Download Safety Light Curtain 120V AC Interface - Allen

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Rectifier wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Voltage optimisation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power over Ethernet wikipedia , lookup

Switch wikipedia , lookup

Mains electricity wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Relay wikipedia , lookup

Distribution management system wikipedia , lookup

Control system wikipedia , lookup

Crossbar switch wikipedia , lookup

Buck converter wikipedia , lookup

Power electronics wikipedia , lookup

Metadyne wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
Safety Products Supplement
Safety Light Curtain
120V AC Interface
Presence Sensing
Safety Devices
Power Supply and Safety Relay
Description
The Allen-Bradley Guardmaster 120V AC interface box consists of a
NEMA 4 rated lockable metal enclosure, a DIN mount 3amp, 24V DC
power supply and either a single or dual 22.5mm safety relay(s).
The single safety relay module provides 2 N.O. safety and one N.C.
auxiliary (nonsafety) “potential free” relay outputs. The dual safety
relay configuration allows for two pairs of safety light curtains to
independently control one or two machines.
The safety relay(s) can be configured for monitored manual reset or
automatically reset. The resetting function can be through the key
switch mounted on the front cover of the interface box or wired as a
remote switch.
Prepunched holes located on the bottom of the enclosure allow for
easy wiring of the system.
56
Specifications
Input Power
120/230V AC
Output Power
24V AC ±15%
Power Consumption
2W/4W
Fuses
Input (external, recommended) 500mA time lag
Output (external, recommended) 6A quick acting
2 N.C. Symmetric or Asymmetric
Inputs
Switch Selectable
Maximum Input Resistance
S11-S12 300 ohms
S21-S22 200 ohms
S33-S34 250 ohms
Reset
Monitored Manual or
Automatic/Manual
Outputs
4 N. O. Safety
2 N.C. Auxiliary nonsafety
Output Rating
N.O. B300, AC15, 3A/250V AC
P300, DC13, 3A/24V DC
N.C. B300, AC15, 2A/250V AC
P300, DC13, 2A/24V DC
Min. Switched Current/Voltage
1mA/10V
Power ON Delay
Manual Reset 40ms
Auto Reset 200ms
Response Time
15ms
Relay Module Indication LEDs
Power Green = Ready
K1 Green = K1 Closed, If K1 alone is lit,
check for short across reset button
K2 Green = K2 Closed
Operating Temperature
-15°C to +55°C (+5° to +131°F)
Humidity
90% RH
Enclosure Protection
NEMA 4, IP65
Max. Conductor Size
1 x 2.5mm2 (14AWG) stranded
1 x 4mm2 (12AWG) solid
Weight
4886/5113g (10.75/11.25lbs)
Electrical Life
230 VAC/2 A/460VA/AC 15 100,000 operations
Maximum Operating Frequency
1200 cycles/hour
Mechanical Life
10,000,000 operations
Vibration
0.35mm 10-55Hz
Safety Products Supplement
Safety Light Curtain 120V AC Interface
Ordering Details
Inputs
Safety Outputs
Auxiliary Outputs
2 N.C.
2 N.O.
1 N.C.
4 N.C.
4 N.O.
2 N.C.
Power Supply
24V DC
Catalog Number
440L-M8400
440L-M8500
Dimensions—mm (in)
200.0 (7.87)
301.6
(11.87)
Presence Sensing
Safety Devices
161.9 (6.37)
3.17
(0.12)
1.77
(0.07)
.0
.12
5
70
63.5 (2.5)
104.7
(4.12)
22.2 (0.87)
Application Details
Disconnect power. Use a screwdriver to pop
open cover to reveal internal switches.
L
Light
Curtain
Interface
Box
L1
1 2 3 4 5 6 7 8 9 10 1112 13 14 15 16 17
Power LED
K3
101.6
(4.0)
K1
Receiver
Transmitter
K4
+24V
GND
K3 K4
Man. Restart
(Jump 15 & 16)
Auto Restart
(Jump 16 & 17)
Man. Restart w/
MPCE feedback
(N.C. contacts
between 15 & 16
Symmetric Inputs
Switch S1
Asymmetric Inputs
K2
Machine Prime
Mover Elements
Automatic Reset
Switch S2
Monitored Manual Reset
K3 K4
Auto Restart
w/MPCE
feedback (N.C.
contacts
between 15 &
16
Arc suppression
devices (100Ω, 2.2µF)
K3
Or
N
(Jumper req’d if
mts not used)
L2
K4
101.6 (4.0)
57
Safety Products Supplement
Controllers/Relay
Interfaces
Specifications
min.
typ.
max.
