is reorganized according to grouping possibilities
- It is possible to select another column for grouping which will be then the
second level of grouping within each group of the first level grouping
toggling the button Show Grouping in the Toolbar will show the spreadsheet in
grouped and in normal view
to deselect grouping select the column icon in the grouping area above the
spreadsheet and drop it somewhere in the spreadsheet.
•
•
60
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
Adding new rows and sub-rows or deleting a row
When the spreadsheet allows the adding of new rows this is be seen in the bottom area below
the spreadsheet. The button Add allows to add a row. All rows and sub-row possibilities are visible by select buttons per row type.
To delete a row or several rows you have to select these rows by the standard MicroSoft methods
(CTRL or SHiFT button pressed). Press the keyboard Delete key to delete the selected rows. A
confirmation window will pop up and you have to confirm your action.
Sorting
You may sort one or several rows in alphanumeric order by selecting the columns you want to
sort and click the direction for sorting button in the Toolbar.
Be aware that a sequential order as it was given by the spreadsheet before is lost (e.g. the sequence of data objects and data attributes in a complex data object structure). You have to deselect the spreadsheet and select it again to get the logical sequence back.
Text matching search
In a long list you may search for a specific row. This is possible by searching in a selected column for the start character of the element you are looking for.
Select the column in which you are searching. Type the first character of the element. The first
row which matches will be highlighted. Each time you type the character the next row which
matches will be highlighted.
6.3
CCT Column visibility control
The Column Visibility Control panel is only used to organize the columns of the
•
•
Report Control Engineering (BRCBs)
Goose Control engineering (GoCBs)
The use and definition of the different columns is described in chapter 8, section 3 "BRCB engineering" and section 4 "GoCB engineering".
61
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
en06000114.vsd
Figure 37:
CCT: Column Visibility Control panel
There are three levels of selecting a column to be shown in the panel.
1. show all attributes
2. show all columns of a group
3. select individual columns to be shown
Show all Attributes
Selected = all possible columns are visible
Show all columns of a group and / or select individual columns
Selected = all possible columns of this group are shown. Not selected = all columns are disabled.
Selected and shaded = each column can be selected individually
See figure above for the different selection methods.
62
CCT views and windows
Chapter 4
PCM 600 and CCT tool set for
station engineering
en06000090.vsd
Figure 38:
CCT: GoCB panel with all possible columns selected
en06000091.vsd
Figure 39:
CCT: GoCB panel with some columns not shown
63
CCT options and features
7
Chapter 4
PCM 600 and CCT tool set for
station engineering
CCT options and features
The options can be selected from the menulist Tools>Options. A pop up window will be displayed showing the entry point for the five different options. The five options are:
•
•
•
•
•
Environment
- Execution Mode
- LoggerOptions
IEC 61850 Options
- not supported in this CCT version
- the shown DataSet rules are used in an ABB internal CCT version to build
the default DataSets for IED products. These DataSets are always included
in the ABB IEDs.
Navigator Structure Options
- IEC 61850 Structure Options
- LogicalNode Types Structure Options; not supported in this CCT version
- LogicalNodes by IED Structure Options; not supported in this CCT version
MicroSCADA System Options
- not supported in this CCT version
NCC Gateway Communication Options
- not supported in this CCT version
en06000116.vsd
Figure 40:
64
CCT: selectable options
CCT options and features
7.1
Chapter 4
PCM 600 and CCT tool set for
station engineering
Execution mode
en06000115.vsd
Figure 41:
CCT: Execution mode option window
This window is for information only. The User Role may not be changed. The three selections
are for development purposes only. In the actual delivered configuration the changes are not taken and the user level keeps on Standard.
7.2
Logger options
en06000037.vsd
Figure 42:
CCT: Logger options window
As described in chapter 4, section 6 "CCT views and windows" CCT writes a log about all activities. This log is made visible by selecting the panel Output. In normal operation and with
skilled knowledge about the way it operates the list will include only the history of your actions.
The output view may be used when a problem occurs and it is not apparent why.
65
CCT options and features
Chapter 4
PCM 600 and CCT tool set for
station engineering
It is also used when a failure occurs or when any other abnormal sequence occurs which may be
clarified by ABB. The log file is requested by ABB when you communicate a failure or any other
item. It is therefore requested to keep the log file history for this purpose. You may clear your
hard disc from the burden of the CCT history from time to time. Ways to configure the log:
•
•
•
•
•
•
7.3
Log Category
- allows a selection from which message type upwards the messages should be
listed in the Log window of the Output panel
Log File Size
- this is the size per file! A daily file of 1MB is hard to achieve. Be aware of
the volume when you select a daily file. Clear the history from time to time!
CCT extends the file name with the date when the file was started. So a daily
log makes it easy to identify the file which is of interest.
Append Log File
- will continue to write in the existing file when a new session is started. The
different parts of each session can be identified by date and time.
Write Daily Log
- we recommend enabling this function. A daily file makes it easier for search
in a list as well to check other dates etc.
Log File Path
- the path is fixed and can not be modified
Log File Name
- the name is fixed and can not be modified
Navigator structure options
en06000038.vsd
Figure 43:
CCT: Navigator Structure Options
CCT works with the IED section, the communication section and indirect with the Data Type
Template section. The organization structure of these section is presented in the Project Navigator panel. The visible naming of the elements (Nodes) can be arranged to your demand by selecting the available name elements and concatenate them in a sequence. This can be arranged
in the IEC 61850 Structure Option.
66
CCT options and features
Chapter 4
PCM 600 and CCT tool set for
station engineering
This is possible for six different Node types and for each node type up to three naming elements
(Token) can be chosen. The available naming elements depends on the node type. You have to
chose a Separator between the naming elements to get the string readable.
Supported Node Types:
•
•
•
Communication section
- Subnetwork
- Connected access points
IED section
- IED
- Logical Node
- Access point
Data Type Templates
- Logical Node type
The configuration of a Node Type can be done as follows:
•
•
•
•
•
•
select a Node Type row or add a new one by clicking the Add button
select a node type out of the drop down list
select the various Token (1 to 3) and select a naming element out of the drop
down list
fill in the separators of your own choice
when you leave the selected row, CCT detects the changes and starts to update
the complete sections and the Project Navigator with the new presentation form.
This takes some ten seconds depending on project size etc. Wait until CCT has
finished the update.
To see the result you have to close the option window and open the sections in
the Project Navigator
An empty Token is left out. Make some examples to see the results and configure it to your demands.
67
CCT options and features
68
Chapter 4
PCM 600 and CCT tool set for
station engineering
About this chapter
Chapter 5
Set up a project in PCM 600
Chapter 5 Set up a project in
PCM 600
About this chapter
PCM 600 operates on the basis of projects. This chapter describes how a project is handled by
the tool.
69
Set up a project in PCM 600
1
Chapter 5
Set up a project in PCM 600
Set up a project in PCM 600
PCM 600 operates on projects.
•
•
•
A project contains all information about the station configuration, the IEDs, the
engineering of the IEDs when done with PCM 600, the uploaded and downloaded files and internal files produced by PCM 600 and the tool components used to
run the project.
A project is stored under the directory of PCMDataBase on the PC or workstation
on which PCM 600 is installed. PCM 600 runs various projects under the control
of PCM 600. But only one project can be active at a time. These imported projects
are handled by the MSSQL$SERVER which is part of PCMDataBase.
