Download Power Factor Correction for Power Systems Power Factor Correction

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Pulse-width modulation wikipedia , lookup

Buck converter wikipedia , lookup

Islanding wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Three-phase electric power wikipedia , lookup

Decibel wikipedia , lookup

Voltage optimisation wikipedia , lookup

Standby power wikipedia , lookup

Mains electricity wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power over Ethernet wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Audio power wikipedia , lookup

Wireless power transfer wikipedia , lookup

Electric power system wikipedia , lookup

Alternating current wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electrification wikipedia , lookup

Power factor wikipedia , lookup

AC adapter wikipedia , lookup

Power engineering wikipedia , lookup

Transcript
Power Factor Correction for Power Systems
First Semester Report
Spring Semester 2007
by
Pamela Ackerman
Prepared to partially fulfill the requirements for
EE401
Department of Electrical and Computer Engineering
Colorado State University
Fort Collins, Colorado 80523
Report Approved:
Project Advisor
Senior Design Coordinator
Abstract
Wasted energy capacity, also known as poor power factor, is often overlooked. It can
result in poor reliability, safety problems and higher energy costs. The lower your power
factor, the less economically your system operates.
The actual amount of power being used, or dissipated, in a circuit is called true power.
Reactive loads such as inductors and capacitors make up what is called reactive power. The
linear combination of true power and reactive power is called apparent power.
Power system loads consist of resistive, inductive, and capacitive loads. Examples of
resistive loads are incandescent lighting and electric heaters. Examples of inductive loads are
induction motors, transformers, and reactors. Examples of capacitive loads are capacitors,
variable or fixed capacitor banks, motor starting capacitors, generators, and synchronous
motors.
Power factor correction (PFC) is usually achieved by adding capacitive load to offset
the inductive load present in the power system. The power factor of the power system is
constantly changing due to variations in the size and number of the motors being used at
one time. This makes it difficult to balance the inductive and capacitive loads continuously.
There are many benefits to having power factor correction. As a customer the cost
doesn’t get passed on for having a low power factor. As a utility company, equipment has a
much longer life span and maintenance costs remain low.
- ii -
Table of Contents
Title
i
Abstract
ii
Table of Contents
iii
List of Figures
iv
Chapters
Chapter I – Types of Power
1
Chapter II – Power System Loads
2
Chapter III – Power Factor Defined
4
Chapter IV – Methods of Power Factor Correction
7
Chapter V – Benefits of Power Factor Correction
11
Chapter VI – Conclusions and Future Plans
11
References
12
Bibliography
12
- iv -
List of Figures
Figure 1
Types of Power with Equations
1
Figure 2
Resistive Load Circuit Example
3
Figure 3
Inductive Load Circuit Example
3
Figure 4
Resistive and Inductive Load Circuit Example
4
Figure 5
The Power Triangle
5
Figure 6
Power Factor Triangle Illustrating Effects of a Capacitor
8
Figure 7
Induction Motor Without Parallel Capacitor
9
Figure 8
Induction Motor With Parallel Capacitor
10
- iv -
Chapter I – Types
Types of Power
The actual amount of power being used, or dissipated, in a circuit is called true power.
It is measured in watts and is symbolized mathematically by the capital letter P. True power is
a function of the circuit’s dissipative elements, such as resistances (R). [1]