Standards
EN 50100
Approvals
BG and CE marked for all
applicable directives
Protection Class
I
Housing Protection
IP 20 (switch cabinet, standard rail)
Supply Voltage U V
19.2V
24V
28.8V
Residual Ripple ➊
5V SS
Power Consumption (no load)
0.3A (6W)
Inputs Command Unit
Start key
Presence Sensing
Safety Devices
T 13,T 14
NO contact
Command Unit Act. Time Period
30 ms
Contactor Monitoring
T 21,T 22 Contactor Monitoring
NC contacts in series
Permissible Cont. Drop-off Time
No restrictions
Permissible Contactor Resp. Time
200 ms
Sensor Signal T 3,T 4
Two-channel
Description
Input Resistance (active)
606Ω
The Allen-Bradley Guardmaster 440L-M8200 safety relay is designed
specifically to interface with safety light curtains. It has two normally
open safety outputs (control reliable) and one normally closed
auxiliary output. The 440L-M8200 requires 24V DC and has
convenient connections for the transmitter and the receiver.
Signal Active at
17.6V U V
Safety Light Curtain Safety Relay
Features
•
•
•
•
•
•
•
Automatic or manual reset
MPCE monitoring
Din rail mount
LED indication of power on outputs
2 N.O. safety outputs
1 N.C. auxiliary output
Removable terminal strip for easy replacement
Signal LOW at
0V
Time Period Tolerance between T3
and T4
15 ms
674Ω
742Ω
2.4 V
Outputs
15 ms ➋
Response Time
Switching Current
<0.1mA➌
4A
Switching Voltage AC/DC
240V AC /
60V DC
Switching AC /DC
1200 VA/
50 W
Mech. Life Expectancy (switch
actions)
10 7
Elec. Life Expectancy (switch actions) 10 9
Delay on Energization (NO contacts) 40 ms
Delay on Energization (NC contacts) 15 ms
Supply Voltage
Connection
UV
Pluggable strip terminal
Cable Cross Section
2.5 mm 2
Load Capacity of Terminals
(C 1 ...4,D 1 ...4)
2.5 A
Operating Data
Safety Category
Type 4
Tested to
pr EN 50100 Part 1 and 2
Ambient Operating Temp.
0°C
+55°C
Storage Temperature
–25°C
+75°C
Relative Humidity (noncondensing)
15%
95%
Vibration Specification
5g,10 ...55Hz as per IEC 68-2-29
Shock Resistance
10g,16ms as per IEC 68-2-29
Dimensions (W x H x D)
152 x 73 x 118 mm 3
➊ Maximum voltage limits must not be exceeded,minimum levels must be acheived.
➋ Response time without attenuation of switching elements (relays), e.g. by means of
interference suppressors.
➌ Contact gold plating vaporizes when currents >100mA switched. Minimum switched
current becomes 10mA.
58
Safety Products Supplement
Controllers/Relay
Interfaces
Ordering Details
Reset
24V DC
Manual/
Automatic
Floating
Blanking
Fixed
Blanking
PSDI
Muting
Relay Outputs
no
no
no
no
2 N.O. Safety
1 N.C. Aux.
4 amp
Catalog
Number
440L-M8200
Presence Sensing
Safety Devices
Voltage
Dimensions—mm (in)
152
(5.98)
118
(4.65)
70
(2.76)
35 (1.38)
Connections
Command Without
start/
Unit
N.O.
“Reset”
restart Monitoring
N.C.
interlock of contactors Without N.O. input
contact
contactor
input
monitoring input
2)
24V DC 0V
1)
or
A 1+
A 2-
PE
T0
PE
T 13
T 14
X 12
T21
T 22
2)
X 21
X 22
1.3
2.3
3.1
N.O. N.O. N.C.
Contacts
Auto
Power Input
Off
On
Monitor Ext.