Projects may be grouped into two categories:
- Engineering projects for IEC 61850 based stations. Engineering projects are
focused on the complete engineering of a substation with its IEDs. The most
practical size for a project is a substation.
- System monitoring projects. System monitoring projects are focused on the
monitoring information from the operating IEDs located in several substations. The most practical size for a project depends on the structure of the
grid and customer's responsibility. This is described in the 'Engineering
guide for IED 670 products'.
Tasks in an IEC 61850 station engineering project in PCM 600:
•
•
•
•
•
•
build up a plant structure for the substation
place the bay IEDs to the voltage levels and bays
place / check the bay IEDs to be connected to the IEC 61850 subnetwork
engineer ABB IED products to generate their ied.ICD files
load all other bay IEDs with their ied.ICD files
export the station.SCD file for use in CCT
•
re-import the station.SCD file from CCT to update the ABB IED products and to
generate the ied.CID files
do signal engineering for the IEDs which are receiver of GOOSE messages.
•
70
Managing projects in PCM 600
2
Chapter 5
Set up a project in PCM 600
Managing projects in PCM 600
The PCM 600 manages the project in its own PCMDataBase which is placed on the PC or workstation running the PCM 600 tool set. The projects imported to PCMDataBase or set up in PCMDataBase are the actual available projects for PCM 600. They can be selected via the menu
bar File. But once again only one project at a time can be open.
These projects are handled by the MSSQLPCMSERVER which is included in the PCMDataBase.
It is possible
•
•
•
•
to import projects
to create new projects
to export projects
to delete projects out of the PCMDataBase
A PCM 600 project is identified by its suffix "project.PCMP"
To open a project select File>Open/Manage Projects. The Open/Manage Project window will
pop up.
New
Import
en05000552.vsd
Figure 44:
PCM 600: Open / Manage Project window
Choose an existing project
• open the tree Projects on my computer. Projects available in the PCMDataBase
are listed.
• select a project from the list and click Open Project.
71
Managing projects in PCM 600
•
Chapter 5
Set up a project in PCM 600
you may also select the project in the traditional way from the list shown in the
menubar File>list of last used projects.
Import a project
• open the tree Projects on my computer.
• select the icon Import Project.
• a standard Windows file selection window will pop up
• navigate to the directory where you have stored exported projects
• select your project to import (suffix = PCMP)
• PCM 600 will import the project. The contents will be reorganized according to
the PCM 600 internal needs. Depending on project size this can take some time.
• the imported project will be listed under the tree Projects on my computer.
• select the imported project and open it.
en05000608.vsd
Figure 45:
PCM 600: Import a project window
Create a new project
• open the tree Projects on my computer
• select the icon New Project
• a New Project window will pop up
• give the new project a name and include a description (optional)
• PCM 600 will set up a new project
• the new project will be listed under the tree Projects on my computer
• select the new project and open it
72
Managing projects in PCM 600
Chapter 5
Set up a project in PCM 600
en05000609.vsd
Figure 46:
PCM 600: Create a new project window
export a project
• open the tree Projects on my computer
• select the project you want to export
• select the icon Export Project
• a standard Windows file selection window will pop up
• navigate to the directory where you want to store the project
• the file name may be adapted to your needs
• PCM 600 prepares the contents of the project for import. The procedure is opposite to the task listed under import a project
• the project still exists in PCM 600 and can be continued to be used
delete a project
• open the tree Projects on my computer
• select the project you want to delete
• select the icon Delete Project
• a warning window will pop up
• be sure you have exported the project first before using it later
• confirm that you want to delete the project
• PCM 600 will delete all files etc. about this project from its PCMDataBase
rename a project
• this is only possible when the project is not active in PCM 600
• close the project when active
73
Managing projects in PCM 600
•
•
•
•
•
74
Chapter 5
Set up a project in PCM 600
select File>Open/Manage Projects. The Open/Manage Project window will pop
up.
select the project which should be renamed
click Rename using the right mouse button
rename the project and close the naming field
PCM 600 will rename the project
About this chapter
Chapter 6
Set up a project in CCT
Chapter 6 Set up a project in
CCT
About this chapter
This chapter describes how a project is defined, created and managed by CCT.
75
Managing projects in CCT
1
Chapter 6
Set up a project in CCT
Managing projects in CCT
The CCT manages a project in its own data base per project. CCT uses the MicroSoft Access
Data Base. The CCT projects can be stored and managed at a place which is selected by the user.
It is possible
•
•
•
•
to open projects
to create new projects
to save the actual project
to close projects
A CCT project is identified by its suffix "project.mdb".
en06000119.vsd
Figure 47:
CCT: Handling Projects
Open Project
• select File > Open Project to open an existing project. This is only possible when
no project is active at this time. When you want to run another project you have
to close the running one first.
• a MicroSoft standard window to select a file pops up. Rout to your directory
where the project you want to open is stored.
• select the project and open it
CCT will read the data base and opens the project. This will take some time and is partly shown
in a progress bar at the bottom of the CCT window.
When the project is loaded you may check that it is the one you are looking for. A typical station.scd project may look like the figure below shows in the four SCL sections. The right
screen-shot shows the structure with available DataSets and report control blocks below a
LLN0.
76
Managing projects in CCT
Chapter 6
Set up a project in CCT
en06000040.vsd
Figure 48:
CCT: Section view in the Project Navigator
Create new Project
• select Create new Project
• a Create new Project window pops up
• type a name for the new project
• browse to the location where you want to store the CCT project (Project Path)
• press OK, which is enabled when a project path is defined
77
Managing projects in CCT
Chapter 6
Set up a project in CCT
en06000120.vsd
Figure 49:
CCT: Create new Project
CCT prepares the basics in the data base and generates the internal structure of an IEC 61850
SCL file. When it has finalized its preparation task the Project Navigator shows a basic structure
with a placeholder in the substation section for a first Voltage Level and under the Data Type
Templates section the list of IEC 61850 defined Base types of type Enum. The IED and Communication sections are empty.
Save
• this action is always possible
CCT stores all values in the data base, so all additions and modifications are taken to the data
base.
Close Project
• this action is always possible
CCT asks to save the changes made, when it shall close the project and changes are pending.
CCT will close the project which will take some time when it has to save the project before.
78
Import/export station.SCD files
2
Chapter 6
Set up a project in CCT
Import/export station.SCD files
CCT as a tool for IEC 61850 signal engineering can do this tasks for a single IED or for a complete station with all IEDs linked to communication and defined in the substation section of the
SCL file.
This section describes the import and export of a station.SCD file.
2.1
Import station.SCD file
•
•
•
•
•
•
•
select Tools > SCL Import/Export > Import SCL File
a window pops up to prepare the file which should be imported
select Browse and rout to the final directory where the station.SCD file you want
to import is located
select the SCD file. You may have to change the file-type to *.SCD to get the
available files visible.
CCT checks the file to be a SCL file. If the check is successful the Import button
will be highlighted
select/ check Delete superfluous Data not represented in SCL file to be selected
press Import
en06000118.vsd
Figure 50:
CCT: Import / export station.SCD file
CCT starts to read the station.SCD file and prepares the internals to operate the project with the
file. This will take some time and is partly shown in a progress bar at the bottom of the CCT
window.
