Low-Impedance Busbar Differential Protection Modeling and Simulation Using ATP/EMTP Alfredo Pianeta Escudero, Kleber Melo e Silva, Felipe Vigolvino Lopes Department of Electrical Engineering (ENE) University of Brası́lia, Brazil [email protected], {klebermelo, felipevlopes}@unb.br Abstract—This paper describes the modeling of a numerical low-impedance busbar protection scheme by using the MODELS language available in the software ATP. The instantaneous valuesbased differential protection algorithm was implemented, taking into account external fault detection and zone selection logics. The relay model also includes the data acquisition systems and signal conditioning modules. The well known tripping logics 1-out-of-1 and 2-out-of-2 were used, which has been widely implemented in numerical relays commercially available. Aiming to validate the relay model, simulations of both internal and external faults on a 230 kV substation with double busbar single breaker arrangement were carried out using the ATP. The obtained results reveal this type of modeling is useful for studies regarding busbar differential protection schemes, as long as it provides a closed loop simulation, allowing the evaluation of the relay algorithm during power system operational conditions not readily available in actual records. Index Terms—Busbar protection, CT saturation, differential protection, ATP, MODELS language. I. I NTRODUCTION Busbars play an major role in the power system operation, as it is the point of connection of several power apparatus such as lines and transformers. Among faults in electric systems, those in busbars are cause of great concern for utilities, as they typically lead to widespread blackouts [1], [2]. Therefore, studies regarding busbar protection functions by using simulation platforms have aroused the interest of utilities, as it allows the analysis of system operational conditions not readily available in actual records. In the open literature, the Electromagnetic Transients Programs (EMTP) have been shown to be a proper alternative for modeling and simulating protective relays [3], [4], since they use more thorough models of the system components and provide suitable environments to link user-defined numeric relay models. Most of the researches are focused on transmission lines protection modeling [5]-[8]. Besides, it was also reported the use of EMTP to model the percentage differential protection of power transformers and the high-impedance differential protection of busbars [9], [10]. However, lowimpedance differential busbar protection has not been reported yet. Therefore, this work aims to model a phase segregated This work was supported by the Brazilian National Research Council (CAPES). low-impedance instantaneous values-based busbar differential protection using the MODELS language of the Alternative Transients Program (ATP). In the proposed model, the data acquisition system, signal conditioning module, external fault detection logic and zone selection function were implemented [11], [12]. In order to distinguish internal from external faults, the well known tripping logics 1-out-of-1 and 2-out-of-2 were taken into account, which have been widely implemented in commercially available busbar differential protection relays [13]. Several fault scenarios were simulated in ATP, including adverse ones, such as cases of external faults with severe current transformer (CT) saturation, as well as external-to-internal evolving faults. The obtained results validate the implemented relay model and illustrate how it is useful for protection relays tests. II. F UNDAMENTALS OF B USBAR D IFFERENTIAL P ROTECTION Numerical low-impedance busbar differential relays are based on the Kirchhoff’s current law. Basically, these relays compare the operating current iop with the restraining current ires , in order to