Download Data Bulletin Shedding Non-Priority Loads with

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power factor wikipedia , lookup

Electronic engineering wikipedia , lookup

Power over Ethernet wikipedia , lookup

Wireless power transfer wikipedia , lookup

Electric machine wikipedia , lookup

Ground (electricity) wikipedia , lookup

Switched-mode power supply wikipedia , lookup

General Electric wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Induction motor wikipedia , lookup

Utility frequency wikipedia , lookup

Mains electricity wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Electric power system wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Regenerative circuit wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Islanding wikipedia , lookup

Two-port network wikipedia , lookup

Electrical substation wikipedia , lookup

Variable-frequency drive wikipedia , lookup

History of electric power transmission wikipedia , lookup

Fault tolerance wikipedia , lookup

Electrification wikipedia , lookup

Alternating current wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power engineering wikipedia , lookup

Earthing system wikipedia , lookup

Residual-current device wikipedia , lookup

Circuit breaker wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Transcript
0611DB1107
03/2012
Data Bulletin
Replaces 0611DB1107 12/2011
Shedding Non-Priority Loads with PowerPact™ H-, J-, and
L-Frame Circuit Breakers with Micrologic™ Trip Units
Introduction
Load-shedding is one of the active energy efficiency features of the
PowerPact™ H-, J-, and L-frame circuit breakers with Micrologic™
electronic trip units.
Load-shedding (preventing some non-priority loads from being supplied
during a certain period of time) can be used to limit power to an entire
electrical installation.
The advantages are:
•
•
•
lower energy consumption
cost optimization
improved system availability
Load-shedding is used to:
•
prevent overload tripping: if the load approaches the maximum load
threshold, a load-shedding order on previously selected loads can help
prevent a general power failure throughout the installation (improved
availability)
•
allow a lower level power contract, while allowing all the devices to
operate correctly
•
carry the consumption forward to an off-peak tariff period (cost
optimization.
Two load-shedding solutions are provided:
•
•
Figure 1:
“reflex” load-shedding using a local order
“centralized” load-shedding using a remote order
Load Shedding
Centralized Load Shedding
06114925
06114924
Reflex Load Shedding
PC or PLC
controller
Ethernet
EGX100
PowerPact
Circuit Breaker
Modbus
SDx
IFM
FDM121
Micrologic 5.3 E
PowerPact
Circuit
Breaker
Micrologic 5.3E
Trip Unit
BSCM
Circuit
Breaker
Boiler
Priority Loads
Non-Priority Load
© 2011–2012 Schneider Electric All Rights Reserved
™
Shedding Non-Priority Loads
Data Bulletin
0611DB1107
03/2012
Reflex Load-Shedding
Description
The reflex load-shedding order is generated locally by the PowerPact H-, J-,
or L-frame circuit breaker itself using the Micrologic electronic trip unit. The
Micrologic E electronic trip unit (energy measurement) is used to manage
alarms based on the monitoring of electrical variables such as the
instantaneous current, the demand power (Pdmd) or even the frequency.
An activation (pick-up) threshold (SA) with its time delay (TA) and a
deactivation (drop-out) threshold (SD) with its time delay (TD) are
associated with each alarm. The time delays are independent and can be
set from 1 s to 3000 s.
The following figure illustrates the high alarm activation condition:
High Alarm Activation Condition
06114926
Figure 2:
SA
SA
TA
SD
TD
1
TA
Activation threshold
Activation time delay
Deactivation threshold
Deactivation time delay
Alarm: activation zone (green)
SD
TD
(t)
1
06114030
SDx Module
The detection of a threshold triggers load shedding of the load connected to
the threshold. Shedding the load connected to threshold prevents the circuit
breaker from tripping and therefore improves availability.
The reflex load-shedding order is sent to the load-shedding contactor
through the SDx module installed in the PowerPact H-, J-, or L-frame circuit
breaker. After configuring the thresholds, all that is required is to assign the
alarm to output 2 on the SDx module (as output 1 is already assigned to the
SDT long delay tripping notification).
