Download Full Text - Journal of American Science

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stray voltage wikipedia , lookup

Electric power system wikipedia , lookup

Wind turbine wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electrification wikipedia , lookup

Electrical substation wikipedia , lookup

Life-cycle greenhouse-gas emissions of energy sources wikipedia , lookup

History of electric power transmission wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Power engineering wikipedia , lookup

Alternating current wikipedia , lookup

Rectiverter wikipedia , lookup

Electrical grid wikipedia , lookup

Intermittent energy source wikipedia , lookup

Distributed generation wikipedia , lookup

Islanding wikipedia , lookup

Mains electricity wikipedia , lookup

Bus (computing) wikipedia , lookup

Transcript
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
Integration of wind Power Plant on Electrical grid based on PSS/E
S. Othman 1; H. M. Mahmud2 S. A. Kotb3 and S. Sallam2
1
Faculty of Engineering, Al-Azhar University, Cairo, Egypt.
2
Egyptian Electricity Hold Company, Cairo, Egypt.
3
Egyptians Atomic Authority, Egyptian 2nd Research Reactor, Cairo, Egypt.
[email protected]
Abstract: The capacity of electrical power system in Egypt will increase rapidly in the coming twenty years. The
conventional energy sources such as oil, natural gas, coal are finite and generate pollution. Alternatively, the
renewable energy sources like wind, fuel cell, solar, biogas/biomass, tidal, geothermal, etc. are clean and abundantly
available in nature. In the year 2030 will reach the generation of electricity from wind generation plants to about
20% of the electrical network loads according to the forecast of the Egyptian government. This paper concerned on
PSS/E modeling of wind power generation of Doubly-fed Induction Generator (DFIG) type and their impact on
issues of Egyptian electrical grid. Since Wind Turbine Generators (WTG) doesn't have the same characteristics as
synchronous generators, the appropriate modeling of wind farms is requisite for transmission system operators to
analyze the best options of transmission grid reinforcements as well as to evaluate the wind power impact on
reliability and security of supply. In case of grid faults wind turbines have to supply a definite reactive power
depending on the instantaneous voltage and to return quickly to normal operation.
[S. Othman; H. M. Mahmud S.; A. Kotb and S. Sallam. Integration of wind Power Plant on Electrical grid based
on PSS/E. J Am Sci 2015;11(11):103-110]. (ISSN: 1545-1003). http://www.jofamericanscience.org. 11
Keywords: Power System transients, PSS/E dynamic simulation DFIG
of PSS/E WTG user models which have been covered
in many publications.
Not with standing the provisions of the Egyptian
Transmission System Code (the Grid Code), this Wind
Farm Grid Connection Code specifies the special
requirements for the connection of Wind Farms to the
High and Extra High Voltage transmission system (the
Grid). The modelling approach of wind farms is based
on Wind Grid Code Requirements. The aim of Wind
Grid Code is to provide a self-contained description of
the technical and operational requirements that are to
be met by the developers and operators of WindPowered Generating Stations (WPGS) that wish to
connect to the Egyptian electricity grid [4]. The Wind
Code applies to all WPGSs that are or have applied to
be connected to the transmission grid, with installed
capacity of more than 7 GW until 2030. Developers of
WPGSs intending to apply for connection to the
transmission grid should be aware that they are
required to provide Project Planning data at this level
of detail at the time of filing the application in order
for the TSO (Transmission system operator,) to carry
out the relevant connection design and impact studies.
The Grid Operator is authorized to change one or
more of the following requirements or to give further
requirements, if it is necessary for a safety and stable
operation of the Grid.
 In case of a deviation of the voltage ranges at
the Grid Connection Point from its permissible
voltage range, the Wind Farm shall be able to deliver
Available Active Power according to wind conditions
1. Introduction
The large scale development of wind
turbines/farms becoming a significant part of the
generation capacity in some area, which requires that
the power system treats the wind turbines/farms like a
power source, not only an energy source. The wind
power penetration would result in variations of load