distinguish between internal and external fault to the protection zone [13]. Fig. 1 shows an example of the differential busbar protection (ANSI 87B) connection in a simplified busbar arrangement, where the protection zone is defined by the location and polarities of the CTs. In this paper, instantaneous current values are used, providing very short tripping time (fast operation) of the busbar Transformer 1 Transformer 2 CT4 CT5 Busbar Protection Zone 87 CT1 Line 1 CT2 Line 2 CT3 Line 3 Figure 1. Differential protection zone of a simple busbar configuration. k=1 where n is the number of network elements connected to the busbar and ik represents the instantaneous current of the k-th element. Ideally, the relay must operate whenever iop exceeds a minimum threshold current imin and a percentage K of ires : iop > imin AND iop > K · ires (3) The threshold imin aims to prevent false trip for load current, CT measurement errors, switching transients and leakage currents provided by equipments such as surge arresters, auxiliary power transformers and voltage transformers. Although these equipments are inside the busbar protection zone, the currents flowing through them are not taken into account to calculate iop and ires [11]. The percentage K, in turn, is related to the relay sensitivity, so that the smaller the value of K, the greater the relay sensitivity. Also, analyzing (2), one can note that ires consists of a positive signal, but that may be zero at some instants, since the monitored currents are sinusoids, what can lead the relay to misoperate. In order to overcome this drawback, instead of ires , its smoothed version i∗res is traditionally used in (3), which is computed as shown in the Appendix. Aiming to improve the protection scheme reliability, the trip command is issued only if the operating condition (3) is fulfilled during a certain period of time, typically chosen as 3 or 4 ms, regarding the CT time to saturate [13]. In this paper, the two well known tripping logics are taken into consideration: 1-out-of-1 and 2-out-of-2. Basically, (3) is monitored in real time and a counter counts how many times such condition is fulfilled during consecutive 4 ms along the evaluated signals. Thus, if there is one count soon after the fault inception, a trip signal is generated. This type of operation is named 1-out-of-1 tripping logic (fast operation mode). Also, if two counts are verified during a period smaller than 8 ms at any period of the evaluated signals, the trip command is also generated. This type of operation is named 2-out-of-2 tripping logic. Fig. 2(a) illustrates the behavior of iop , i∗res and the trip commands generated by the 1-out-of-1 and 2-out-of-2 logics for an internal fault. In case of an external fault, i∗res quickly increases, whereas iop remain unchanged with the value almost equal to zero. If this condition is verified during a specific period of time (e.g., 4 ms) lesser than the CT time to saturate, an external fault is detected, toggling the state of an external fault flag EF . Once EF is set to 1 (one), the 1-out-of-1 logic is inhibited for a period of time (secure operation mode), typically set to 150 1-out-of-1 2-out-of-2 operation operation 25 Current (pu) 4 ms 20 iop 4 ms * K.ires t≤8 ms 15 10 5 Internal Fault Inception 0 1-1 2-2 70 80 90 100 110 Time (ms) 120 130 140 (a) 4 ms 10 5 4 ms 4 ms 15 Current (pu) differential protection scheme. Traditionally, for busbars with more than two network elements, numerical percentage differential relays compute the instantaneous values of iop and ires as follows [13]: n X (1) iop = ik , k=1 n X ires = |ik | , (2) t>8 ms No 2-out-of-2 operation iop * K.ires External Fault Inception 0 1-1 2-2 EF 70 80 90 100 110 Time (ms) 120 130 140 (b) Figure 2. Tripping logics evaluation for: (a) an internal fault; (b) an external fault with CT