This load-shedding contactor (2-pole NC) cuts off the non-priority feeders.
Products used
Products needed to set up load shedding are shown below. For catalog
numbers, see the PowerPact H-, J-, and L-Frame catalog, 0611CT1001.
Table 1:
Products Required for Ethernet Connection
Product
2
Description
Circuit Breaker
PowerPact™ H-, J-, or L-Frame Circuit Breaker
Micrologic Trip Unit
Electronic trip unit with energy measurement: Micrologic E
SDx
Indication relay module
Cx
Two-pole contactor (2-pole NC) 20 A
© 2011–2012 Schneider Electric All Rights Reserved
0611DB1107
03/2012
Shedding Non-Priority Loads
Data Bulletin
Configuration
The alarms are configured using the RSU software (downloadable from
schneider-electric.com)
Example 1
Load-shedding based on the instantaneous current threshold of the
phase (I1).
The detection of an instantaneous current high threshold overrun on a
phase indicates an overload on that phase. Shedding a single-phase load
connected to the phase prevents the circuit breaker from tripping on
overload (long time delay) and therefore improves availability.
Example 1 Alarms Setup
06114927
Figure 3:
The load-shedding order is given as soon as the phase 1 current exceeds
80 A for more than 20 s.
This order will be maintained as long as the phase 1 current does not fall
below 30 A for more than 10 s.
NOTE: To avoid beat phenomena, it is recommended that the difference
between the high threshold (80 A) and the low threshold (30 A) should be
greater than the current consumed by the shed load.
Example 2
Load-shedding based on a total demand power threshold (Pdmd).
The detection of a demand total power high threshold overrun indicates an
overload on this installation. Load shedding prevents the subscribed power
from being exceeded and therefore optimizes costs.
Example 2 Alarms Setup
06114928
Figure 4:
© 2011–2012 Schneider Electric All Rights Reserved
3
Shedding Non-Priority Loads
Data Bulletin
0611DB1107
03/2012
The load-shedding order is given as soon as the total demand power
exceeds 53 kW for more than 70 s. This order will be maintained as long as
the total demand power does not fall below 20 kW for more than 15 s.
Example 3
Load-shedding based on frequency threshold (f).
The detection of a network frequency low threshold overrun in the event of
the installation being operated by a diesel generator indicates an imbalance
between the demand and the capacity of the generator. Load shedding
makes it possible to redress the balance and therefore to improve
availability.
Example 3 Alarms Setup
06114929
Figure 5:
The load-shedding order is given as soon as the frequency falls below
48 Hz for more than 2 s. This order will be maintained as long as the
frequency does not rise above 49.5 Hz for more than 5 s.
06114930
Wiring Diagram
a 230 V
SDT
output 1
SD3
Cx
output 2
SD2
A1
A2
SD4
SDx
Q
SD1
a
4
© 2011–2012 Schneider Electric All Rights Reserved
0611DB1107
03/2012
Shedding Non-Priority Loads
Data Bulletin
Test
Test whether the reflex load-shedding solution has been implemented by
using the LSU (Local Simulation Utility) software. This software, which is
available from www.schneider-electric.com, can be used to simulate the
electrical variables (I, V, f, THD, phase shift angle phi). The USB port is
connected using the maintenance module.
Connection Using the USB Port
06114931
Figure 6:
1. Standard USB cable connecting the maintenance module to the PC
2. Maintenance module power supply unit
3. Micrologic cable connecting the maintenance module to the trip unit test socket
From the LSU software, a current is simulated on phase 1 (I1=83 A for
example) and at the end of the activation time delay (20 s), it is noted that
output 2 on the SDx module changes to 1 and therefore supplies the coil of
the load shedding contactor (Cx) that will cut off the non-priority feeders. To
change the SDx module output back to 0, a current of less than 30 A must
be simulated on phase 1 for at least 10 s.
The same procedure can be followed for load-shedding solutions based on
the power or frequency threshold.
Centralized Load Shedding
Description
The centralized load-shedding order is generated remotely by the controller
(PC or PLC).
06114932
The controller is used to generate load-shedding orders based on
monitoring the electrical variables of the entire electrical installation, taking
the time bands, operating constraints or even process-related information
into consideration.
BSCM