Contactors Outputs
Off
Reset
Sender
Receiver
24V DC 0V
D1
X 11
0V
24V DC 0V
C1
or
24V DC 0V
PE
24V DC 0V
C2
D2
24V DC 0V
PE
24V DC 0V
T3
T4
OSSD OSSD
1
2
AOPD type 4
AOPD type 4
Sender
Receiver
C3
D3
24V DC 0V
PE
C4
D4
1.4
2.4
N.O.
output
3.2
N.C.
contact
input
N.O.
output
1) Potential equalization, if power pack -0V
not connected with (VDE 0160)
2) Wire jumper
The jumpers X11/X12 for (disabling of) restart inhibit and X21/X22 for
(disabling of) contactor monitoring must not be routed externally (only in
isolated plastic-sheathed cables).
59
Safety Products Supplement
Controllers
Application Possibilities and Conditions
Areas of Application
The 440L-M8100 with an AOPD is used as a control unit in protective
applications for point-of-operation guarding, hazardous areas and
entry/exit systems. Furthermore, it assumes responsibility for control
functions such as the muting of palletizer entry/exit systems or press
brakes, as well as blanking and other control functions on presses (e.g.
break operation).
Typical areas of application are:
Presence Sensing
Safety Devices
General
• Presses in the metal-working, plastics, leather and stone industries
(functions: guarding, break operation, blanking, etc.)
• Press Brakes (functions: guarding, blanking, muting before bottom
dead center, etc.)
• Palletizer or entry/exit applications (functions: guarding, muting,
etc.)
The 440L-M8100 Programmable Safety Interface Light Curtain
Control Unit is a control unit for active optoelectronic protective
devices (AOPD), and is designed as a self-monitoring device in
accordance with EN 50100. It is intended for industrial applications
and is distinguished by:
Regulations for Use
•
•
•
•
The same applies to applications which take place outside closed
rooms (ambient temperature 0°C - 50°C (32°F - 122°F)).
High availability
No wearing parts
Compact construction
Universal applicability
Note: This product is only for use with POC safety light curtains.
It can not be used with SafeShield, PAC or AAC devices.
Features
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Wear-free operation
Secure, short-circuit-protected semi-conductor outputs
Line monitoring of outputs
Modem microprocessor technology
Short response time
LCD display for programming function indication and diagnostic
messages
Connection for two pairs of AOPD type 4 sensors or up to four
pairs of AOPD type 2 sensors (also mixed operation)
Automatic testing of AOPD type 2 sensors
User-programmable combinations of defined functions
Pre-programmed standard functions: Guard only, single-break,
double-break
Programming password
Contactor monitoring and restart interlock may be selected
Fixed/floating blanking for AOPD type 4 (SafeShield Safety Light
Curtain)
Muting function with connection for up to 4 muting sensors
Outputs for indicators of all special functions
RS 485 data interface for sensor controls and diagnostics
Connection for operating mode selector switch
Break operation with up to 8 breaks
60
The 440L-M8100 is designed to be installed in the machine's control
cabinet (IP 20). If it is used outside the control cabinet a suitable
housing fitted with a DIN rail profile should be used, e.g. an electrical
enclosure (IP 54).
Operations such as programming or connecting the unit, i.e. all
activities on the 440L-M8100 which could affect the safe operation
of the unit, should only be carried out by qualified personnel.
System Structure
Overview of System
The 440L-M8100 has a standard housing with two 33-pin plug-in
terminal strips. A two-line LCD display and set of control keys are
built into the front panel for operation and programming. Three
integral LED indicators display the 440L-M8100’s output conditions:
green LED illuminate
outputs active
red LED illuminate
outputs inactive
yellow LED illuminate
malfunction
The yellow LED indicates an operational malfunction of the system or
the peripheral equipment.
Safety Products Supplement
Controllers
Connecting and Operating Elements
The LCD display contains two lines, each capable of displaying 20
characters. In addition to the programming menus, all the system’s
operational states are displayed. In the event of operational
malfunctions or malfunctions of the peripheral equipment,
appropriate diagnostic messages are given.
The control keyboard is used in conjunction with the LCD display for
programming and diagnostics on the 440L-M8100. Details on
programming may be found in the operating instructions.
1 pair of
type 4
sensors
or
2 pair of
type 2
sensors
1 pair of type 4
sensors
or
2 pair of type 2
sensor
1 pair of
type 4
sensors
or
2 pair of
type 2
sensors
E1
Function and Operation
E2
440L-M8100
E1
Presence Sensing
Safety Devices
Thanks to the plug-in connection terminals, the wiring can be
prepared without the 440L-M8100, thus enabling any exchange to be
carried out in the shortest possible time, without any need to rewire
the connecting leads.