saturation. ms, in such a way that the trip command can only be issued by the 2-out-of-2 logic during this time [13]. An external fault with CT saturation is shown in Fig 2(b). Even with the increase of iop due to the CT saturation, no false trip signal is issued. In fact, being EF set to 1 (one), the fast mode operation is inhibited and, since there are no double counts along the signals, the 2-out-of-2 logic is not fulfilled. III. A NALYZED P OWER S YSTEM D ESCRIPTION Fig. 3 shows the 230 kV test power system evaluated in this paper. The system consists of a double-bus arrangement with single breaker and five switches in each branch, among which one is a bypass switch used during circuit breaker maintenances. Four perfectly transposed transmission lines 180 km long and two power transformers are connected to the busbars, which are in turn connected by a bus coupler circuit breaker that remains closed during the normal power system steady-state regime. The ATPDraw interface was used to model and simulate the test power system, whose parameters are presented in Tables I and II. Power systems around the busbar arrangement were represented by Thevenin equivalent circuits connected to the remote terminals of each branch, whose parameters are shown in Table III. Current signals at each branch were taken from the CT model C800 1200-5 [15], taking into account the saturation characteristic. The secondary currents in each branch were used as inputs of the differential protection functions implemented using the MODELS language. A time-step of 1µs was used and a sampling frequency fs equal to 1920 Hz was simulated, i.e. 32 samples/cycle for 60 Hz systems. BUS 1 D1CB (NC) CVTB1 D1TL2 (NO) D1TF1 (NC) D2TL1 (NO) D2TL2 (NC) D2TF1 (NO) CTCB1 D1TF2 (NO) D1TL3 (NC) D1TL4 (NO) D2TF2 (NC) D2TL3 (NO) D2TL4 (NC) CCB D1TL1 (NC) CTCB2 D2CB (NC) BUS 2 CVTB2 D4TL1 D4TL2 D4TF1 D5TL3 D4TF2 D3TL4 CBTL4 D5TF2 D3TL3 CBTL3 D5TF1 D3TF2 CBTF2 D5TL2 CBTF1 D5TL1 FAULT D3TF1 CBTL2 D3TL2 CBTL1 D3TL1 D5TL4 D4TL3 D4TL4 CTTLP CTTLP CTTFP CTTFP CTTLP CTTLP CTBP CTBP CTBP CTBP CTBP CTBP FAULT CVTTL TL2 CVTTL TF1 CTTFP CTTLP CVTTL TL2RCB I TL1RCB Transmission Line 2 EQ Transmission Line 1 EQ CTTFP TF1RCB Transformer 1 EQ TL3 TF2 I CTTLP CVTTL CVTTL CVTTL TL1 CTTLP CVTTL TF2RCB TL4 CTTLP CVTTL TL3RCB Transformer 2 EQ Transmission Line 3 EQ TL4RCB Transmission Line 4 EQ Figure 3. Single-line diagram of the evaluated double busbar single breaker arrangement. TABLE I. Z0 (Ω/km) T RANSMISSION LINES PARAMETERS Z1 (Ω/km) 0.532 + j1.541 B0 (µS/km) 0.098 + j0.510 TABLE II. 2.293 B1 (µS/km) 3.252 P OWER TRANSFORMER PARAMETERS Transformer S (MVA) Primary (kV) Secondary (kV) TF1 TF2 450 150 500 (Y) 230 (Y) 230 (Y) 69 (∆) Among the five disconnecting switches (DS) used in each branch, besides the bypass switch, two DSs are used as busbar selector switches and the two others, which operate normally close (NC), which are used to isolate the circuit breaker during its maintenance. This type of busbar arrangement provides great operational flexibility and security, allowing the circuit breaker maintenance without interrupting the energy supply. However, as a consequence, the protection logic becomes more complex, since the busbar can assume different configurations. Therefore, the protection zones should be self-adapted in accordance with the busbar configuration. Under normal operating conditions, to distribute the load uniformly throughout the busbar, some network elements are connected to the bus 1 and other ones to the bus 2. For example, consider the test power system shown in Fig. 3. One can see that the transmission line 1, transformer 1 and transmission line 3 are connected to the bus 1. Such a connection is done through the selector switches D1TL1, D1TF1 and D1TL3, respectively, which operate normally closed (NC). Thus, the protection zone Z1 encompasses line 