LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
SECTION 283123
FIRE ALARM AND DETECTION SYSTEM
PART 1 - GENERAL
1.01
SUMMARY
A. Section Includes: Furnish and install automatic and manual fire alarm and smoke detection
system as shown on Drawings and as specified.
1.02
SUBMITTALS
A. Shop Drawings: Submit drawings showing layout, dimensions and wiring diagram.
B. Product Data: Submit clear description and complete data for each device being furnished.
C. Certification: Submit UL Field Certification after final Checkout of system.
D. Project Record Drawings: Accurately record actual location of end-of-line devices. Submit
Record Drawings.
1.03
QUALITY ASSURANCE
A. Codes and Standards (refer to Section 260140.51):
1.
NFPA (National Fire Protection Association)
a. 70 (NEC)
b. 72A, B, C,
c. 90A
d. 101.
2.
ANSI (American National Standards Institute)
3.
UL (Underwriters Laboratories)
4.
FM (Factory Mutual System)
5.
BOCA (Building Officials and Code Administrators International, Inc.)
6.
ICBO (International Conference of Building Officials)
7.
SBCCI (Southern Building Code Congress International)
1.04
SYSTEM DESCRIPTION
A. Design Requirements: New fire alarm equipment must be compatible with existing fire alarm
system and central fire reporting station. Alarm must transmit to the local Fire Department
station, or other User designated, 24 hour supervisory facility.
B. Performance Requirements:
1.
The system shall meet requirements of the NFPA code and all other applicable codes.
2.
The system consists of a central new fire alarm control panel, power supplies, a conduit
and wiring system, and all auxiliary and accessory devices required to provide a complete
operating system.
3.
Provide a complete non-coded, zoned, electrically supervised fire alarm and detector
system (NFPA 72, Style D, Class A) as shown on the Drawings and as specified.
283123 - 1
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
4.
System Operation:
a. The operation of a station, manual or automatic, shall cause a continuous general alarm
to sound on all devices, cut off stipulated fans and mechanical equipment, until the station
is restored to normal.
b. System shall be supervised and a line fault or shift from main to stand-by power shall
cause a trouble alarm to sound. (Alarm may be silenced by a switch which turns on a
light which remains on until panel is reset to normal.) One ground condition on the
system shall not prevent the alarm from being transmitted.
c. Each zone is represented on the remote annunciators and the control panels by an amber
trouble lamp and a red alarm lamp. The lamps for each circuit shall be identified by the
lettered nameplate showing the zone designation. Circuit trouble or supervisory device
operation shall be indicated by the amber trouble lamp lighting. An alarm signal shall be
indicated by both the amber trouble lamp and the red alarm lamp lighting. Audible trouble
and alarm devices shall function as specified.
d. The system shall operate from a source of 120 VAC and shall rectify this to 24 VDC for
system operating power.
e An automatic charger shall be provided to completely restore run down batteries within 48
hours
f. A standby battery and automatic transfer device shall provide emergency power.
PART 2 PRODUCTS
2.01
ACCEPTABLE MANUFACTURERS
A. Simplex Time Recorder Co.
B. Pyrotronics.
C. Edwards.
D. Kidde.
E. Firelite.
2.02
COMPONENTS
A. The fire alarm control panel shall be solid state plug-in module type composed of solid-state plugin modules factory interconnected to meet the specific installation requirements.
B. An alarm control module shall be provided which allows alarm from other zone to be silenced, but
allows subsequent alarms from other zones to resound the alarm. The module shall provide a
Step 1 system reset, a LED lamp test feature, a system LED flasher, a waterflow signal output, a
signal silenced LED and alarm lock-up feature.
C. A trouble control module shall be furnished which provides trouble resound, a remote trouble
signal connection, a system trouble LED, annunciator troubled LED, an earth fault LED for both a
positive and negative fault, an acknowledge switch for alarm and trouble, a printer output
connection for system trouble and acknowledge conditions, a Step 2 system reset switch, a
supervised annunciator trouble output, a loop monitor circuit and a trouble signal lock-in which
shall allow a trouble signal to be temporarily suspended during the sounding of an alarm
283123 - 2
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
D. An automatic dual-rate battery charger module shall be charging a gel cell battery. A constant
trickle charge shall continuously be applied to the battery in order to maintain it at a full charge
state. A method of adjusting the trickle charge rate shall also be provided in order to supply the
selected battery with the exact charge rate it requires. A meter shall be included which shall be
capable of monitoring batter voltage or trickle current. In the event of a failure of the charger, the
charger failure LED shall illuminate. Should the battery capacity drop below specified limits, the
charger shall automatically change to high rate condition and a LED shall illuminate.
E. A monitor module is to be provided which shall monitor the charger and either the remote battery
or the battery mounted within the control panel. Should the battery voltage become excessively
low, excessively high or not be connected at all, the system trouble module shall be activated and
the battery trouble LED shall flash. The module shall also have provisions for printer connection
and a supervised annunciator output. In the event of a charger failure, the system trouble module
shall be activated and the charger trouble LED shall flash.