E2
440L-M8100
Operating Principle
The 440L-M8100 assumes responsibility for control functions as an
operational link between the machine control system and the control
function from the AOPD, and switches the required control elements
(contactors) of the machine control system via dual-channel semiconductor outputs.
The signals arriving from the 440L-M8100 and the peripheral
equipment are further electronically processed by dual channel
microprocessor electronics. Type 2 sensors (testable) and/or Type 4
sensors (self-monitoring) may be operated with the 440L-M8100. The
internal control system can distinguish between the different
categories. Type 2 sensors are automatically cyclically tested by the
440L-M8100 every 60 minutes.
The 440L-M8100 is designed for the connection of two pairs of
AOPD type 4 sensors or up to four pairs of AOPD type 2 sensors. (1
pair = 1 emitter and 1 receiver.) "Mixed" operation of sensor type 4
and type 2 AOPDs can also be configured.
E1
440L-M8100
E2
E1
E2
A 440L-M8100
Various types of connection to the 440L-M8100
Type 2 sensors are always to be used in pairs, i.e. 2 pairs of type 2 or 4
pairs of type 2 are used. The automatic testing of type 2 sensors
increases the protective level of the whole protective system (no
external measures needed).
Instead of a second AOPD type 4 sensor, an extra 440L-M8100 (type
4) can also be connected, in order to "daisy chain" 440L-M8100s.
61
Safety Products Supplement
Controllers/Relay
Interfaces
Operating Modes
External
Mode Select
Presence Sensing
Safety Devices
Setting Operating Modes
All set up 440L-M8100 operating modes can be called up using a
corresponding BCD switch. A bridge connection or direct selection
using the "run modes" program is possible for a fixed operating mode.
Standard operating modes, such as guard only, single-break, doublebreak are provided preprogrammed, i.e. the interface can be operated
without user programming.
Input
1
2
3
0
0
0
Furthermore, 3 positions of the selector switch can be devoted to
user-definable application programs.
keyboard mode
(programming)
0
0
1
guard only operation
0
1
0
single-break
1
0
0
double-break
1
1
0
user program 1
1
0
1
user program 2
0
1
1
user program 3
(1
1
1
not used)
0
input not connected with ↓ open
1
input connected with ↓
Restart Interlock/Indicator Lights
The function "with/without restart interlock" can be set directly on
terminals 52, 53 and 54. This can be done using either jumpers or
external changeover contacts, which makes it possible to switch over
the restart interlock (RI) without programming, e.g. on presses:
• In the dangerous downward motion with RI
• In the nondangerous upward motion without RI
For direct connection to indicator lights showing the following
functions 24 DC outputs are available on terminals 57 to 64:
Connection terminals for operating mode selector switch, with
assignment
"Reset button required"
"Muting"
"Reduced Resolution/Blanking" and "Dirt build-up" (AOPD)
Guard only operation
*)
Single-break
*)
Max. output current 0.4A each (minimum current 0.02A for "muting"
and "blanking").
Double-break
*)
Multi-break (3-... 8 breaks)
*)
Blanking
*)
Muting
*)
Mechanical Mounting, Ambient Conditions
Reduced Resolution
*)
Starting sequence for break operation
*)
The 440L-M8100 is mounted on a DIN rail, or if necessary in a
suitable external housing (snap-on mounting). The permissible
ambient temperature range is 0°C - 50°C
(32°F - 122°F) (IP 54).
Sensor test with/without
Single stroke restart
*)
Contactor monitoring: with/without
Reset button: latched/unlatched
*) Can be programmed or combined into user programs 1, 2 and 3
Operating modes which may be programmed via the
440L-M8100 menu
Installation
Electrical Installation
The 440L-M8100 operates with 24V DC ± 20% and has a current
consumption of 0.5A (without load). Connection is potential-free via
two 33-pin plug-in terminal strips. This enables the wiring to be
carried out before the 440L-M8100 is installed. The terminals are
designed for a maximum wire cross-section of:
1 x 2.5 mm2 with sleeve, or
1 x 4 mm2 solid.
62
Safety Products Supplement
Controllers/Relay
Interfaces
A1 and A2
muting
muting
muting
muting
-
B1 and B2
- (open)
muting
single-stroke restart
“latched restart”
single-stroke restart
“unlatched restart”
single-stroke restart
“latched restart”
single-stroke restart
“unlatched restart”
External Indicators Blanking/Reduced Resolution Muting
If "Blanking/Reduced Resolution" is used, the corresponding
indicators must be connected. These safety related indicators are
monitored via the 440L-M8100 (output current 0.02...0.4A).