flows in the interconnected systems, as well as redispatch of conventional power plants, which may
causes the reduced reserve power capacity [1, 2].
Integration of large scale wind power may have severe
impacts on the power system operation. Stable,
reliable and economic operation of the power system
under the massive integration of wind power is a big
challenge to power system operators. The technical
specifications, grid codes, for grid connection of wind
turbines have been produced to specify the
requirements that wind turbines must meet in order to
be connected to the grid. Examples on such
requirements include capabilities of contributing to
frequency and voltage regulation by continuously
controlling the active power and reactive power
supplied to the power system, and the low voltage
ride-through capability [3, 4, and 5]. This paper
present the most significant characteristic and specific
aspects of detailed DFIG modeling containing variable
speed wind turbine units. A specific case study is
analyzed in order to identify the main requirements for
wind farm connection to the Egyptian electrical grid.
This paper will not address the detailed mathematics
103
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
when the voltage at the Grid Connection Point
remains within the ranges from 0.9 to 1.1 per unit..
Any automatic disconnection of the Wind Farm from
the Grid shall be prohibited due to the deviation
within the voltage ranges, expressed by the voltage at
the Grid Connection Point related to nominal voltage.
 In case of a deviation of the grid frequency
from its permissible value, any automatic
disconnection of the Wind Farm from the Grid shall
be prohibited due to the deviation within the
frequency range of 47.5 Hz until 51.5 Hz.
 Voltage unbalance is defined as the deviation
between the highest and lowest line voltage divided by
the average line voltage of three phases. Wind Farms
shall be able to withstand voltage unbalance not
exceeding 3%.
 The voltage fluctuations in a Wind Farm can
occur because of the switching operations (capacitor
banks, wind turbine generator start/stop), inrush
currents during wind turbine generator starting etc.
The maximum voltage fluctuation is 5% from the
voltage nominal value.
 The wind turbine generators of the Wind
Farm shall only connect to the Grid (start-up), if the
frequency and the voltage at the Grid Connection
Point are within the following limits: Frequency: 48
Hz ≤ f ≤ 50.2 Hz and Voltage arrowed 0.95 per unit ≤
U ≤ 1.05 per unit.[6]
2. Egyptian Electrical National Grid
The Egyptian Electrical National Grid (EENG)
in Egypt is divided into five geographical regions,
namely, Alexandria, Delta, Cairo, Canal, and Upper
Egypt. The Egyptian Electricity transmission system
is composed of 500 kv, 400 kv, 220 kv, 132 kv, and
66 kv levels [7]. A proposal of wind power plant will
be located in the Canal Zone. Figure (2) shows the
section from the Canal Zone which contain the wind
power plant.
3. Wind turbine model
The DFIG wind turbine generator model is
defined in Behnke [8]. The complete WTG model is
divided into four functional blocks, as indicated in
Figure (1). This paper is primarily concerned with the
dynamic interactions of the wind turbine and electrical
grid under transient fault.
Fig.1. WTG dynamic model connectivity, from [8].
The power system modeling including wind
turbines for steady state analysis in PSS/E version33 is
fairly simple, as shown in figure (2). Each individual
wind turbine generator (WTG) is connected to a 690V
bus and the WTGs are connected to the wind farm
internal network through their 0.69/35 kV step-up
transformers. The internal network is organized in
eight rows or sections with five WTGs in each section.
Within these rows, the wind turbines are connected
through 35kV underground cables of different lengths
and capacities depending on the location of each unit
and the distance to the 35kV collector bus. The load
flow solution provides the initial conditions for
subsequent dynamic simulations. The maximum and
minimum limits of active and reactive power must be
respected in order to achieve a successful
initialization. Inconsistencies between the power flow
and the dynamic model will result in an unacceptable
initialization. The proposed wind frame connection on
Canal Zone as shown in figure (2).
104
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
Fig. (2) Proposed wind frame connection in Canal Zone
rotor induction generator with a voltage source