F. The alarm initiating circuit modules shall provide 4-wire Class A circuitry monitoring for alarm
trouble and ground faults. The module shall provide alarm and trouble LED's, LED lamp test
feature, supervised alarm and trouble annunciator outputs, supervised alarm and trouble relays,
alarm and trouble printer outputs, alarm and trouble auxiliary contacts (N/O; 2.0 A Resistive),
alarm and trouble resound with flasher acknowledge and a three-position disconnect/test switch.
The module shall be completely pluggable and inherently power limited (limited energy) with a
1,000 ohm maximum line resistance.
G. A remote station module shall be provided which transmits alarm and trouble conditions to a
compatible reverse polarity receiving unit. The module shall provide drill and disconnect switches,
a city base disconnect LED, a remote line trouble LED, trouble resound capability, supervised
annunciator and printer output connections. Remote Annuciators shall accurately describe the
location within the building. Marking of "Zone 1", "Zone 2", etc is not acceptable.
H. A power supply module shall be furnished supplying 5 amperes of continuous filtered power, or 8
amperes intermittent of the proper voltage. The power supply shall be capable of furnishing the
system power and power for devices such as smoke detectors, auxiliary relays, door holders, etc.
The Power Supply shall automatically transfer to the secondary (Standby) power supply within 30
seconds. The secondary power supply shall be capable of operating the fire alarm system on a
non-alarm mode for 24 hours and then, at the end of 24 hours to operate all alarm notification
appliances for five minutes. The Power Supply shall contain a normal power LED, battery trouble
LED and power supply trouble LED, all viewable on front of enclosure. Capability of connecting a
voltage regulator shall be included.
I.
A voltage regulator module shall be furnished capable of regulating voltage within a +5 percent of
system requirement. It shall be capable of continuous 2 ampere output, it shall include a trouble
LED and circuit breaker mounted on front of enclosure. It shall automatically transfer to standby
power when detecting abnormal conditions.
J.
A "Monaco" narrow-band capability radio transceiver, frequency 138.9250 MHz, shall be provided
for interface with the existing base System. All wiring, interfaces, cables, antennas, and devices
necessary for operation and interfacing shall be provided.
K. A dual rate marche time module shall be furnished which will provide 120 beats/minute for marche
time general alarm. The module shall include a LED which flashes at the selected code rate.
L. Pluggable relays and their bases complete with terminals for contractor wiring shall be furnished
for control of external equipment. Each relay shall be 4 PDT and operate on 24 VDC. Contacts
shall be rated at 1 amp and bifurcated for low current and resistance operation.
283123 - 3
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
M. A separate heavy duty power distribution module shall be furnished as part of the control
whenever the DC input exceeds 15 amps at 24 VDC. The terminals shall be distinctly marked
+ Batt and - Bat. There shall be 2 input and 12 output terminals on each module.
N. Terminal connections and harnesses shall be provided for field connections of remote supervised
annunciators or for the modules' auxiliary contacts. Each connector shall have provision for at
least 16 separate points and shall be fastened securely on the rack end.
O. Manual pull stations shall be semi-flush type and shall be installed where shown on Drawings.
Station shall be the single action type. The station body shall be so constructed that scratches will
not deface the station. Stations shall be keyed compatible with the fire alarm control panel. Pull
lever shall be mounted behind a glass door which must be broken to gain access to the pull lever.
Once pulled, the pull lever shall remain at right angles to lever. Once pulled, the pull lever shall
remain at right angles to the station until reset. Manual fire alarm boxes shall be mounted with the
operable part not less than 3-1/2 feet and not more than 4-1/2 feet from the floor. ADA
requirements: Forward reach = 48 inches, side reach = 54 inches.
P. Automatic heat detectors shall be combination rate of rise and 136 deg. F. fixed temperature, or
200 deg. F. fixed temperature. Detectors shall be white, low profile type.
Q. Alarm Notification Appliances: Audible and visual appliances may be combined into a common
enclosure. One or more audible alarm notification device shall be installed on each floor. The
minimum sound level for an audible device is 15 dBA above the average ambient sound level or 5
dBA above the minimum sound level having a duration of at leads 60 seconds (whichever is
greater), in every occupied space within the building. The evacuation signal shall be a "three
pulse" temporal pattern. The temporal pattern consist of an "on" phase lasting 1/2 second
followed by an "off" phase lasting 1/2 second repeated three times. After three "on" phases there
is a 1-1/2 second "off" phase before the next on phase.
R. Visual Alarm Notification Appliances: The following characteristics are required:
1.
The lamp shall be Xenon strobe type or equivalent.
2.
The color shall be clear or nominal white (i.e., unfiltered white light)
3.
The maximum pulse duration shall be two-tenths of one second (0.2 sec) with a
maximum duty cycle of 40 percent. The pulse duration is defined as the time interval between
initial and final points of 10 percent of maximum signal.
4.
The intensity shall be 75 candela.
5.
The flash rate shall be a minimum of 1 Hz and or maximum of 3 Hz.
6.