79
Import/export station.SCD files
Chapter 6
Set up a project in CCT
When the file is established you may check that it is the one you was looking for. A typical station.scd project may look like shown in figure 48
2.2
Export station.SCD file
•
•
•
•
•
save your project before
select Tools > SCL Import/Export > Export SCL File
an export window will pop up which shows a default place where CCT will store
the station.SCD file. This is done in the directory “SCL” below the directory
where the project is stored. This directory will be created by CCT if it does not
exist.
browse and select another place and/or name for the file when necessary
press Export
The CCT will generate a station.SCD file by keeping those parts which are not touched by the
CCT which is the Substation and Data Type Templates section. The communication and IED
section may have been modified and extended by CCT.
In addition CCT creates a set of ied.ccf files per IED in the project. These files include the SCL
part which is of interest for the named IED only. They may be used to re-import the IED part to
the IED configurator tool directly. These files are located at the same place as the station-SCD
file.
80
Import/export ied.ICD files
3
Chapter 6
Set up a project in CCT
Import/export ied.ICD files
CCT as a tool for IEC 61850 signal engineering can do this tasks for a single IED or for a complete station with all IEDs linked to communication and defined in the substation section of the
SCL file.
This section describes the import and export of an ied.ICD file.
CCT can be used to configure DataSets and report control blocks (BRCBs) for a single IED before it is integrated in a station project. This makes sense when the IED is used more then once
in the project. Import of the ied.ICD file to CCT, do DataSet and BRCB engineering and export
it back allows to use the extended IED as a template for similar or same control or protection
IEDs.
In the actual version of PCM 600 it is only possible to include client IEDs in a station project
via CCT.
3.1
Import ied.ICD file
•
•
•
•
•
•
•
•
select Tools > SCL Import/Export > Import ICD File
a window pops up to prepare the file which should be imported
select Browse and rout to the final directory where the ied.ICD file you want to
import is located
select the ICD file
CCT checks the file to be a SCL file. If the check is successful the Import button
will be highlighted
you can select more then one ied.ICD file to be imported at the same time. Repeat
“Browse” until all files you may import are selected.
check that the files you want to import are selected. The function “Generate defaults for MicroSCADA” is not supported in this CCT version.
press Import
81
Import/export ied.ICD files
Chapter 6
Set up a project in CCT
en06000117.vsd
Figure 51:
CCT: Import / export ied.ICD file
CCT starts to read the ied.ICD file and prepares the internals to operate the project with the
file(s). This will take some time and is partly shown in a progress bar at the bottom of the CCT
window.
When the file(s) is/are established you may check that they are the ones you was looking for.
3.2
Import of a client IED via CCT into a station project
A client IED will be imported in the same way as described above. To integrate it in a station
project you have to load the station project first and then import the client IEDs in addition.
•
•
•
•
•
•
•
•
82
load the station project to which the client IEDs belong
import the client IEDs as described
check the client IEDs in the IED section. They must be presented in the tree structure as given in chapter 6, section 1, fiure 48. A client IED contains a logical device and at least three Logical nodes, the two standards plus a client specific LN
of group “I” (ITCI or IHSI).
select the access point of the IED in the Project Navigator and configure the subnetwork name out of the drop list in the Propertiespane. It must be the same subnetwork then the other IEDs are connected to.
define the Access Point Name according to the rules of the project
repeat the steps for all imported client IEDs
save the project, close the project and open the project again
the client IEDs are now completely included in the SCL structure of the IED section and in the communication section
Import/export ied.ICD files
•
3.3
Chapter 6
Set up a project in CCT
they are not included in the substation section. In this case it is a formal information which has no influence on the normal signal engineering for reports or for
GOOSE messages
Export ied.ICD file
•
•
•
•
•
save your project before
the export of an ied.ICD file is only possible when the specific IED is selected.
Select the IED in the Project Navigator and press the right mouse button. Select
Export ICD
an export window will pop up which shows a default place where CCT will store
the station.SCD file. This is done in the directory “SCL” below the directory
where the project is stored. This directory will be created by CCT if it does not
exist.
browse and select another place and/or name for the file when necessary
press Export
en06000121.vsd
Figure 52:
CCT: Export ied.ICD file
The CCT will generate an ied.ICD file for the selected IED. The file may be re-imported to the
IED configurator tool for further use.
83
Import/export ied.ICD files
84
Chapter 6
Set up a project in CCT
About this chapter
Chapter 7
Station configuration with PCM 600
Chapter 7 Station
configuration with
PCM 600
About this chapter
This chapter describes how a station can be configured to fulfil the IEC 61850 requirements for
signal engineering. The configuration of the substation from voltage level to bay and IEDs and
the configuration of the communication structure is part of this chapter.
85
Set up a substation for IEC 61850
1
Chapter 7
Station configuration with PCM 600
Set up a substation for IEC 61850
PCM 600 organizes the structure of a substation in the Plant Structure window. The plant structure is used to locate each IED in its location within the electrical grid. It is a geographical image
of the substation and the bays within the substation.
You will build up the plant structure according to your project requirements. To do this PCM
600 offers some elements which build the hierarchical order from a Center down to the IEDs in
a bay. The organization of the station according to IEC 61850–6 is done in PCM 600 on the basis
of the 'Product related naming' (IEDName). This is shown in chapter 2, section 3.1 "The Substation section", figure 8.
The following levels are available:
1. Project = Center (not used for the naming)
2. Region = when your grid might be subdivided into regions this level should be
used in addition (optional)
3. Substation = Name of the substation (relevant for object designation)
4. Voltage Level = identifies to which grid type or part in the substation the IED belongs to
5. Bay = Bay within the voltage level
6. IED = selection of the IED which is used in the bay. Several IEDs are possible
within a bay (e.g. one control IED and two protection IEDs)
Level (2.) is optional all other level are a must to identify an IED.
Once a plant structure is built the identification should be renamed by the names/identifications
used in your project and to the specification for object identification as described in chapter 2
"IEC 61850 station engineering". Use the right mouse button to build the plant structure and to
rename the elements.
en05000565.vsd
Figure 53:
PCM 600: Set up a plant structure
Building a plant structure using the Object Types view
This is useful when a complete grid with a large number of IEDs have to be built.
86
Set up a substation for IEC 61850
Chapter 7
Station configuration with PCM 600
Steps to build a plant structure:
•
•
•
•
•
•
select the Object Types view
place the Object Types window beside the Project Explorer window by selecting
the Object Types tab and move it outside the Project Explorer window.
select the General pane
select the elements you need and place them in the plant structure by drag and
drop
to select an IED open the Transmission IED pane and follow the procedure described in the next chapter
close the Object Types window
select IED
en05000557.vsd
Figure 54:
1.1
PCM 600: Set up a plant structure by using Object Type window
Naming conventions for IEC 61850
The following definition is taken from IEC 61850–6 clause 8.4:
The SCL model allows two kinds of object designation:
1. A technical key, which is used on engineering drawings and for signal identifications. This is contained in the attribute name as identification of each object. If
this value is used as reference to an object, it is contained in an attribute name
87
Set up a substation for IEC 61850
Chapter 7
Station configuration with PCM 600
starting with a string denoting the reference target object type, and ending with
the string Name. The technical key is used within SCL for referencing other objects. Observe that name is a relative identification within a hierarchy of objects.
2. A user oriented textual designation. This is contained in attribute desc. Attributes
are not allowed to contain carriage return, line feed or tab characters. The semantics of desc shall also be relative within an object hierarchy.
End of reference to the standard.
PCM 600 takes care for these two possibilities. The two possible designations naming are available per object in the object properties for all hierarchical levels beginning with the station as
highest level.