1, transformer 1 and line 3, unless the selector switches D1TL1, D1TF1 and D1TL3 open and D2TL1, D2TF1 and D2TL3 close, which in turn operate normally open (NO). By doing so, these equipments are included in the protection zone Z2 . The same analysis suits for the network elements connected to the bus 2, which TABLE III. S OURCE E QUIVALENTS Source Voltage (pu) Z0 (Ω) Z1 (Ω) Line1 Line2 TF1 TF2 Line3 Line4 1.006 0◦ 1.006 − 5◦ 1.006 − 5◦ 1.006 0◦ 16.07 + j25.04 18.41 + j28.69 28.07 + j43.74 5.52 + j8.61 18.42 + j28.69 16.07 + j25.04 12.05 + j18.78 13.39 + j20.89 18.71 + j29.16 4.02 + j6.26 13.39 + j20.87 12.05 + j18.78 1.006 − 10◦ 1.006 4◦ normally belong to the protection zone Z2 , but can be included in the protection zone Z1 by operating properly the respective selector switches. Usually, each network element is connected to only one bus, thereby the protection zones Z1 and Z2 are well-defined. Also, a check-zone zone Z12 is typically used. It includes all the elements connected to the busbar and supervises the operation of both protection zones Z1 and Z2 , in such a way that the Z1 and Z2 trip commands are issued to the associated circuit breakers only if the check-zone also detects an internal fault. Otherwise, if Z12 inhibits the operation of zones Z1 and Z2 . In this paper, in order to implement the adaptive zone selection, it was considered that each zone has a flag associated with each CT, indicating whether the measured current should be considered to compute the operation and restraint currents: n X ZF Z F iop = fk · i k , (4) k=1 F iZ res = n X , fkZ · iF k (5) k=1 where n is the total number of network elements connected to ZF F the busbar; iZ op and ires are operating and restraint currents of the Zone Z and phase F , respectively; iF k is the instantaneous current value of the k-th zone Z and phase F and fkZ is the zone selection flag. TABLE IV. A SSIGNMENT OF LOGIC STATES OF FLAGS Branch fk1 fk2 fk12 TL1 ((D1TL1) AND (CBTL1 OR D5TL1)) OR ((PB) AND (CBTL1 OR D5TL1)) ((D2TL1) AND (CBTL1 OR D5TL1)) OR ((PB) AND (CBTL1 OR D5TL1)) (CBTL1) OR (D5TL1 AND CCB) TL2 ((D1TL2) AND (CBTL2 OR D5TL2)) OR ((PB) AND (CBTL2 OR D5TL2)) ((D2TL2) AND (CBTL2 OR D5TL2)) OR ((PB) AND (CBTL2 OR D5TL2)) (CBTL2) OR (D5TL2 AND CCB) TF1 ((D1TF1) AND (CBTF1 OR D5TF1)) OR ((PB) AND (CBTF1 OR D5TF1)) ((D2TF1) AND (CBTF1 OR D5TF1)) OR ((PB) AND (CBTF1 OR D5TF1)) (CBTF1) OR (D5TF1 AND CCB) TF2 ((D1TF2) AND (CBTF2 OR D5TF2)) OR ((PB) AND (CBTF2 OR D5TF2)) ((D2TF2) AND (CBTF2 OR D5TF2)) OR ((PB) AND (CBTF2 OR D5TF2)) (CBTF2) OR (D5TF2 AND CCB) TL3 ((D1TL3) AND (CBTL3 OR D5TL3)) OR ((PB) AND (CBTL3 OR D5TL3)) ((D2TL3) AND (CBTL3 OR D5TL3)) OR ((PB) AND (CBTL3 OR D5TL3)) (CBTL3) OR (D5TL1 AND CCB) TL4 ((D1TL4) AND (CBTL4 OR D5TL4)) OR ((PB) AND (CBTL4 OR D5TL4)) ((D2TL4) AND (CBTL4 OR D5TL4)) OR ((PB) AND (CBTL4 OR D5TL4)) (CBTL4) OR (D5TL1 AND CCB) Coupling Never P B AND CCB P B AND CCB Never Never Never TABLE V. C IRCUIT B REAKER T RIPPING L OGIC TL1 [(Z1 AND D1TL1) OR (Z2 AND D2TL1)]AND Z12 AND CBTL1 TL2 [(Z1 AND D1TL2) OR (Z2 AND D2TL2)]AND Z12 AND CBTL2 TF1 [(Z1 AND D1TF1) OR (Z2 AND D2TF1)]AND Z12 AND CBTF1 TF2 [(Z1 AND D1TF2) OR (Z2 AND D2TF2)]AND Z12 AND CBTF2 TL3 [(Z1 AND D1TL3) OR (Z2 AND D2TL3)]AND Z12 AND CBTL3 TL4 [(Z1 AND D1TL4) OR (Z2 AND D2TL4)]AND Z12 AND CBTL4 MODEL NORM MODEL 87B MODEL Smoothed MODEL Trip GROUP Circuit Breaker MODEL CBStatus MODEL Setflags In Table IV, all the expressions used to assign the logical status of the flag fkZ of each zone are presented. Variables CBTL1, CBTL2, CBTF1, CBTF2, CBTL3, CBTL4 and CCB represent the logical status of the circuit-breakers of lines, transformers and busbar coupling in the test power system. They are set to 1 (one) when the circuit-breaker is closed and set to 0 (zero) when it is open. Therefore, from (5), one can verify that the CT secondary currents