The appliance shall be 80 inches (2030 mm) above the highest floor level within the
space or 6 inches (152 mm) below the ceiling, whichever is lower.
7.
No place in any room or space required to have a visible appliance shall be more than 50
feet (15 m) from the appliance (in the horizontal plane).
8.
No place in common corridors or hallways in which visible alarm notification appliances
are required shall be more than 50 feet (15m) from the appliance.
9.
Visual Alarm Appliances shall be provided in restrooms and any other general usage
areas (e.g., meeting rooms), hallways, lobbies, and any other area for common use.
10.
Outside Audible/Visual alarm appliance shall be weatherproof.
S. Smoke detectors shall be photo-electric or ionization type, 24 VDC as indicated on the Drawings.
Detector shall have a continuous visual indication of the condition of the detector and its proximity
to alarm or trouble. A pulsed diode pilot light shall be seen from a distance of 50 to 60 feet and
shall be UL listed, and field adjustable.
283123 - 4
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
T. Duct smoke detectors shall be photo-electric Type 24 VDC to be return duct, side mounted. The
detector shall have a pulsed light-emitting diode, visible through the airtight housing, providing
alarm or trouble indication. Provide remote test panel for each duct detector.
1.
Duct Smoke Detectors shall be mounted by one of the following methods:
a. Rigidly mounted within the duct.
b. Rigidly mounted to the wall of the duct with sensing element protruding into the duct.
c. Mounted outside the duct with rigidly mounted sampling tubes protruding into the duct.
d. Mounted outside the duct with projected light beam through the duct.
2.
Duct Smoke Detectors mounted in or on return air ducts shall be located at least six duct
widths downstream from any duct openings, deflection plates, sharp bends, or branch
connections.
3.
Location of all detectors shall be readily accessible for cleaning, and be permanently and
clearly identified and recorded.
PART 3 EXECUTION
3.01
INSTALLATION
A. Install system in accordance with manufacturer's instructions and NFPA.
B. The entire system shall be installed under the supervision of a factory trained representative.
C. Wiring: Wiring shall be in strict accordance with NFPA 70, 72, 72A and 72C and all applicable
regulations. Minimum of No. 18 AWG wire shall be used and installed in conduit. Wiring shall be
installed in accordance with the manufacturer's wiring diagram and shall test free from grounds,
opens, and shorts.
D. Wiring shall be in conduit and of the same approved type as used for electric light power wiring
and shall meet the requirements of electrical codes. The sizes of the different wires shall be
those specified by the manufacturer. Color shall be those specified by the manufacturer. Color
code shall be used where specified. Wires shall be tagged at junction points and test free of
grounds or crosses between conductors.
E. Wiring, both indicating and initiating circuits, shall be 4 wire Class A. Wiring shall be 105 deg C
power limited rated fire alarm cable and shall be listed and marked "FPL", FPLR", or "FPLP".
F. All Fire Alarm System circuits shall be identified at terminal and junction locations.
3.02
SYSTEM PRECHECK
A. Check the system power supply and verify that the main power supply is clearly marked "Fire
Alarm Circuit Control".
B. Check the secondary power supply by interrupting the main power supply. Verify that a trouble
light is indicated and the system automatically transfers to the secondary source.
C. Verify the power supply has an NEC approved ground connection.
D. Visually check all fuses in the main control panel, in any remote battery cabinets and any circuit
interface panels to confirm that they are correctly sized. Observe the ampacity value marked on
every fuse and compare that value with the value marked on the fuse holder in the panel or on the
wiring diagram.
283123 - 5
LUKE AIR FORCE BASE – MACC TASK ORDER NO. 1, BUILDING 976
F-35 FOREIGN MILITARY SALES TRAINING FACILITIES
14708 W SUPER SABRE
LUKE AIR FORCE BASE, ARIZONA 85309
E. Verify that the fire alarm system junction boxes and terminal boxes are clearly identified.
F. Inspect all lights, sounders and switches on the panels. Lights on all remote annunciators and
circuit interface panels should be checked. Sounders on the main control and on any remote
annunciators and circuit interface panels should be checked. Check all silencing switches, reset
switches and monitor disconnect switches on the control panel and all remote annunciator panels.
3.03
ACCEPTANCE TESTING
A. If the building is occupied, notify the occupants that the system is being tested.
B. Testing shall be done in the presence of a manufacturer's representative and shall be inspected
and certified in good working order by the representative, in writing, submitted to the Contracting
Officer.
C. Every sprinkler flow switch must be tested.
D. Every initiating device circuit and every alarm notification appliance circuit shall be checked during
the acceptance test. In accordance with NFPA 72, one connection shall be opened at 10% of all
devices and appliances on each circuit to ensure that they have been properly connected. The
integrity of the installation conductors shall be tested while the initiating devices are being tested.
E. While the initiating devices are being actuated confirm that the magnets holding smoke doors
release and that the smoke doors close tightly.
F. Upon completion of testing a "Certificate of Completion" shall be issued in accordance with
NFPA 72.
END OF SECTION
283123 - 6