The technical key is automatically generated by PCM 600 based on the rules and type specifications of IEC 61346 and the definitions done for substations by a technical committee. The
technical key is shown in the Object Properties under “SCL TechnicalKey”.
•
•
•
the start point is the station which is predefined by “AA1” where 1 is the index.
Leave the station name untouched, even when it is the wrong station name. PCM
600 needs this start definition to build the technical key by itself.
the second hierarchical level is the voltage level. The voltage level has to be selected in the Object Properties from a drop list. The corresponding character is
automatically included in all objects. The drop list explains the voltage range for
each character so it should be no problem to select the right character. The list is
build on the definitions of the standard.
the bay and the IED is appended with the coding defined in the IEC 61346 standard and the substation definition lists.
The “user oriented textual designation” is visible in the plant structure for each object. It is the
name given by default or changed via the Rename possibility. It is shown in the Object Properties in the row Caption.
en06000029.vsd
Figure 55:
88
PCM 600: IEC 61850 signal designation concept
Set up a substation for IEC 61850
Chapter 7
Station configuration with PCM 600
In the above figure the bay named in the example “B_TR42” is visible in the object properties
with the two designations. The technical key AA1C1Q1 can be read like this:
•
•
•
AA1 = station 1 in the project
C1 = voltage level from 380 to 420 kV
Q1 = the first bay in the voltage level
Selection of object designation for the technical key
As described before PCM 600 supports two possibilities for object designation. One of this two
possibilities will be selected for the technical key in the SCL file when you export the station as
station.SCD file. Using the designation according to IEC 61346 guarantees (Navigator Object
Technical Key) that the naming is correct but maybe not useful in the naming your station is using. Using your own designation model (PCM Navigator Object Caption) is useful and can be
done when the total length according to IEC 61850 (32 characters) is regarded and the designation for each level is unique.
It should also be checked and notified when one of the user IEDs (most likely the client IEDs)
have additional rules for the length of each level etc. Be careful and make a general concept for
all partners in the project. See the standard IEC 61850–6 and chapter 2 "IEC 61850 station engineering" for more details.
1.2
PCM 600 selection of an IED
This section includes the description how to select an ABB IED 670 product as bay IED. For the
total capability see 'Engineering guide for IED 670 products'.
A control or protection IED 670 can be delivered in two general versions:
•
•
open configuration IEDs
pre-configured IEDs
When selecting an IED 670 a wizard is displayed which helps you to make the correct selection.
Open configuration IED
An open configuration IED is described by:
•
•
the delivered hardware
the delivered lists of selected functions
It includes:
•
a set of ordered functions available for engineering the logic and operation of the
functions
It does not include:
•
•
•
any configuration of the application configuration program
any engineering preparation for the IO hardware and IO signals
no defined settings other then the default values
89
Set up a substation for IEC 61850
Chapter 7
Station configuration with PCM 600
It is important to understand, that the list of delivered functions correspond to the list of available
function blocks in the IED itself. You can not use more function blocks than ordered.
An IED is selected by:
•
•
•
•
selecting the correct IED version 1.0 onwards
type in the IP address for the IED to communicate with PCM 600. This IP address
may be the same as used for the communication protocol (e.g. IEC 61850 or DNP
3.0 on Ethernet) but it must not be the same. This IP address is the link to the
PCM 600 tool set.
Browse to the folder where your order specific zip-file is stored.
When you do not use an order specific configuration indicate that in the selection
box.
en05000643.vsd
Figure 56:
Order specific IED selection
Pre-configured IED
A pre-configured IED is described by:
•
•
•
the delivered hardware loaded with the basic functions and logic, ready for use
after some project specific engineering additions like IO signal marshalling etc.
the delivered engineering configuration
- configured logic with basic functions active for direct use
- predefined signals for IO which needs only to be routed to physical IO boards
the optional functions are available in the engineering tool fully configured and
presented in a template
It does not include:
90
Set up a substation for IEC 61850
•
•
Chapter 7
Station configuration with PCM 600
adaptations to the project specific settings
IO signal routing for application specific IOs
A pre-configured IED is ready to use after some minor engineering additions, which are in any
way project specific. Similar to the order specific version it includes only those functions and
options which are ordered and available in the IED itself.
en05000644.vsd
Figure 57:
Pre-configured IED selection
When the pre-configured IED versions are not delivered in a zip file. Skip this window by selecting No PreConfig File. Check the availability of pre-configured IED versions in the CAP
531 template folder.
1.3
PCM 600 Generic IEC 61850 IED
The Generic IEC 61850 IED (Gen-IED) has to be installed when additional non ABB bay IEDs
are used in the project. The tasks to integrate these IEDs are:
•
•
select a Gen-IED where requested
import the ied.ICD file which belongs to this IED
91
Set up a substation for IEC 61850
Chapter 7
Station configuration with PCM 600
en06000031.vsd
Figure 58:
Generic IEC 61850 IED selection
The vendor has to supply an ied.ICD or ied.SCD file for each IED.
Import of an ied.ICD file for a Gen-IED
en06000032.vsd
Figure 59:
Generic IEC 61850 IED import of ied.ICD file
After a Gen-IED is installed it is necessary to load the corresponding ied.ICD file.
•
•
•
•
•
•
92
select the Gen-IED
select Import IED SCL... with the right mouse button out of the menu
a standard Microsoft windows for file selection pops up. Navigate to the directory where the ied.ICD or .SCD file is located and open the file for import
a selection window SCL Import Options pops up
leave the Import Type as set to “Update PCM Structure from SCL”. The existing
already build SCL file structure will be extended with the contents of the imported file. In the other case the ied.ICD file would be append to the SCL file and is
not included in the structure as already given and necessary.
open the Advanced Options
Set up a substation for IEC 61850
•
•
Chapter 7
Station configuration with PCM 600
Select the “Replace... ” alternative. Because it is a Gen-IED it must be possible
to replace the IED object types with the known Generic IEC 61850 IED object
types.
select “Allow overwriting... ” . The Gen-IED is a not known IED until now for
the PCM 600. It must be possible to overwrite the default IED type with the type
defined in the vendors IED.
The SCL file import starts and a progress window shows the status. A message will indicate the
conclusion of a successful import. The IED name may not change by loading the file. Check and
adapt the IED name to the projects definition with the Rename selection in the right mouse button menu.
Note
The actual version of PCM 600 does not support the integration of client IEDs in the plant structure nor in the communication structure.
This is actual only possible by adding the client ied.ICD file in the CCT and configure the communication section in the CCT with the additional client IED. See chapter 6, section 3 "Import/export ied.ICD files" how to do it.
93
Set up communication for IEC 61850
2
Chapter 7
Station configuration with PCM 600
Set up communication for IEC 61850
The actual version of PCM 600 supports a communication network with one subnetwork according to IEC 61850 only. Client IEDs can be integrated in a station project by CCT only.
The communication structure can be checked by selecting it in the Project Explorer beside the
Plant structure. By opening the tree structure it is visible that the OPC server of the PCM 600
itself is on top with the NETWORK below.
All bay IEDs configured in the Plant Structure must be shown and connected to the NETWORK. In the figure below also the client IEDs are presented after re-import the station.SCD
file from the CCT to PCM 600 for final IED 670 engineering.
en06000208.vsd
Figure 60:
PCM 600: Communication Structure with IEDs
The Logical devices of an IED are listed when opening the IED. This is for information only
Adding the IP address of an IED
The communication structure allows to add/modify the IP address of an IED in the Object Properties.