are only taken into account for a given protection zone if the element is connected to the correspondent bus. There is another variable named ’Paralleled Buses’ (PB), which is used in the logics shown in Table IV. This variable is set to 1 (one) if both selector DSs of any network element close simultaneously for transfer of the said network element between buses, resulting a current that is not measured by either zone may flow out of one bus into the other. This upsets the current balance in both of the zones and may lead to a false trip of both buses. Aiming to overcome this drawback, whenever PB is set to 1 (one), both zones are expanded to encompass the entire busbar [16], such as the check-zone does. In case of the evaluated system, PB can be set as follows: P B = (D1T L1 AN D D2T L1) OR (D1T L2 AN D D2T L2) OR (D1T F 1 AN D D2T F 1) OR (D1T F 2 AN D D2T F 2) OR (D1T L3 AN D D2T L3) OR (D1T L4 AN D D2T L4). Table V shows the tripping logic of each circuit breaker of the evaluated power system, in which Z1 , Z2 and Z12 represents the trip status of the protection zones. IV. M ODELING OF D IFFERENTIAL BUSBAR PROTECTION USING THE MODELS LANGUAGE Fig. 4 shows the block diagram of the low-impedance busbar differential protection scheme implemented in MODELS [17], whose modules are described next. MODEL DSStatus MODEL DSBP Figure 4. Model Block Diagram in ATPDraw. A. Samples Normalization This module deals with the current signals conditioning, so that it can be divided into the following submodules: • Auxiliary transformers: Receive as input the secondary currents of the CTs. Its main function is to convert and restrict the signals to suitable voltage levels for the A/D converter treatment, that typically is ± 10 V. • Analog Anti-Aliasing Filter: The filter is used to remove the high frequency components to prevent the aliasing effect in the sampling process. Here, it was used a 2nd Butterworth low-pass filter, which was implemented through the resident function LAPLACE. • Sample-and-Holder(S/H): This module samples the simulated current signals with a rate of 32 samples per cycle, i.e. a sampling frequency fs equal to 1920 Hz. Therefore, S/H is implemented in MODELS by setting the command TIMESTEP MIN to 520.833 µs. • A/D Converter: This module emulates the quantization process of the samples in binary words of 16 bits as described in [8]. • TAP: In order to deal with CTs with different current ratios, this module normalizes the current samples to per unit of the primary nominal current of those CT with the highest current ratio [12], [14]. B. CB and DS states This module gets the state of all the CBs and the bus selector DSs of each network element connected to the busbar. C. Set Flags This module defines the flag of the protection zone fkZ , taking into account the tripping logics described in Table IV. D. Relay 87B In this module, the instantaneous normalized current values are received with the associated enabling flags in order to calculate the operating and restraint currents for Z1 , Z2 and Z12 using (4) and (5), respectively. E. Smoothed restraint current Aiming to maintain the restraint current stable and without oscillations, thereby misoperation of the differential protection during external faults with CT saturation is avoided, it was applied the filtering strategy described in [13] and [18], which emulates the behavior of a charging and discharging of a capacitor with a time constant τ of 60 ms, as described in the Appendix. F. Trip Logic This module uses the tripping logics described in [13], such that the logics 1-out-of-1 and 2-out-of-2 were implemented, providing both sensibility for internal faults and security for external faults with CT with saturation. Besides, it was implemented an external fault detection logic, which inhibits the operation of 1-out-of-1 tripping logic for 150 