converter connected to the slip-rings of the rotor. The
stator winding are coupled directly to the grid and the
rotor winding is connected to power converter as
Shown in figure (3) [8, 9, 10].
4. Dynamic model of DFIG
The variable speed wind turbine using DFIG are
more popular technology which is used word-wide
due to advantages such as high energy efficiency and
controllability. DFIG is basically a standard, wound
Fig. (3) Double- Fed induction generator
105
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
initial conditions. Figure (4.b) shows the change in
generators active power surrounding generators active
power violations, the active power to zero P.U
suddenly during the fault time 0.2. After fault
clearance, the active power starts to recover the same
initial condition at t=8 sec.
Figure (4.c) shows the surrounding generator
reactive power oscillations start to damp from t = 2.2
sec till 8 sec and goes to steady state situation which is
the same as the initial conditions. The speed
generators are shown in Fig (4.d). Clearly, short
circuit occurrence at its bus changes the speed
generators. They oscillate severely during the fault
duration (from t = 2 to 2.2 sec). Then, the oscillations
start to damp from t = 6 sec. till sec. and goes to
steady state situation which is the anther initial
conditions.
Figure (4.e) shows the surrounding buses voltage
violations, the voltage dips to zero P.U suddenly
during the fault time 0.2. After fault clearance, the
voltage starts to recover itself.
5. Simulation Result
Effect Electrical disturbance on wind power plant
1- Fault on Bus 1517 (WPP)
A three-phase short circuit is applied to the
generator terminal on bus 1517 (wind power plant)
when t= 2 sec and cleared when t = 2.2 sec, with the
line being tripped at the same time. The simulation
result is shown in Figure (4).
As shown from Figure (4.a-e), when the fault can
be cleared correctly, the system can run stable and the
wind power plant can operate without dropping the
unit. The change in mechanical power, change in
active power, change in reactive power, change in the
generator speed and change in the bus voltage.
The mechanical power of power generators is
shown in Figure (4.a). Clearly, short circuit
occurrence at its bus changes the mechanical power of
generators. They oscillate severely during the fault
duration (from t = 2 to 2.2 sec). Then, the oscillations
start to damp from t = 2.2 sec till sec and goes to
steady state situation which is the same as the new
0.9
0.5
bus 1517-2
bus 1517-3
0.85
bus 1517-1
bus 1517-2
bus 1517-3
bus 1517-4
0.4
A ct iv e power (pu)
mechanical power (pu )
bus 1517-1
bus 1517-4
0.8
0.3
0.2
0.1
0
0.75
0
2
4
6
8
0
10
1
2
3
4
5
6
time in sec
time in sec
9
10
0.11
0.2
0.1
0.15
Change of speed (pu)
Reactive power (pu)
8
(b) Change in Active generation power
(a) Mechanical power
0.1
bus 1517-1
bus 1517-2
bus 1517-3
bus 1517-4
0.05
0
-0.05
7
0
2
4
6
time in sec
8
10
0.09
0.08
bus 1517-1
bus 1517-2
bus 1517-3
bus 1517-4
0.07
0.06
0.05
0
2
4
time in sec
(c) Reactive generation power
6
(d) Change generator Speed
106
8
10
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
reactive power, change in the generator speed and
change in the bus voltage.
The mechanical power of power generators is
shown in Fig (5.a). They oscillate during the fault
duration (from t = 2 to 2.2 sec). Then, the oscillations
start to damp from t = 2.2 sec till sec and goes to
steady state situation which is the same as the new
initial conditions. Figure (5.b) shows the change in
generators active power surrounding generators active
power violations, the active power to zero P.U
suddenly during the fault time 0.2. After fault
clearance, the active power starts to recover the same
initial condition at t=7 sec. Figure (5.c) shows the
surrounding generator reactive power oscillations start
to damp from t = 2.2 sec till 8 sec and goes to steady
state situation which is the same as the initial
conditions. The speed generators are shown in Figure
(5.d). Clearly, short circuit occurrence at its bus
changes the speed generators. They oscillate during
the fault duration (from t = 2 to 2.2 sec). then, the
oscillations start to damp from t = 9 sec till sec and
goes to steady state situation which is the anther initial
conditions. Figure (5.e) shows the surrounding buses
voltage violations, the voltage dips to zero P.U
suddenly during the fault time 0.2. After fault
clearance, the voltage starts to recover itself.
1
bus 1517
bus 1999
(pu)
0.6
Voltage
0.8
0.4
0.2
0
0
2
4
6
8
10
time in sec