The centralized load-shedding order is sent to the BSCM installed in the
PowerPact H-, J-, or L-frame circuit breaker through the Modbus™
communication network. The BSCM is connected to the communicating
motor operator. The communicating motor operator is the actuator that
opens or closes the circuit breaker.
06114933
The FDM121 front display module can be added as an optional extra. In
addition to displaying measurements, alarms and operating information, the
FDM121 can be used to give a local order to open/close the PowerPact H-,
J-, or L-frame circuit breaker.
FDM121
In remote mode, only orders from the controller are taken into account. In
local mode, only orders from the display unit are taken into account.
This ensures, for example, that no unwanted circuit breaker opening orders
are received and that the closed position is maintained during a critical
operation (backup, transfer of sensitive data, etc.).
© 2011–2012 Schneider Electric All Rights Reserved
5
Shedding Non-Priority Loads
Data Bulletin
0611DB1107
03/2012
Products used
Products needed are shown below. For catalog numbers, see the
PowerPact H-, J-, and L-Frame catalog, 0611CT1001.
Table 2:
Configuration
Figure 7:
Products Required for Ethernet Connection
Product
Description
Circuit Breaker
PowerPact™ H-, J-, or L-Frame Circuit Breaker with Micrologic
Electronic trip unit
MTc
Communicating motor operator
BSCM
Breaker Status Control Module
NSX Cord
Wire length L= 1.3 m
IFM
Modbus interface module
FDM121
Front display module
EGX100
Modbus/Ethernet communication gateway
No special configuration is required for the Micrologic trip unit. The loadshedding order (circuit breaker opening/closing) is sent by the controller to
the BSCM module through the Modbus network. The configuration of the
BSCM module Modbus circuit breaker opening/closing orders is specified in
the Modbus Communication—User Guide (48940-328-01).
Ethernet Connection
Ethernet
white
D1 D0
RS485
TX
RX
white
e
06114934
blue
LX
TX
RX
100
blue
24 V
24 V
Rx- Rx+ Tx- Tx+
Modbus
Switches
0V 24V
2 wire
UP/ON DOWN/OFF
FDM121
NSX cord
B4
HL
+ -
a (220/240 V)
BSCM
MTc
Q
0
I
A1
auto
manu
a
6
© 2011–2012 Schneider Electric All Rights Reserved
0611DB1107
03/2012
Shedding Non-Priority Loads
Data Bulletin
Test
Test whether the centralized load-shedding solution has been implemented
by using the RCU (Remote Control Utility) software. This software, which is
available from schneider-electric.com, can be used to open/close the
PowerPact H-, J-, or L-frame circuit breaker using the communicating motor
operator. Connection to the PC Ethernet port is through the
Modbus/Ethernet EGX communication gateway.
In the main set-up menu, go to the User profile submenu and choose
“control”. The control tab is now available and can be used to check that the
communicating motor operator is operating correctly over the Modbus
network.
User Profile Submenu
06114935
Figure 8:
Conclusion
The reflex load-shedding solution using a local order with PowerPact H-, J-,
or L-frame breaker provides:
•
a reduction in capital expenditure, as its purchase price is lower than
that of a traditional solution: the cost of a PowerPact H-, J-, or L-frame
circuit breaker with a Micrologic E trip unit (energy measurement) + SDx
module is similar to the cost of a PowerPact H-, J-, or L-frame circuit
breaker without the measurement function + Power Meter + I/O + CT.
The difference is the cost of installing/wiring/testing the CTs, which is
included in the PowerPact H-, J-, or L-frame circuit breaker.
•
a reduction in operational expenditure, due to optimized energy costs
and to the improved availability provided by the load-shedding function.
NOTE: As standards, specifications and designs change from time to time,
please ask for confirmation of the information given in this publication.
© 2011–2012 Schneider Electric All Rights Reserved
7
Shedding Non-Priority Loads
Data Bulletin
Schneider Electric USA, Inc.
3700 Sixth St. SW
Cedar Rapids, IA 52404 USA
1-888-778-2733
www.schneider-electric.us
8
0611DB1107
03/2012
Electrical equipment should be installed, operated, serviced, and maintained only by
qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
Square D™ and Schneider Electric™ are trademarks or registered trademarks of
Schneider Electric. Other trademarks used herein are the property of their respective
owners.
© 2011–2012 Schneider Electric All Rights Reserved