ms (secure operation mode). G. Circuit Breaker This block was modeled by means of ideal switches controlled by MODELS, where the opening condition is active, only when a tripping signal is received. The ideal switch does not have a opening logic when the current equal or very close to zero, therefore it was implemented. The interrupting time for this model is 50 ms, corresponding to 3 cycles of the fundamental frequency of 60 Hz. Then, each pole of the breaker opens only when the current crosses by zero [6]. V. S IMULATIONS AND R ESULTS The performance of the proposed model was evaluated for both internal and external faults. All the figures were plotted using the PlotXY/ATPDraw interface. Therefore, to better distinguish between the response of the 1-out-of-1 and 2-out-of-2 tripping logics, different scale factors were used in plotting. Also, legends are presented at the bottom of each figure using the following nomenclature: current signals are shown as IXZφ, where X represents either the operating current (OP) or restraint current (RS), respectively; Z represents either the protected zone 1 (Z1) or zone 2 (Z2), respectively; φ assumes A, B or C according to the system phases. Moreover, the following notation is used for tripping signals: TY φZ, where φ and Z are the same codes described before and T assumes either 11 or 22 to represent the tripping logics 1-out-of-1 and 2-out-of-2, respectively. A. Internal Fault An internal AG fault at Bus 1 (Z1 ) was considered in 80 ms. Fig. 5 shows the waveforms of the operating and restraint currents for the phase A and B elements of the Z1 . Because of space limitations, the Phase C is not shown, the behavior is the same of the phase B. As can be seen, for the healthy phases, the restraint current increases and the operating current remain unchanged with value near zero, so that the external fault detection logic is fulfilled, thereby EF is asserted 4 ms after the fault is detected. Still, the operating and restraint currents increase simultaneously for the faulted phase, so that both 1out-of-1 and 2-out-of-2 tripping logics issue a trip, wherein 1-out-of-1 provides the fast trip just 4 ms after the fault is detected. For the sake of simplicity, only the response of the Z1 are shown, but all the phase elements of the Z2 detect external fault. On the other hand, the elements of the checkzone respond as the same way as Z1 elements, allowing the trip command is sent to the breakers, that open approximately 3 cycles after (Fig. 6). B. External Fault In case of an external AG fault was simulated at 80 ms, no trip command was activated, so that both protection zones remain stable (Fig. 7). In fact, for external faults, unless CT saturates, only the restraint current increases thereby the external fault detection logic is fulfilled. Phase A 20 10 0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPAZ1 0,15 0,20 0,15 0,20 [s] 0,25 m:IRSZ1A Phase B 0,6 0,4 0,2 0,0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPBZ1 1,5 [s] 0,25 m:IRSZ1B External Fault Z1 1,0 0,5 0,0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:FXTAZ1 0,15 m:FXTBZ1 0,20 [s] 0,25 [s] 0,25 m:FXTCZ1 TRIP 1-out-of-1 AND 2-out-of-2 1,5 1,0 0,5 0,0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:T11AZ1 m:T11BZ1 0,15 m:T11CZ1 0,20 m:T22AZ1 m:T22BZ1 Figure 5. Internal AG fault in B1 at 80 ms. m:T22CZ1 CBTL1 2000 [A] 1300 1,5 1,0 600 -100 0,5 -800 -1500 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 c:CBTL1A-BL1A 0,15 c:CBTL1B-BL1B 0,20 [s] 0,25 c:CBTL1C-BL1C 0,05 (file BusDiffProtModels.pl4; x-var t) CBTL3 2000 [A] 1300 0,0 0,00 0,10 m:FXTAZ1 0,15 m:FXTBZ1 m:FXTCZ1 0,20 m:FXTAZ2 m:FXTBZ2 [s] 0,25 m:FXTCZ2 0,5 0,0 600 -0,5 0,00 -100 0,05 (file BusDiffProtModels.pl4; x-var t) 0,5 0,10 m:T11AZ1 0,15 m:T11BZ1 m:T11CZ1 0,20 m:T11AZ2 m:T11BZ2 m:T22AZ2 m:T22BZ2 [s] 0,25 m:T11CZ2 -800 -1500 