(e) Bus Voltage
Fig (4) Effect the fault from 2 to 2.2 sec on bus
1517 on WPP and Grid
2- Fault on Bus 1519 (WPP)
A three-phase short circuit is applied to the
generator terminal on bus 1519 (wind power plant)
when t= 2 sec and cleared when t = 2.2 sec, with the
line being tripped at the same time. The simulation
result is shown in Figure (5). As shown from Figure
(5.a-e), when the fault can be cleared correctly, the
system can run stable and the wind power plant can
operate without dropping the unit. The change in
mechanical power, change in active power, change in
0.5
bus1519-1
bus 1519-2
bus 1519-2
bus 1519-4
bus 1519-5
mechanical power (pu)
0.45
0.4
0.35
real power (pu)
bus 1519-1
bus 1519-2
bus 1519-3
bus 1519-4
bus 1519-5
0.81
0.3
0.25
0.2
0.15
0.1
0.05
0.76
0
1
2
3
4
5
6
time in sec
7
8
9
10
0
0
1
(a) Mechanical power
4
5
6
time in sec
7
8
9
10
0.11
bus 1519-1
bus 1519-2
bus 1519-3
bus 1519-4
bus 1519-5
0.15
bus 1519-1
bus 1519-2
0.105
bus 1519-3
bus 1519-4
bus 1519-5
0.1
change of speed (pu)
reactive power (pu)
3
(b) Active generation power
0.2
0.1
0.05
0
-0.05
2
0.095
0.09
0.085
0.08
0.075
0
1
2
3
4
5
6
time in sec
7
8
9
10
0
(c) Reactive generation power
1
2
3
4
5
6
time in sec
7
8
(d) Change generator Speed
107
9
10
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
reactive power, change in the generator speed and
change in the bus voltage.
The mechanical power of power generators is
shown in Figure (6.a). They oscillate during the fault
duration (from t = 2 to 2.2 sec). Then, the oscillations
start to damp from t = 2.2 sec. till sec. and goes to
steady state situation which is the same as the same
initial conditions. Figure (6.b) shows the change in
generators active power surrounding generators active
power violations, the active power to zero P.U
suddenly during the fault time 0.2. After fault
clearance, the active power starts to recover the same
initial condition at t=8 sec. Figure (6.c) shows the
surrounding generator reactive power oscillations start
to damp from t = 2.2 sec till 8 sec and goes to steady
state situation which is the same as the initial
conditions. The speed generators are shown in Fig
(6.d). Clearly, short circuit occurrence at its bus
changes the speed generators. They oscillate during
the fault duration (from t = 2 to 2.2 sec). Then, the
oscillations start to damp from t = 9 sec. till sec. and
goes to steady state situation which is the anther initial
conditions. Figure (6.e) shows the surrounding buses
voltage violations, the voltage dips to zero P.U
suddenly during the fault time 0.2. After fault
clearance, the voltage starts to recover itself.
1
bus 1519
bus 1999
bus voltage (pu)
0.8
0.6
0.4
0.2
0
0
1
2
3
4
5
6
time in sec
7
8
9
10
(e) bus voltage
Fig. (5) Effect the fault from 2 to 2.2 sec on bus
1519 on WPP and Grid Functions
3- Fault on Bus 1528 (WPP)
A three-phase short circuit is applied to the
generator terminal on bus 1530 (wind power plant)
when t= 2 sec and cleared when t = 2.2 sec, with the
line being tripped at the same time. The simulation
result is shown in Figure (6). As shown from Fig. (6,
a, b, c, d, e), when the fault can be cleared correctly,
the system can run stable and the wind power plant
can operate without dropping the unit. The change in
mechanical power, change in active power, change in
0.3
bus 1528-1
bus 1528-2
bus 1528-3
bus 1528-4
bus 1528-5
bus 1528-6
bus 1528-7
0.8
0.75
real power (pu)
mechanical power (pu)
0.85
0.25
bus 1528-1
bus 1528-2
0.2
bus 1528-3
bus 1528-4
bus 1528-5
bus 1528-6
bus 1528-7
0.15
0.1
0.05
0
2
4
6
8
10
0
time in sec
0
(a) Mechanical power
1
2
3
4
5
6
time in sec
7
8
9
10
(b) Active generation power
0.11
bus 1528-1
bus 1528-2
bus 1528-3
bus 1528-4
bus 1528-5
bus 1528-6
bus 1528-7
0.105
reactive power (pu)
0.2
0.15
change of speed (pu)
bus 1528-1
bus 1528-2
bus 1528-3
bus 1528-4
bus 1528-5
bus 1528-6
bus 1528-7
0.25
0.1
0.1
0.095
0.09
0.085
0.08
0.05
0
0.075
0
1
2
3
4
5
6
time in sec
7
8
9
10
0
(c) Reactive generation power
1
2
3
4
5
6
time in sec
7
8
(d) Change generators Speed
108
9
10
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
power, change in reactive power, change in the
generator speed and change in the bus voltage.
The mechanical power of power generators is
shown in Fig (7.a). They oscillate during the fault
duration (from t = 2 to 2.2 sec). Then, the oscillations
start to damp from t = 2.2 sec. till sec. and goes to
steady state situation which is the same as the new
initial conditions. Figure (7.b) shows the change in
generators active power surrounding generators