Reactive loads such as inductors and capacitors dissipate zero power, but the fact that
they drop voltage and draw current gives the perception that they do dissipate power. This
“dissipated power” is called the reactive power and is measured in Volt-Amps-Reactive (VAR).
Reactive power is represented by the capital letter Q, and is a function of a circuit's reactance
(X). [1]
The combination of true power and reactive power is called apparent power. It is the
product of a circuit's voltage and current, without reference to phase angle. Apparent power
is measured in the unit of Volt-Amps (VA) and is symbolized by the capital letter S. Apparent
power is a function of a circuit's total impedance (Z). [1]
There are equations relating the three types of power to resistance, reactance, and
impedance (all using scalar quantities):
P =True Power
P = I 2R
P=
V2
R
Where P is measured in Watts
V2
X
Where Q is measured in VoltVolt-AmpsAmps-Reactive (VAR)
Q = Reactive Power Q = I 2 X
Q=
V2
S = VI
Z
Where S is measured in VoltVolt-Amps (VA)
S = Apparent Power S = I 2 Z
Figure 1
-1-
S=
Chapter II – Power System Loads
Power system loads consist of resistive, inductive, and capacitive loads. Examples of
resistive loads are incandescent lighting and electric heaters. Examples of inductive loads are
induction motors, transformers, and reactors. Examples of capacitive loads are capacitors,
variable or fixed capacitor banks, motor starting capacitors, generators, and synchronous
motors. [2]
Inductive and capacitive loads are opposite in nature. Equal amounts of inductive and
capacitive loads within the same system will offset each other leaving only real power. This is
defined as a power factor of 1 or unity. When a unity power factor is achieved the real power
(KW) or demand is equal to the apparent power (KVA). Achieving a unity power factor will
provide the most efficient power system. [2]
In a purely resistive circuit, all circuit power is dissipated by the resistor, voltage and
current are in phase with each other, and the true power is equal to the apparent power (as
seen in Figure 2). [1]
In a purely reactive circuit, no circuit power is dissipated by the load. Rather, power is
alternately absorbed from and returned to the AC source. Voltage and current are 90o out of
phase with each other, and the reactive power is equal to the apparent power (as seen in
Figure 3). [1]
In a circuit consisting of both resistance and reactance, there will be more power
dissipated by the load than returned, but some power will definitely be dissipated and some
will merely be absorbed and returned. Voltage and current in such a circuit will be out of
phase by a value somewhere between 0o and 90o. The apparent power is vector sum of the
true power and the reactive power (as seen in Figure 4). [1]
-2-
P = True power = I2R = 240 Watts
Q = Reactive power = I2X = 0 KVAR
S = Apparent power = I2Z = 240 VA
Figure 2: Resistive load only
P = True power = I2R = 0 Watts
Q = Reactive power = I2X = 238.73 KVAR
S = Apparent power = I2Z = 238.73 VA
Figure 3: Inductive load only
-3-
P = True power = I2R = 119.365 Watts
Q = Reactive power = I2X = 119.998 KVAR
S = Apparent power = I2Z = 169.256 VA
Figure 4: Resistive and inductive load
Chapter III
III – Power Factor Defined
In power systems, wasted energy capacity, also known as poor power factor, is often
overlooked. It can result in poor reliability, safety problems and higher energy costs. The lower
your power factor, the less economically your system operates.
Power factor is the ratio between the real power and the apparent power drawn by
an electrical load. Like all ratio measurements it is a unit-less quantity and can be represented