94
Set up communication for IEC 61850
Chapter 7
Station configuration with PCM 600
en06000209.vsd
Figure 61:
PCM 600: Adding the IP address of an IED
95
Import/Export station.SCD files
3
Chapter 7
Station configuration with PCM 600
Import/Export station.SCD files
The IEC 61850 standard defines four file types in the sequence of engineering. These files have
a different definition which is explained in IEC 61850–6 clause 7. Three of this file type are used
in the engineering process for an IED 670.
•
•
•
ied.ICD = IED Capability Description
station.SCD = Station Configuration Description
ied.CID = Configured IED Description
Export a station.SCD file
The procedure is a follows:
•
•
•
•
•
•
•
select the station in the plant structure. See figure 62
select “Export System SCL...” with the right mouse button
a standard Windows menu pops up to select a location. Choose a destination
where the file should be stored and give it a name
PCM 600 starts the process and will generate a new selection window. See
figure 63
select “SCL Object Naming” variant for your project. See chapter 7, section 1
"Set up a substation for IEC 61850".
check that the selection box “Export Private Section” is blank (not set). IEC
61850–6 defines in clause 8.2.6 the possibility to include a private structure of
presentation in the SCL file for later reuse etc. This is actually not supported and
not needed.
start export. A progress window will show the export procedure which will take
some time depending on the number of IEDs.
Station
en06000025.vsd
Figure 62:
96
IEC 61850: Export station.SCD step 1
Import/Export station.SCD files
Chapter 7
Station configuration with PCM 600
en06000026.vsd
Figure 63:
IEC 61850: Export station.SCD step 2
Import a station.SCD file
When an exported station.SCD file is extended with the signal engineering by the CCT tool it is
necessary to import the extended station.SCD file back and update the IED 670 products with
the additional configuration.
The procedure is as follows:
•
•
•
•
select the station in the plant structure.
select “Import System SCL...” with the right mouse button
a standard Windows menu pops up to select the file to be imported. Browse to the
destination the file is stored and start the reading.
a selection menu pops up which queries how the file should be handled during
import. See figure 64.
1. The standard is the basic window as shown in the right screen-shot in
figure 64
2. “Update PCM Structure from SCL” expects that the file is the one which was
exported but now extended by configuration actions done in CCT. This is the
normal case and set by default.
3. “Append SCL to PCM Structure” will append the information for each IED
to the existing ICD part in the IED. This is useful, when the station configuration part is done on a basis ied.ICD file with no specific engineering or the
ICD file does not exist for the IED 670 until now.
4. “Advanced Options” expand the window as shown in the left screen-shot of
figure 64.
5. “Don't import ...” protects the existing IEDs in case the station.SCD file does
not match the original configuration in PCM 600.
6. “Replace unknown ...” can be used when it is known, that the file includes
additional IEDs which are needed. The IED of type “Generic IEC 61850
IED” is used to integrate these kinds of IEDs in the plant structure etc.
7. “Allow overwriting ...” should only be done when it is clear what happens
and justified with the complete project.
97
Import/Export station.SCD files
•
Chapter 7
Station configuration with PCM 600
start “Import” when you have completed your definitions. A progress window
will show the import procedure which will take some time depending on the number of IEDs.
en06000027.vsd
Figure 64:
3.1
IEC 61850: Import station.SCD file
ied.CID file generation for IED 670
This part is described in 'Engineering guide for IED 670 products'. It must be seen in the whole
engineering sequence and requests knowledge about the IED 670 engineering.
98
About this chapter
Chapter 8
Signal engineering with CCT
Chapter 8 Signal engineering
with CCT
About this chapter
This chapter describes how the data objects in IEC 61850 are configured to data sets. How the
different control blocks are configured and how the links for the control blocks to clients or other
IEDs is done.
99
IEC 61850 Attribute Editor
1
Chapter 8
Signal engineering with CCT
IEC 61850 Attribute Editor
The IEC 61850 attribute editor in this CCT version is not used for editing. It is only allowed and
possible to view the structure and contents of Logical nodes and their data objects and data attributes. The organization of Logical nodes and their contents is under control and responsibility
of the IED vendor.
The structure and content of a Logical node is defined in IEC 61850–7–3 and IEC 61850–7–4.
It describes the data objects, the data attribute classes and the base types as mandatory or optional elements of a Logical node. The IED products define their Logical nodes based on this standards. But these Logical nodes are described as LN types, because these LN contain only the
used and available data objects etc. So each IED product will have its own set of used Logical
node types.
The SCL structure takes care of this in the Data Type Templates section where all used and
available Logical node types, their data object types and their data attribute types and when given their additional base types of type Enumerated are included. The reference to the LN types is
given in the IED section for each logical node by the LN type name as part of the Logical node
identification.
en06000045.vsd
Figure 65:
CCT: IEC 61850 Attribute editor (viewer)
The attribute editor can be used to get an overview and to verify the content of a Logical node.
Select a Logical node or a data object below the LN in the Project Navigator. Select Attribute
Editor in the IEC 61850 Data Engineering pane.
100
IEC 61850 Attribute Editor
Chapter 8
Signal engineering with CCT
The visible list may be sorted in the sequence as shown in the figure above. In the example figure
a Logical node of type CVMMXU is selected. This LN type is used in IED 670 products and
represents the standard measured values of a bay. A part of the list of data attributes of the data
object “TotW” is shown. The different columns from left to right contain the description values
of each data attribute in a row listed in column one (Name).
No. Title
IEC 61850–
Description (taken from the standard)
1
Name
6, clause 9.5.4, table 44 Reference of the last named data attribute or basic type
described in this row
2
Descr.
6, clause 9.5.4, table 44 Description in free text form of the data attribute
3
FC
6, clause 9.5.4, table 44; Functional constraint of this data attribute
7–2, clause 10.2.2.4.2;
7–3 in data class tables
4
TrigOPt.
dchg
6, clause 9.5.4, table 44; Trigger a report transmission when the value changes. E.g. new
7–2, clause 10.2.2.4.3; position of a disconnector.
7–3 in all data class
tables
5
TrigOpt.
qchg
6, clause 9.5.4, table 44; Trigger a report transmission when the quality value changes.
7–2, clause 10.2.2.4.3; E.g. oscillatory of a binary signal because of a sensor failure
7–3 in all data class
etc.
tables
6
TrigOpt.
dupd
6, clause 9.5.4, table 44; Trigger a report transmission when a data value is updated.
7–2, clause 10.2.2.4.3; E.g. counter values are frozen and ready for transmission
7–3 in all data class
tables
7
Basic
Type
6, clause 9.5.4, table 44, Basic type according to definition in IEC 61850–7–2 clause
7–2, table 2; 7–3 in all
5.5.2 and the enumerated types in IEC 61850–7–3 clause 6
data class tables
(Attribute Types)
8
Type
6, clause 9.5.4, table 44 only used if “Basic Type” = Struct or Enum to refer to the appropriate enumeration type or DAType when Struct is given.
9
Value
6, clause 9.5.4.4
Value of the data attribute when it can be taken from the SCL
file
10
Short
Address
6, clause 9.5.4.3
The short address of a data attribute which can be used for several purposes. Do not modify them.
11
Value
Kind
6, clause 9.5.4.1
Special information about the state of engineering process.
Used / modified by the engineering tools
12
Count
6, clause 9.5.4, table 44 Used by the engineering tools internal. Optional for data
attribute of type structure. Shall state the number of array elements in the case where the attribute is an array.