0,00 0,0 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 c:CBTL3A-BL3A 0,15 c:CBTL3B-BL3B 0,20 [s] 0,25 c:CBTL3C-BL3C CBTF1 12 -0,5 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) [kA] 0,10 m:T22AZ1 0,15 m:T22BZ1 m:T22CZ1 0,20 [s] 0,25 m:T22CZ2 Figure 7. External AG fault in TL1 at 80 ms. 6 0 Phase A 16 -6 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 c:CBTF1A-BT1A 0,15 c:CBFT1B-BT1B 0,20 [s] 0,25 8 CCB 6000 [A] 4000 4 2000 0 0,00 0 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPAZ1 0,05 0,10 0,15 0,20 (file BusDiffProtModels.pl4; x-var t) c:CBCCBA-BCCA c:CBCCBB-BCCB c:CBCCBC-BCCC [s] 0,15 0,20 [s] 0,25 0,15 0,20 [s] 0,25 0,15 0,20 [s] 0,25 0,20 [s] 0,25 [s] 0,25 m:IRSZ1A Phase B 10 -2000 -4000 0,00 12 c:CBTF1C-BT1C 0,25 5 Figure 6. Internal AG fault in B1 at 80 ms, current through Zone 1 CBs. C. External Fault with CT Saturation In case of external faults with CT saturation, the operating current does not remain stable with value near zero. In fact, the operating current may be greater than the restraint current during the saturation period, what may leads to a false trip command issuing. Therefore, the external fault detection logic must be performed to block the fast operation mode through the 1-out-of-1 tripping logic, guaranteeing the security of the protection scheme as a whole. In Fig. 8 is depicted the performance of the Z1 elements for an ABC external fault with CTs saturation. One can see that the EF flag is set approximately 4 ms after the fault inception, blocking the 1-out-of-1 tripping logic. When the CT saturation takes place, the operating current becomes erroneously greater than the restraint current, so that the operation condition (3) is fulfilled. However, since two consecutive saturation periods do not occur before 8 ms, the 2-out-of-2 tripping logic is not fulfilled and the protection scheme remain stable. D. Evolving Fault An external AG fault in the TL1 was simulated at 80 ms that evolve to an internal ABG busbar fault at 110 ms on the Bus 1. Initially the external fault detection logic of both Z1 and Z12 are asserted, thereby the 1-out-of-1 tripping logic is blocked during 150 ms (secure operation mode). Then, after 0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPBZ1 m:IRSZ1B Phase C 15 10 5 0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPCZ1 m:IRSZ1C External Fault Z1 1,5 1,0 0,5 0,0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:FXTAZ1 0,15 m:FXTBZ1 m:FXTCZ1 TRIP 1-out-of-1 AND 2-out-of-2 0,5 0,0 -0,5 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:T11AZ1 m:T11BZ1 0,15 m:T11CZ1 0,20 m:T22AZ1 m:T22BZ1 m:T22CZ1 Figure 8. External ABC fault in TL1 at 80 ms, with CT saturation. the internal fault initiates, a trip command is issued by the 2-out-of-2 logic two consecutive half-cycle of 4 ms each separated by 8 ms is detected, as shown in Fig. 9. Phase A 15 R EFERENCES 10 5 0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPAZ1 0,15 0,20 [s] 0,25 0,15 0,20 [s] 0,25 0,15 0,20 [s] 0,25 m:IRSZ1A Phase B 20 10 0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPBZ1 m:IRSZ1B Phase C 0,9 0,4 -0,1 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:IOPCZ1 m:IRSZ1C External Fault Z1 1,5 1,0 0,5 0,0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:FXTAZ1 0,15 m:FXTBZ1 0,20 [s] 0,25 [s] 0,25 m:FXTCZ1 TRIP 1-out-of-1 AND 2-out-of-2 1,5 1,0 0,5 0,0 0,00 0,05 (file BusDiffProtModels.pl4; x-var t) 0,10 m:T11AZ1 m:T11BZ1 0,15 m:T11CZ1 0,20 m:T22AZ1 m:T22BZ1 m:T22CZ1 Figure 9. External AG fault with CT saturation in TL1 at 80 ms evolving to an internal ABG in Bus 1 at 110 ms. VI. C ONCLUSIONS In this paper it was presented the modeling and simulation of a low-impedance busbar differential protection with MODELS language. Different ATPDraw simulations were carried out in a 230 kV power system to test the proposed implementation. The