The indicators "Restart Required" and "Weak Signal" are optional
(output current 0...0.4A). In case of using this NPN indicator outputs
on a PLC, a resistor (i.e. 1 kΩ/1 W) has to be connected between
terminal 57-58 and/or 63-64 for potential equalization. The output
signal is provided on terminal 58 and/or 64 (NPN function). The 0Vpotential of both power supplies 440L-M8100 and PLC must be
linked.
Functions dependent on program settings.
Type-2 Sensors
When type 2 sensors are used, two pairs are to be connected for each
440L-M8100 input circuit. They are tested automatically. The test
command to the sensor (terminals 14/16/26/28) can be selected by
simple connection to the adjacent terminals (terminals 15/17/27/29)
(test with 0V potential or plus potential).
The single-channel switching outputs of the type 2 receivers are
connected to terminals 9 and 10 (pairs 1 and 2) and/or to terminals 21
and 22 (pairs 3 and 4).
63
Presence Sensing
Safety Devices
The extent of wiring depends on the particular application.
Safety Products Supplement
Controllers/Relay
Interfaces
Specifications
440L-M8100 Blanking Modes
1.
Floating Blanking
A. 14mm System: Min. = Gap - 0.2" - 0.9" Resolution
Max. = Gap - 4.7" - 5.3" Resolution
These are in 0.3" Increments
Presence Sensing
Safety Devices
B. 30mm System: Min. = Gap - 0 5" - 1.7" Resolution
Max. = Gap - 9.4" - 10.6" Resolution
These are in 0.6" Increments
Note: You may not use floating blanking with PSDI mode
(e.g.: single break mode).
2.
Reduced Resolution
A. 14mm System Only
Min. = 0.2" Gap - 0.9" RESOLUTION
Max. = 1.1" Gap - 1.8" RESOLUTION
These are in 0.3" INCREMENTS
3.
Fixed Blanking
A. 14mm and 30mm: Can blank all beams but beam #1
Note: You may blank more than one area.
ATTENTION: The safety distance must
be recalculated and light curtains must be
remounted when floating blanking,
reduced resolution or fixed blanking is
activated.
Supply voltage
Ripple
24V DC 20%
max. 5VSS
Current Consumption
approx. 12W (without load)
Inputs
Run modes
Data interface
For 2 ESPD type 4, 4 ESPD type 2 fixed/
programmable, called up via selector or
fixed setting RS 485 for ESPD sensor
failure control and diagnostics, Twisted
pair required for cable length>10m
Input currents
Contactor monitoring: dynamic 100mA
for T<1ms, static 10mA.
Test inputs: dynamic 100mA for T<1ms,
static 10mA
Outputs
Switching output
2 x PNP, 0.5A, overload protection
Response time
5ms
Lamp driver
For command devices and special
functions, max. 0.4A per output
Diagnostics
Via display for RS 485 interface
Requirement
In accordance with EN 50100 type 4
Enclosure rating
IP 20
Connection terminals
Plug-in type
Wire cross-section, max.
2.5mm2 with end sleeve/4mm2 solid
Ambient operating temp.
0 to 50°C
Storage temperature
-25°C to +70°C
Housing
WxHxD
Standard housing for top hat rail (snapon mounting)
200 x 123 x 118mm3
Fitting type
Top hat rail 35 x 15mm2
Programmable InterfaceOptional
64
Input
Voltage
Reset
Floating
Blanking
Fixed
Blanking
PSDI
Muting
Outputs
Catalog
Number
24V DC
Manual/
Automatic
yes
yes
yes
yes
2 PNP OSSD
440L-M8100
Safety Products Supplement
Controllers/Relay Interfaces
Dimensions—mm (inches)
200 (7.87)
118 (4.65)
4.5
(0.18)
Presence Sensing
Safety Devices
123
(4.84)
34.5
(1.36)
Wiring Diagram
PE
Input
24V DC
K2
K1
K2
24V max 0.5A
K1
24V max 0.5A
AOPD Sender
White
Green
Yellow
Gray
Blue
Brown
Black
White
Green
Blue
Brown
Black
AOPD Receiver
No Conn.