101
Data set engineering
2
Chapter 8
Signal engineering with CCT
Data set engineering
The concept of DataSets is described in a brief form in chapter 2, section 3.4 "Signal engineering".
select FC
select LN
add DataSet
select DO
select DA
en06000043.vsd
Figure 66:
CCT: Generating a DataSet
When the Data Set Engineering pane is selected you will get a pane which includes four list boxes. One is for information only (Filtered Preview). The other three are needed to configure a
DataSet:
•
102
Data Sets
- lists all available DataSets with their names located in that Logical node
Data set engineering
Chapter 8
Signal engineering with CCT
-
•
•
•
allows to add a new DataSet
allows to remove (delete) an existing DataSet
to change the name of a DataSet select the DataSet and click again. The field
is ready to accept a new name entry
- regard the rules for DataSet naming according to IEC 61850–7–2 clause
11.2.2.1
Data Set Entries
- lists all selected Logical nodes, Data objects or data attributes which are selected to be a member of the DataSet.
- the used functional constraint (FC) is shown in brackets at the end
- allows to remove (delete) a selected member out of the list.
- the address (reference) of each selected FCD or FCDA is shown. The reference includes the logical device part below the server as start point. This
gives the possibility to select any FCD, FCDA within the IED to be a member of the DataSet. In which way this is useful to get the right information
sorted logically is a question to the project.
- the selected Logical nodes with their data objects or the selected data objects
directly are called Functional Constraint Data (FCD) or Functional Constraint Data attributes (FCDA) when the member is a direct data attribute
IED Data Model
- lists all Logical nodes within the IED with their data objects and data attributes in a tree structure
- each element can be selected to be a member of a DataSet
- allows, requests to select a FC to separate those attributes which will be
member of the DataSet entry. Only FC = MX or ST are possible constraints
for reports to clients.
- allows to add the selected object to the list box of Data Set Entries. It will be
then a member of the DataSet (Add)
- allows to modify an already available member by overwriting its contents
with the one of the selected object (Modify)
Filtered Preview
- This list box shows all data attributes of the selected FC of the selected object
in the IED Data Model list box. These attributes will be transmitted in case
one of the data attributes has forces a trigger to send the DataSet member.
Remark
Analyzing all defined data attributes defined in IEC 61850–7–3 only data attributes with FC =
MX or ST are marked with the capability to generate a trigger. And they belong to process data
objects which contain the process information used at runtime. All other data attributes belong
to control (commands), settings, functional configuration parameters or descriptions. These information are handled by other IEC 61850 communication services and are not part of a report.
103
Data set engineering
Chapter 8
Signal engineering with CCT
select DA only
DO with stVal; q; t
en06000048.vsd
Figure 67:
CCT: DataSet with FCDA member
Remark
CCT has to update the contents of all four list boxes whenever a new object, item etc. is selected.
To do this it reads the main part of data base to identify which objects etc. have to be presented.
This takes some time and it is not directly shown by an hourglass or similar. A small help in this
situation would be to start the Windows Task Manager and minimize it. The small dynamic icon
in the low right corner shows when the CPU is active.
Task Manager
en06000204.vsd
Figure 68:
104
CCT: CPU activity
Data set engineering
Chapter 8
Signal engineering with CCT
To configure a DataSet the following steps are requested in CCT:
•
•
•
•
•
•
•
•
•
select the Data Set Engineering tab in the IEC 61850 Data Engineering pane
select the Logical node where the new DataSet should be located. This should be
in normal cases the LLN0 of a LD.
when requested and agreed in a project it is possible by the IEC 61850 standard
to locate the DataSet in any LN. This is not allowed for DataSets which are used
by GOOSE messages. These DataSets are only allowed in LLN0 !
press the Add button to add a new Data Set in the Data Sets list box
give the DataSet a name. The name must be unique within the station to be able
to identify it in the communication between a client and a server IED.
select the FCD or FCDA which should be member of the DataSet in the IED Data
Model list box.
select the correct FC out of the list in the Func. Constraint list box
click Add to add the FCD, FCDA to the Data Set Entries list box
click Modify when the selected member of the Data Set Entries list box should
be replaced or modified by the FCD, FCDA selected in the IED Data Model list
box
Repeat the procedure for all DataSets which are needed in this IED. Continue to do it for all IEDs
where additional DataSets are requested.
2.1
Predefined DataSet
The IEC 61850 standard allows to have predefined DataSets which the vendor of an IED has
included in his product. These predefined DataSets will be visible when you open an IED and
will be listed under the LLN0.
These DataSets may be modified or extended in a project. The possibility to do it must be announced by the vendor of the IED.
ABB has defined four predefined DataSets for the IED 670 products:
•
•
•
•
MeasFlt
- includes those measured values which will be transmitted on dchg trigger
given by a threshold value (deadband)
StatIed
- includes the behavior status of all Logical nodes
StatNml
- includes the trip signals (operate) of all protection Logical nodes
StatUrg
- includes the urgent alarms of the Logical nodes. The definition of what is urgent was done by ABB experts and may be checked by the project
105
BRCB engineering
3
Chapter 8
Signal engineering with CCT
BRCB engineering
The concept of buffered report control blocks (BRCB) is described in a brief form in chapter 2,
section 3.4 "Signal engineering".
en06000047.vsd
Figure 69:
CCT: Generating and link of a BRCB
When the Report Control Engineering pane is selected you will get a pane which contains a list
with several columns and some or a lot of rows. Each row represents a BRCB description with
all BRCB attributes which are of interest.
When already client IEDs are linked to that BRCB this is visible by the icon element to expand
the BRCB for next level rows. Each next level row contains the identification of a linked client
IED.
The five main steps to generate a BRCB are:
•
106
add a new BRCB row to the list by clicking Add... Report Control in the bottom
area of the pane
BRCB engineering
•
•
•
•
•
Chapter 8
Signal engineering with CCT
give the BRCB a unique name according to the rules described in IEC 61850–7–2
clause 14.2.2.2 and the rules defined in the project
select the DataSet out of the list of available DataSets for this BRCB. Always
only one DataSet per BRCB. See the example in the figure above
link the BRCB to the client IEDs which should receive these event telegrams.
This is done by selecting the icon of the Logical node of the client IED (e.g. ITCI
or IHSI) and link it to the name field of the corresponding BRCB by using the
drag-and-drop method. Repeat this for all client IEDs which should receive the
information. See the arrow in the figure above.
configure the BRCB attributes to the standards defined in the project.
do Update DataFlow by selecting this task via the menubar Tools > IEC 61850
Data Flow Engineering. CCT will now add the needed information in the SCL
file in:
- the IED section for the 'BRCB' in the Logical node defined for this DataSet
and therefore for the BRCB. Should be normally LLN0
- the IED section with the identification of the connected client IEDs per
BRCB
en06000036.vsd
Figure 70:
CCT: Update Dataflow
Configuration of the BRCB attributes
The possible attributes which are needed to describe the operation etc. of a BRCB are included in
•
•
•
IEC 61850–6 clause 9.3.8 and listed in table 22, table 23 and table 24
IEC 61850–7–2 clause 14.2 and mainly listed in table 23
the attributes used by the CCT to get the description from the user are all listed
in the CVC selection box for the BRCB.
For the identification of a column the same text is used in the BRCB list and in the CVC. To see
them in the CVC completely you have to select an element. The complete description will pop
up, when there is more text then in the visible part. The sorting order for the column may be
changed to your demands. So the only element to make the link to CVC is the identification text
of the column. How to operate the CVC see chapter 4, section 6.3 "CCT Column visibility control".