active power violations, the active power to zero P.U
suddenly during the fault time 0.2. After fault
clearance, the active power starts to recover the same
initial condition at t=9 sec. Figure (7.c) shows the
surrounding generator reactive power oscillations
start to damp from t = 2.2 sec till 8 sec and goes to
steady state situation which is the same as the initial
conditions.
The speed generators are shown in Figure (7.d).
Clearly, short circuit occurrence at its bus changes the
speed generators. They oscillate during the fault
duration (from t = 2 to 2.2 sec). Then, the oscillations
start to damp from t = 7 sec till sec and goes to steady
state situation which is the anther initial conditions.
Figure (7.e) shows the surrounding buses voltage
violations, the voltage dips to zero P.U suddenly
during the fault time 0.2. After fault clearance, the
voltage starts to recover itself.
1
0.9
0.8
bus 1528
bus 3999
voltage (pu)
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0
1
2
3
4
5
6
time in sec
7
8
9
10
(e) Change in bus voltage
Fig. (6) Effect the fault from 2 to 2.2 sec on bus
1528 on WPP and Grid Functions
4- Fault on Bus 1530 (WPP)
A three-phase short circuit is applied to the
generator terminal on bus 1530 (wind power plant)
when t= 2 sec and cleared when t = 2.2 sec, with the
line being tripped at the same time. The simulation
result is shown in Figure (7). As shown from Figure
(7, a, b, c, d, e), when the fault can be cleared
correctly, the system can run stable and the wind
power plant can operate without dropping the unit.
The change in mechanical power, change in active
0.5
1
bus 1530-1
bus 1530-2
bus 1530-3
bus 1530-4
bus 1530-5
0.45
0.4
0.35
real power (pu)
mechanical power (pu)
0.9
0.8
bus
bus
bus
bus
bus
bus
bus
0.7
0.6
1530-1
1530-2
1530-3
1530-4
1530-5
1530-6
1530-7
bus 1530-6
bus 1530-7
0.3
0.25
0.2
0.15
0.1
0.5
0.4
0.05
0
0
1
2
3
4
5
6
time in sec
7
8
9
10
0
3
4
5
6
7
8
9
10
(b) Active generation power
0.4
0.11
bus 1530-1
bus 1530-2
bus 1530-3
bus 1530-4
0.35
0.3
0.1
bus 1530-5
bus 1530-6
bus 1530-7
0.25
bus 1530-1
bus 1530-2
bus 1530-3
bus 1530-4
bus 1530-5
bus 1530-6
bus 1530-7
0.105
Change of speed (pu)
Reactive power (pu)
2
time in sec
(a) Mechanical power
0.2
0.15
0.1
0.095
0.09
0.085
0.08
0.05
0.075
0
-0.05
1
0
1
2
3
4
5
6
time in sec
7
8
9
0
10
2
4
6
time in sec
(d) Change generator Speed.
(c) Reactive generation power
109
8
10
Journal of American Science 2015;11(11)
http://www.jofamericanscience.org
References
1. Amin A. M. "Improvement Integration of
Zafarana Egypt Wind Farm Connected to the
Unified Power Grid." International Electrical
Engineering Journal (IEEJ) Vol. 1 (2011) No. 1,
pp. 514-522 ISSN 2078-2365 514.
2. Kabashi G. "Wind Farm Modeling for Steady
State and Dynamic Analysis" World Academy of
Science, Engineering and Technology Vol:5
2011-02-20.
3. Ramtharan G., "Frequency support from doubly
fed induction generator wind turbines" IET
Renew. Power Gener., 2007, 1, (1), pp. 3– 9.
4. Wind Turbine Grid Connection and Interaction,
Deutsches Windenergie-Institut GmbH Germany
· Tech-wise A/S Denmark · DM Energy United
Kingdom.
5. Ian A. Hisken "Dynamics of Type-3 Wind
Turbine
Generator
Models",
IEEE
TRANSACTIONS ON POWER SYSTEMS,
VOL. 27, NO. 1, FEBRUARY 2012.
6. Wind Farm Grid Connection Code in addition to
the Egyptian Transmission Grid Code (ETGC),
Version: Final Draft 5th January, 2012.
7. Report of actual data for Egyptian Network,
2013.
8. M. Behnke, "Generic Type-3 Wind TurbineGenerator Model for Grid Studies", Version 1.1,
WECC Wind Generator Modeling Group, Sep.
2006.
9. WECC Wind Power Plant Dynamic Modeling
Guide, WECC Renewable Energy Modeling
Task Force, Nov. 2010.
10. PSS/E manual, version 33.
1
0.9
0.8
bus 1530
bus 3999
Bus voltage (pu)
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0
2
4
6
8
10
time in sec
(e) Change in bus voltage
Fig. (7)
Conclusion
Power flow, short circuit and dynamic analyses
were carried out in order to check the influence of the
proposal wind farm on the Egyptian electrical grid in
respect of the Grid Code requirements. The large scale
PSS/E model was used for the computer simulations.
The PSS/E wind turbine stability model WT3 was
used for the dynamic simulation with the objective of
simulating the dynamic performance of DFIG
technology WTGs. The overall conclusion of these
analyses is that the proposal wind farm project does
have an influence on the transmission system, but all
of the requirements of the Grid Code relating to the
wind farm connection were satisfied.