TruePower
KW 
 , where PF is power factor, kW is the real
mathematically as  PF =
=
ApparentPo wer KVA 

power that actually does the work, KVA is the apparent power and KVAR (not included in the
equation) is the reactive power. In an inductive load, such as a motor, active power performs
-4-
the work and reactive power creates the electromagnetic field. The three types of power
relate to each other in a trigonometric form as seen in Figure 5 below. [2]
Figure 5: The Power Triangle
For the purely resistive circuit, the power factor is 1 (perfect), because the reactive
power equals zero. Here, the power triangle would look like a horizontal line, because the
opposite (reactive power) side would have zero length.
For the purely inductive circuit, the power factor is zero, because true power equals
zero. Here, the power triangle would look like a vertical line, because the adjacent (true
power) side would have zero length.
The same could be said for a purely capacitive circuit. If there are no dissipative
(resistive) components in the circuit, then the true power must be equal to zero, making any
power in the circuit purely reactive. The power triangle for a purely capacitive circuit would
again be a vertical line (pointing down instead of up as it was for the purely inductive circuit).
-5-
Power factor can be an important aspect to consider in an AC circuit; because any
power factor less than 1 means that the circuit's wiring has to carry more current than what
would be necessary with zero reactance in the circuit to deliver the same amount of (true)
power to the resistive load. The poor power factor makes for an inefficient power delivery
system.
Poor power factor can be corrected, paradoxically, by adding another load to the
circuit drawing an equal and opposite amount of reactive power, to cancel out the effects of
the load's inductive reactance. Inductive reactance can only be canceled by capacitive
reactance, so we have to add a capacitor in parallel to our example circuit as the additional
load. The effect of these two opposing reactances in parallel is to bring the circuit's total
impedance equal to its total resistance (to make the impedance phase angle equal, or at least
closer, to zero). [3]
Power factor measures how efficiently the current is being converted into real work—
with a low power factor, more electrical current is required to provide the same amount of
real power. All current causes dissipation in a distribution system. These losses can be
(
)
modeled as Loss = I 2 * R , where R is the resistance. A power factor of 1 will result in the
most efficient loading of the supply; a load with a power factor of 0.5 will result in higher
losses in the distribution system. [3]
The reactive load of an industrial power system typically consists of a large number of
AC induction motors. This can cause the total load to be up to 50% inductive. Large inductive
loads cause the apparent power to be 25% to 41% higher than the real power. If the utility
billing is based on real power (KW) only, the utility must provide up to 41% more capacity
than they are billing for. Since it takes more capacity and is more expensive to serve a
customer with a low power factor, that customer has to pick up the tab. Most electrical rate
-6-
tariffs contain provisions that include a minimum power factor. Customers who fall short of
the minimum power factor level receive a power factor charge. Power factor charges may
range from $5 to thousands of dollars per month. [2]
Overall there are several consequences of a low power factor; these consequences
include decreased system capacity, increased system losses, and extra cost.
Benefits of
increasing a low power factor include eliminated or reduced power factor charges on utility
bills, more efficient operations with increased capacity and reduced current draw.
Chapter IV
IV – Methods of Power Factor Correction
In the real world, utilities normally only require a power factor of 0.9. Although a unity
power factor provides the most efficient power system, a unity power factor leaves the power
system susceptible to harmonic problems. Harmonic problems cause excessive heating in
motors, nuisance tripping, and premature failure of solid state components.
Power factor correction (PFC) is usually achieved by adding capacitive load to offset
the inductive load present in the power system. The power factor of the power system is
constantly changing due to variations in the size and number of the motors being used at
one time. This makes it difficult to balance the inductive and capacitive loads continuously.
In addition, harmonic problems can be introduced if the capacitors are not sized with
the specific power system characteristics in mind. The utility company may also restrict or deny
the introduction of KVARs into their power system. These are all considerations that need to
be addressed prior to making any decisions about the size or type of power factor correction.
-7-
Figure 6: Power Triangle illustrating effects of capacitor PFC
The most inexpensive and widely used method of correcting the power factor is
through the use of one fixed capacitor bank connected to the incoming transformer or
switchgear bus. The fixed capacitor bank is sized to regulate a 0.9 power factor during
maximum operational inductive loading. This means that during periods of operation where
less than maximum inductive loading is utilized, extra KVAR capacity will be introduced into
the utility power system. The only draw backs to this method are utility restrictions and future