107
BRCB engineering
Chapter 8
Signal engineering with CCT
BRCB attributes
1
23
Client IED attributes
en06000205.vsd
Figure 71:
108
CCT: CVC for BRCB
BRCB engineering
Table 1:
Chapter 8
Signal engineering with CCT
BRCB attributes
No. Title
IEC 61850–
Description (taken from the standard)
1
Name
6, clause 9.3.8, table
22,1; 7–2, clause 14.2,
table 23,1
Name of the report control block. This name is relative to the
LN hosting the RCB, and shall be unique within the LN
2
Descr.
6, clause 9.3.8, table
22,2
The description text
3
DataSet
6, clause 9.3.8, table
22,3; 7–2, clause 14.2,
table 23,5
The name of the data set to be sent by the report control block;
datSet can only be empty within an ICD-File.
4
Identifier 7–2, clause 14.2, table
23,3
The attribute RptID shall be the client-specified report identifier
of the BRCB that has caused the generation of the report. If the
report identifier value of the BRCB is NULL, then the instance
name (the whole path-name) of the BRCB shall be reported as
the report identifier.
NOTE: The report identifier field may be used by clients to distinguish between reports from various BRCBs. This value is
mirrored by the server.
5
Integrity
Period
6, clause 9.3.8, table
22,4; 7–2, clause 14.2,
table 23,19
Integrity period in milliseconds see IEC 61850-7-2. Only relevant if trigger option period is set to true
If TrgOp is set to integrity, the attribute IntgPd shall indicate the
period in milliseconds used for generating an integrity report.
An integrity report shall report the values of all members of the
related DATA-SET. BufTm shall have no effect when this
change issues a report.
A value of 0 shall indicate that no integrity reports shall be
issued.
NOTE: An integrity scan may transmit the same values as a
general interrogation. The integrity scan is issued by the server.
The general-interrogation is issued by the client.
6
Config.
Ref.
6, clause 9.3.8, table
22,6; 7–2, clause 14.2,
table 23,6
The configuration revision number of this report control block
7
Buff
6, clause 9.3.8, table
22,7
Specifies if reports are buffered or not; see IEC 61850-7-2
8
Buff.
Time
6, clause 9.3.8, table
22,8; 7–2, clause 14.2,
table 23,16
Buffer time; see IEC 61850-7-2
The attribute BufTm shall specify the time interval in milliseconds for the buffering of internal notifications caused by
data-change (dchg), quality-change (qchg), dataupdate (dupd)
by the BRCB for inclusion into a single report.
Upon receipt of the first internal event notification of the referenced DATA-SET, the BRCB shall start a timer of the duration
buffer time. When the timer expires, the BRCB shall combine
all internal events that have been received during the time interval into a single report. The next internal event following the
timer expiration shall signal the new start of that timer. The
default value of 0 shall be reserved to indicate that the buffer
time attribute is not to be used by the BRCB. Each internal
event shall cause the BRCB to send a single report. The value
shall be settable in 1 ms increments and shall be able to convey up to 1 h of buffer time
109
BRCB engineering
Chapter 8
Signal engineering with CCT
No. Title
IEC 61850–
Description (taken from the standard)
9
Max.
Enabled
6, clause 9.3.8, table
23,2
Defines the maximum number of report control blocks of this
type, which are instantiated at configuration time in the LN (and
then used online)
10
Report
6, clause 9.3.8, table
Enabled 23,1
Description
The description text
11
TrigOpt.
Dchg
The attribute TrgOp shall specify the trigger conditions which
shall be monitored by this BRCB. The following values are
defined:
7–2, clause 14.2, table
23,18
•
12
TrigOpt.
Qchg
7–2, clause 14.2, table
23,18
data-change (dchg)
•
quality-change (qchg)
•
data-update (dupd)
•
integrity
•
genral-interrogation
The trigger options dchg, qchg, and dupd refer to the attribute
trigger option (TrgOp) of the DataAttribute of the common
DATA classes in IEC 61850-7-3. The trigger options integrity
and general-interrogation shall be trigger conditions defined by
the attributes IntgPd and GI of the BRCB respectively
Details related to the generation of a report based on the different trigger options shall be as specified in 14.2.3.2.3.
13
TrigOpt
Dupd
7–2, clause 14.2, table
23,18
14
TrigOpt.
Period
7–2, clause 14.2, table
23,18
15
Seq. No. 7–2, clause 14.2, table
23,8
If a BRCB does not support one or more of the trigger options,
the attempt to set the TrgOp attribute to TRUE for one of these
not supported values, shall cause a negative response of the
SetReportControlValues service.
The attribute SqNum shall specify the sequence number for
each BRCB that has report enable set to TRUE. This number is
to be incremented by the BRCB for each report generated and
sent. The increment shall occur once the BRCB has formatted
the report and queued the report to the N-1 protocol layer. The
first report following the setting of the report enable to TRUE
shall contain sequence number 0.
If TRUE SqNum shall be included in the report.
16
Time
Stamp
7–2, clause 14.2, table
23,9
The attribute TimeOfEntry shall be the time, when the entry is
added to the buffer. That time may be different to the time
stamp of the data, which shall be the time when the event
occurred that caused the entry to be created.
If TRUE TimeOfEntry shall be included in the report.
17
110
Data Set 7–2, clause 14.2, table
23,11
DataSet-name; If TRUE DatSet shall be included in the report.
BRCB engineering
Chapter 8
Signal engineering with CCT
No. Title
IEC 61850–
Description (taken from the standard)
18
7–2, clause 14.2, table
23,10
The reason for inclusion shall be included in the report if the
optional fields to include in report attribute (OptFlds) of the
BRCB includes reason for inclusion (=TRUE); otherwise, it
shall be omitted. The value for the reason for inclusion shall be
set according to the TrgOp that caused the creation of the
report. The value range for reasons for inclusion shall be as
listed
Reason
Code
•
data-change (caused by TrgOp = dchg in an instance of
DATA)
•
quality-change (caused by TrgOp = qchg in an instance of
DATA)
•
data-update (caused by TrgOp = dupd in an instance of
DATA)
•
integrity (caused by the attribute IntgPd in the BRCB)
•
general-interrogation (caused by setting the attribute GI of
the BRCB to TRUE by a client).
reason-for-inclusion. If TRUE ReasonCode shall be included in
the report.
19
Data
Ref.
7–2, clause 14.2, table
23,12
The parameter DataRef shall contain the functional constrained
data (FCD) of the DataAttribute values included in the report.
data-reference. If TRUE DataRef or DataAttributeReference
shall be included in the report.
20
Buffer
Overfl.
7–2, clause 14.2, table
23,13
BufOvl – buffer overflow occurred
The parameter BufOvl shall indicate to the client that a buffer
overflow occurred. The BRCB shall set this field in the first
report that is sent with events that occurred after the overflow.
buffer-overflow. If TRUE BufOvfl shall be included in the report.
21
Entry Id. 7–2, clause 14.2, table
23,14
EntryID = entry identifier
The parameter EntryID shall represent an arbitrary OCTET
STRING used to identify an entry in a sequence of events of a
BRCB.
entryID; If TRUE EntryID shall be included in the report.
22
Conf.
Ref.
23
Segm.
7–2, clause 14.2, table
23,15
conf-revision; If TRUE ConfRev shall be included in the repor.