No Conn,
Supply voltage
24V DC ±20%
Safety Stop Circuit
OutPE
PE OutPE
puts
puts
2
Power Comm 1 2 Power Test 1 Test 2 Power 1 2 Power
Test 3 Test 4 1
Receiver 1
Sender 1
Receiver 2
Sender 2
Output Channels
PE
Auxiliary Inputs
Indicators
A1
A2
B1
B2
Cycle Relay System
Contact Monitor Test
External
Mode Select
Restart
Mode
Restart Restart Muting
Switch Required Active
Reduced
Reso- Weak
lution Signal
Receiver
1 or 2
Output
Status
Ext Int
Blanking Lamp (required)
(24V DC, 0.02-0.4A)
Muting Lamp (requried)
(24V DC, 0.02-0.4A)
Restart Lamp (optionsal)
(24V DC, 0.4A max.)
Restart
Ext = Automatic Reset
Int = Manual Reset
Hard wired for user
defined mode 1,
leave open for
keyboard mode.
Relay Monitor
(or N.C. contact)
Muting switches
or sensors
K1 K2
65
Safety Products Supplement
Mat Manager
Specifications
Standards
IEC/EN60204-1, ISOTR12100,
EN1760-1, ANSI/RIA 15.06, ANSI
B11.19
Safety Category
Cat. 3 per EN954-1
Approvals
CE marked for all applicable
directives,
Power Supply
24V AC/DC, 110/230V AC
0.8 to 1.1 x rated voltage, 50/60 Hz
Power Consumption
Fuses
Presence Sensing
Safety Devices
Safety Mat Manager
Description
The Safety Mat Manager is designed to monitor multiple safety mats,
each with its own connection. The Safety Mat Manager accepts up to 8
individual mats with 4-pin micro quick disconnect connectors.
The Safety Mat Manager provides an LED status indication for each
of the mat connections. Since the LEDs indicate whether the mat is
shorted or open, troubleshooting and replacement of a damaged mat
within a mat system, is much quicker when compared a traditional mat
system where multiple mats are wired in series.
13W or 13VA
Input 500mA internal (2)
Output (external) 6A Slow Blow or 10A Quick Blow
Safety Inputs
8 4-wire safety mats with micro-QD.
Maximum Input Resistance
100 ohms
Reset Internal switch selectable Monitored Manual or Auto./Man.
Button Front Panel or Remote via Terminals
Outputs
2 N.O. Safety; 1 N.C. Auxiliary
Output Rating
B300, AC-15, 2A/250V AC
N300, DC-13, 2A/24V DC
Min. Switched Current/Voltage
10mA/10V
Response Time
35ms
Indication LEDs
Green
Green
Green
Green
Mat Status LEDs Run Condition
Stop Condition
Missing Shorting Plug
Not Used
Green
Green-Red (Bi-color)
Red
Off
Power
Machine Enabled
Auto Reset Mode
Manual Reset Mode
An internal switch allows for the setting of the reset to Automatic/
Manual or Monitored Manual. When set to Automatic/Manual, the
reset circuit can be jumpered, connected auxiliary contacts, or
connected to an unmonitored manual reset by adding a momentary
normally open switch in the monitoring loop. When set to Monitored
Manual, the monitoring circuit must be closed and then opened to
activate the outputs.
Impulse Withstand Voltage
2500V
Pollution Degree
2
Stepping on any one of the mats deactivates the safety outputs. The
outputs include 2 normally open safety rated outputs used to shut
down the machine and 1 normally closed auxiliary output to indicate
the status of the Mat Manager. The safety outputs have independent
and redundant internal contacts to help ensure the safety function.
Mounting
Surface (Wall) Mount
Weight
3160g (7lbs)
Electrical Life
220V AC/4A/880VA cosφ=0.35
220V AC/1.7A/375VA cosφ=0.6
30V DC/2A/60W
10V DC/0.01A/0.1W
100,000 operations
500,000 operations
1,000,000 operations
2,000,000 operations
Mechanical Life
2,000,000 operations
Features
•
•
•
•
Accepts up to 8 individual mats
2 Safety output contacts
1 Auxiliary output contact
Automatic/Manual or Monitored Manual Reset
66
Operating Temperature
-25°C to +45°C (-13°F to 113°F)
Enclosure Protection
IP65 (NEMA 13) Steel with
Polycarbonate Faceplate
Maximum Conductor Size
0.2–2.5mm2 (24-14AWG)
Torque Settings—terminal screws 0.4Nm (3.54 lb•in)
Vibration
10-55Hz, 0.15mm
Shock
10g, 11ms half-sine