inductive loads that change the maximum operational inductive loading. [2]
A variation of the above method can be used only if a discrete number of motors are
causing the power factor problems. Individual capacitors can be connected in parallel with
each motor. When the motor is energized, the capacitor bank is also energized to provide
power factor correction while the motor is being used (as seen in Figures 3 and 4 located on
the next page). The benefit of this method is that the amount of capacitive load is regulated
-8-
with the amount of inductive load. The drawbacks to this method are that it may not be
feasible physically or economically to have an individual capacitor for each motor, and
maintenance of multiple units may be costly and difficult. [2]
Another method of power factor correction is the use of a variable capacitor bank. This
bank would be connected just like the fixed bank. The advantage of the variable capacitor
bank is that the bank monitors the system power factor and automatically regulates the
amount of capacitive load connected to the system to offset the inductive load. Since the
capacitive load is regulated, there would be no conflict with the utility. The variable capacitor
banks normally come with internal protection, provide space for additional banks, and provide
a centrally located easily maintained unit. The draw backs to the variable capacitor bank are
an increased chance of harmonic problems due to the variations in capacitance, initial cost,
and maintenance costs of internal parts used for capacitor switching. [2]
Figure 7: Induction motor without a capacitor in parallel
-9-
Figure 8: Induction motor with a capacitor in parallel
A combination of the previously mentioned methods seems to be the normal
configuration that is used once correction is decided upon. Normally, capacitors are
connected to the largest motors to provide correction while they are running. In addition, a
variable or fixed capacitor bank is connected to the main transformer or switchgear. The
advantage of this is regulation of the capacitive load and a reduction in the size of the
capacitor bank connected to the main transformer or switchgear. [2]
It should be noted that too much capacitance in an AC circuit will result in a low
power factor just as well as too much inductance. You must be careful not to over-correct
when adding capacitance to an AC circuit. You must also be very careful to use the proper
capacitors for the job (rated adequately for power system voltages and the occasional voltage
spike from lightning strikes, for continuous AC service, and capable of handling the expected
- 10 -
levels of current). If a circuit is predominantly inductive, we say that its power factor is lagging
(because the current wave for the circuit lags behind the applied voltage wave). Conversely, if
a circuit is predominantly capacitive, we say that its power factor is leading. Thus, our example
circuit started out with a power factor of 0.705 lagging, and was corrected to a power factor
of 0.999 lagging. [1]
All in all poor power factor in an AC circuit can be corrected to a value close to unity
(1), by adding a parallel reactance opposite to the effect of the load's reactance. If the load's
reactance is inductive in nature (which is almost always will be), parallel capacitance is what is
needed to correct poor power factor.
Chapter V – Benefits of Power Factor Correction
The primary benefit of power factor correction is the elimination of charges related to
reactive power-consumption. If the utility is adding a power factor penalty or billing for
apparent power (KVA), reduction in reactive power will net savings. The amount of savings
seen will depend on the size, configuration, and operation of the power system. Typically, the
costs for correction are paid back inside of one year, and after that, the savings will reduce
operating costs. In addition, power factor correction will improve the overall performance of
the power system which can increase switchgear, starter, and motor life. The bottom line is
protection, efficiency, and savings.
Chapter VI
VI – Conclusions and Future Plans
Since this is the project’s first semester, there is a lot more in store. Our future plans
include learning Siemens Power System Simulator for Engineering (PSS/E) and helping the fall
EE461 students learn and use PSS/E. In order to learn PSS/E we will be utilizing the labs
- 11 -
created by the WAPA System Study Senior Design Group. In addition to the learning PSS/E
our plans include a system impact study of the proposed Colorado State University Windfarm.
Projects are given $50 per person per semester. Since this first semester was mostly
spent doing research, we came in extremely under budget. The only real expenses were
group members’ time.
References
1. Lessons In Electric Circuits Volume II, Sixth Edition, Tony R. Kuphaldt, 2007
2. Power Factor Correction, Ralph A. Frye III, P.E.,
http://www.wagesterlease.com/aboutus/articles/powerfactor.html
3. Power Factor, L M Photonics Ltd,
http://www.lmphotonics.com/pwrfact.htm?gclid=CJbHjdTMjosCFSUeGAodtRe8VQ
Bibliography
Power Factor Correction, Wikipedia, http://en.wikipedia.org/wiki/Power_factor_correction
Power Factor Correction, How Stuff works, http://www.howstuffworks.com/
Electrical Machines, Drives, and Power Systems, Sixth Edition, Theodore Wildi, 2006
Acknowledgements
Thank you to Gerald E. Hager for his time and expertise, Dr. George Collins for his
continued support and the WAPA Impact Study Senior Design Group for their collaborative
efforts.
- 12 -