111
BRCB engineering
Table 2:
112
Chapter 8
Signal engineering with CCT
Client IED attributes
No. Title
IEC 61850–
Description (taken from the standard)
1
Id
6, clause 9.3.8, table
24,2
The instance identification of the LD where the LN resides
2
ReportControlId
3
LogicalNodeId
6, clause 9.3.8, table
24,3,4,5
The LN prefix. The LN class according to IEC 61850-7-4. The
instance id of this LN instance of below LN class in the IED
4
Order
Sequence order number within the list of client IEDs ????
5
Client
Logical
Node
Name
The combined name out of listed elements to get the complete
address of the client
GoCB engineering
4
Chapter 8
Signal engineering with CCT
GoCB engineering
The concept of GOOSE control blocks (GoCB) is described in a brief form in chapter 2,
section 3.4 "Signal engineering".
en06000050.vsd
Figure 72:
CCT: Generating and link of a GoCB
When the Goose Control Engineering pane is selected you will get a pane which contains a list
with several columns and some rows. Each row represents a GoCB description with all GoCB
attributes which are of interest.
When already IEDs are linked to that GoCB this is visible by the icon element to expand the
GoCB for next level rows. Each next level row contains the identification of a linked IED.
GOOSE messages are not handled by the server. They are directly send by the communication
handler as Unicast messages. The access to the Ethernet may need additional address information and timing parameters to monitor the correct sending. These parameters can/must be set per
GoCB in an additional address definition row.
113
GoCB engineering
Chapter 8
Signal engineering with CCT
The main steps to generate a GoCB are:
•
•
•
•
•
•
•
•
add a new GoCB row to the list by clicking Add ... GSE Control in the bottom
area of the pane
give the GoCB a unique name according to the rules described in IEC 61850–7–2
clause 15.2.1.1 and the rules defined in the project
select the DataSet out of the list of available DataSets for this GoCB. Always
only one DataSet per GoCB. See the example in the figure above
link the GoCB to the IEDs which should receive these GOOSE message. This is
done by selecting the icon of the bay IED and link it to the name field of the corresponding GoCB by using the drag-and-drop method. Repeat this for all bay
IEDs which should receive the information. See the arrow in the figure above.
configure the GoCB attributes to the standards defined in the project.
configure the address parameters to the standards defined in the project
do Update DataFlow by selecting this task via the menubar Tools > IEC 61850
Data Flow Engineering. CCT will now add the needed information in the SCL
file in:
- the IED section for the 'GoCB' and for the 'Input' structure elements in the
LLN0
- the communication section for the GSE structure
precondition to do the update dataflow is a correct and complete communication
section including all IEDs with their subnetwork and access point identification
en06000036.vsd
Figure 73:
CCT: Update Dataflow
Each IED which is selected to receive the GOOSE message will get the description of an 'Input'
structure in its SCL IED section in the LLN0 of the LD. It is then the task of IED engineering to
route the input signals of a GOOSE message to the application which deals with the information.
See the brief description in chapter 2, section 3.4 "Signal engineering".
114
GoCB engineering
Chapter 8
Signal engineering with CCT
en06000092.vsd
Figure 74:
CCT: Project Navigator with selected Input of a GOOSE message
Configuration of the GoCB attributes
The possible attributes which are needed to describe the operation etc. of a GoCB are included in
•
•
•
•
•
IEC 61850–6 clause 9.3.10 and listed in table 22 for the additions in the IED section
IEC 61850–6 clause 9.3.13 and table 30 for the designation of the input block in
the receiver IED
IEC 61850 clause 9.4.4 and listed in table 34 for the additions in the communication section
IEC 61850–7–2 clause 15.2 and table 28
the attributes used by the CCT to get the description from the user are all listed
in the CVC selection box for the GoCB.
For the identification of a column the same text is used in the GoCB list and in the CVC. To see
them in the CVC completley you have to select an element. The complete description will pop
up, when there is more text then in the visible part. The sorting order for the column may be
changed to your demands. So the only element to make the link to CVC is the identification text
of the column. How to operate the CVC see chapter 4, section 6.3 "CCT Column visibility control".
115
GoCB engineering
Chapter 8
Signal engineering with CCT
GoCB attributes
1
GoCB address parameter
1
GoCB receiver IEDs
1
en06000206.vsd
Figure 75:
Table 3:
116
CCT: CVC for GoCB
GoCB attributes, address parameters and receiver IEDs
No. Title
IEC 61850–
Description (taken from the standard)
1
Name
6, clause 9.3.10, table
26,1
The name identifying this GOOSE control block.
2
Descr.
6, clause 9.3.10, table
26,2
A description text.
3
DataSet
6, clause 9.3.10, table
26,3
The name of the data set to be sent by the GSE control block.
For type=GSSE, the FCDA definitions in this data set shall be
interpreted as DataLabels according to IEC 61850-7-2. The
attribute datSet can only be empty within an ICD-File.
4
Type
6, clause 9.3.10, table
26,5
If the type is GSSE, then only single indication and double indication data types are allowed for the data items referenced in
the data set, otherwise all data types are allowed. Note that on
stack level, each type might be mapped differently to message
formats. The default type value is GOOSE
5
Identifier.
6, clause 9.3.10, table
26,6
A system wide unique identification of the application to which
the GOOSE message belongs.
GoCB engineering
Chapter 8
Signal engineering with CCT
No. Title
IEC 61850–
Description (taken from the standard)
6
Config.
Ref.
6, clause 9.3.10, table
26,4
The configuration revision number of this control block.
1
Descr.
6, clause 9.4.4, table
34,1
Textual description
2
MinTime 6, clause 9.4.4
The Mintime and Maxtime elements specify the following times:
Mintime: the maximal allowed sending delay on a data change
in ms.
Maxtime: the source supervision time in ms (supervision heartbeat cycle time). Within this time, a failure of the source shall
be detected by the client.
Mintime and Maxtime may influence SCSM parameters. Which
parameters and how they are influenced is defined in the
appropriate SCSM
3
MaxTime
6, clause 9.4.4
The Mintime and Maxtime elements specify the following times:
Mintime: the maximal allowed sending delay on a data change
in ms.
Maxtime: the source supervision time in ms (supervision heartbeat cycle time). Within this time, a failure of the source shall
be detected by the client.
Mintime and Maxtime may influence SCSM parameters. Which
parameters and how they are influenced is defined in the
appropriate SCSM
4
MAC
Address
6, clause 9.4.3
see the standard
5
ApplicationId
same as: 6, clause
9.3.10, table 26,6, see
also clause 9.4.4, table
34,2
The instance identification of the LD within this IED, on which
the control block is located. An LN is not necessary, as these
control blocks are only in LLN0.
6
VLAN ID
7
VLAN
Prio
1
Client
IED
6, clause 9.3.13, table
30,1
The name of the IED from where the input comes
2
Order
Sequence order of all IEDs linked to the GOOSE message
117
GoCB engineering
118
Chapter 8
Signal engineering with CCT
/
&
6
,
3
.
"##1PXFS5FDIOPMPHJFT"#
4VCTUBUJPO"VUPNBUJPO1SPEVDUT
4&7ÊTUFSÌT
4XFEFO
5FMFQIPOF
'BDTJNJMF
*OUFSOFUXXXBCCDPNTVCTUBUJPOBVUPNBUJPO
1SJOUFEPOSFDZDMFEBOEFDPMBCFMMFEQBQFSBU&MBOEFST/PWVN