results reveal a good performance for both internal and external faults, even in cases of external faults with CT saturation and evolving faults. With the use of proposed zone selection can be achieved a robust and flexible implementation of protection zone supervision, associated with the CB and DS status. An important advantage of this type of modeling lies in the fact it provides the evaluation of the relay algorithm during power system operational conditions not readily available in actual records, guaranteeing the correct operation of the relay software. [1] Paul M. Anderson, Power System Protection, Piscataway, New Jersey, USA: IEEE Press Series on Power Engineering, 1999. [2] Cigré TB431, Modern Techniques for protecting busbars in HV networks, Cigré Study Committee B5, working group B5.16, Sibui, Romania, 2010. [3] Cigré Working Group B5.17, ”Relay Software models for use with electromagnetic transient analysis programs,” Tech. Rep., 2006. [4] W. G. C. of the System Protection Subcommittee of the IEEE PSRC, ”Software Models for Relays”, IEEE Transactions on Power Delivery, vol. 16, no.2, Apr 2001. [5] C.-H. Kim, M.-H. L , R. K. Aggarwal, and A. T. Johns, ”Educational use of emtp models for the study of a distance relaying algorithm for protecting transmission lines, IEEE Transactions on Power Systems. vol. 15, no. 1, Feb 2000. [6] K. M. Silva, W. L. A. Neves, and B. A. Souza, ”Emtp applied to evaluate three-terminal line distance protection schemes,” IPST: International Conference on Power Systems Transients, Lyon, 2007. [7] X. Luo and M. K. Zunovic, ”Interactive protection system simulation using atp models and c++”. Transmission and Distribution Conference and Exposition, Dallas, Texas, USA, May 2006. [8] Perez, S. G. A. Modeling Relays for Power System Protection Studies. PhD Thesis University of Saskatchewan, Saskatoon, Canada, 2006. [9] K. A. Tavares and K. M. Silva, ”Modeling and Simulation of the Differential Protection of Power Transformers in EMTP Softwares,” DPSP: International Conference on Developments in Power System Protection, Birmingham, UK, 2012. [10] M. T. S. Alvarenga, P. L. Vianna and K. M. Silva, ”High-Impedance Bus Differential Protection Modeling in ATP/MODELS,” Engineering. vol. 5, pp. 37-42, 2013. [11] K. Behrendt, D. Costello, and S. E. Zocholl, ”Considerations for using high-impedance or low-impedance relays for bus differential protection,” Schweitzer Engineering Laboratories, Inc., Pullman, Washington USA, Tech. Rep., 2010 [12] H. J. Altuve and E. O. Schweitzer, Modern Solutions for Protection, Control and Monitoring of Electric Power Systems. Pullman, USA: Schweitzer Engineering Laboratories, Inc., 2010, pp 155-173. [13] G. Ziegler, Numerical Differential Protection: Principles and Applications, 2nd ed. Berlin, Germany: Siemens, 2012. [14] A. Guzmán, B. Quin and C. Labuschagne, ”Reliable Busbar Protection with Advanced Zone Selection,” IEEE Transactions on Power Delivery, vol. 20, pp. 625 - 629, April 2005. [15] IEEE Power System Relaying Committee, EMTP reference models for transmission line relay testing, Rep. no. WGD10, 2004. [Online]. Available: http://www.pes-psrc.org [16] IEEE Power & Energy Society, Power System Relaying Committee. IEEE Guide for Protective Relay - Applications to Power System Buses, New York, 2009. [17] L. Dube, Models in ATP: Language Manual, 1996. [18] A. Kumar and P. Hansen, Digital buz-zone protection, IEEE Computer Applications in Power, vol. 6, pp. 2934, 1993. VII. A PPENDIX The pseudocode of i∗res computation is presented next: input : ires Zφ , with Z(1 or 2) and φ(A, B or C), τ output: i∗res Zφ var : A0 ires Zφ , Max ires Zφ ,t Max ires Zφ if Max ires Zφ < ires Zφ then Max ires Zφ = ires Zφ ; t Max ires Zφ = t; A0 ires Zφ = ires Zφ ; else Max ires Zφ = A0 ires Zφ × [1 − (60/τ ) × (t − t Max ires Zφ )]; end i∗res Zφ = Max ires Zφ