* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download TRANSFORMER
Stray voltage wikipedia , lookup
Opto-isolator wikipedia , lookup
Buck converter wikipedia , lookup
Power engineering wikipedia , lookup
Rectiverter wikipedia , lookup
Voltage optimisation wikipedia , lookup
Single-wire earth return wikipedia , lookup
Distribution management system wikipedia , lookup
Electrical substation wikipedia , lookup
Magnetic core wikipedia , lookup
Mains electricity wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Three-phase electric power wikipedia , lookup
Resonant inductive coupling wikipedia , lookup
History of electric power transmission wikipedia , lookup
BASICS OF TRANSFORMER 1 NEED WORKING PRINCIPLE TYPES OF TRANSFORMERS CONSTRUCTION FEATURES TRANSFORMERS ACCESSORIES MAJOR TRANSFORMERS IN POWER PLANTS TRANSFORMER LOSSES CONDITION MONITORING OF TRANSFORMERS 2 HISTORICALLY, THE FIRST ELECTRICAL POWER DISTRIBUTION SYSTEM DEVELOPED BY EDISON IN 1880s WAS TRANSMITTING DC (DIRECT CURRENT) IT WAS DESIGNED FOR LOW VOLTAGES (SAFETY AND DIFFICULTIES IN VOLTAGE CONVERSION); THEREFORE, HIGH CURRENTS WERE NEEDED TO BE GENERATED AND TRANSMITTED TO DELIVER NECESSARY POWER THIS SYSTEM SUFFERED SIGNIFICANT ENERGY LOSSES! THE SECOND GENERATION OF POWER DISTRIBUTION SYSTEMS (WHAT WE ARE STILL USING) WAS PROPOSED BY TESLA FEW YEARS LATER. HIS IDEA WAS TO GENERATE AC POWER OF ANY CONVENIENT VOLTAGE, STEP UP THE VOLTAGE FOR TRANSMISSION (HIGHER VOLTAGE IMPLIES LOWER CURRENT AND, THUS, LOWER LOSSES), TRANSMIT AC POWER WITH SMALL LOSSES, AND FINALLY STEP DOWN ITS VOLTAGE FOR CONSUMPTION POWER LOSS IS PROPORTIONAL TO THE SQUARE OF THE CURRENT TRANSMITTED THE STEP UP AND STEP DOWN VOLTAGE CONVERSION WAS BASED ON THE USE OF TRANSFORMERS. O OPTIMISE COST OF BULK TRANSMISSION OF POWER FROM GENERATORS TO CONSUMERS REDUCTION IN TRANSMISSION LOSS O REDUCE OR INCREASE VOLTAGE IN AC SYSTEM NABLES SAFE SUPPLY VOLTAGE TO CONSUMERS SOLATION OF REGULATION TWO SYSTEMS FOR VOLTAGE A TRANSFORMER IS A DEVICE HAT CONVERTS ONE AC VOLTAGE TO ANOTHER T THE SAME FREQUENCY AC VOLTAGE CONSISTS OF ONE OR MORE COIL(S) OF WIRE WRAPPED ROUND A COMMON FERROMAGNETIC CORE HESE COILS ARE USUALLY NOT CONNECTED ELECTRICALLY OGETHER OWEVER, THEY ARE CONNECTED THROUGH THE COMMON AGNETIC FLUX CONFINED TO THE CORE SSUMING THAT THE TRANSFORMER HAS AT LEAST TWO INDINGS, ONE OF THEM (PRIMARY) IS CONNECTED TO A OURCE OF AC POWER; THE OTHER (SECONDARY) IS ONNECTED TO THE LOADS. CORE TYPE CIRCULAR SHAPED WINDINGS SHELL TYPE: RECTANGULAR SHAPED WINDINGS CORE HE CORE WILL WORK AS A CAGE FOR THE MAGNETIC FLUX OST OF THE FLUX WILL BE KEPT INSIDE THE CORE HE CORE IS MADE WITH A VERY SPECIAL ELECTRICAL STEEL HE STEEL IS MADE AS THIN INSULATED SHEETS WHICH UST BE MOUNTED ONE BY ONE HE FINAL GOAL IS TO MINIMIZE THE SIZE OF THE CORE ND LOSSES. THE CORE: WHICH PROVIDES A PATH FOR THE MAGNETIC LINES OF FLUX THE PRIMARY WINDING: WHICH RECEIVES ENERGY FROM THE AC SOURCE THE SECONDARY WINDING: ENERGY FROM THE PRIMARY DELIVERS IT TO THE LOAD THE ENCLOSURE: WHICH RECEIVES WINDING AND WHICH PROTECTS THE ABOVE COMPONENTS FROM DIRT, MOISTURE, AND MECHANICAL DAMAGE. 2 ADJACENT COILS COILS NOT PHYSICALLY CONNECTED TO EACH OTHER HE PRIMARY WINDING IS CONNECTED TO A 50 HERTZ OLTAGE SOURCE AC HE MAGNETIC FIELD (FLUX) BUILDS UP (EXPANDS) AND OLLAPSES (CONTRACTS) ABOUT THE PRIMARY WINDING HE EXPANDING AND CONTRACTING MAGNETIC FIELD ROUND THE PRIMARY WINDING CUTS THE SECONDARY INDING AND INDUCES AN ALTERNATING VOLTAGE INTO HE WINDING HIS VOLTAGE CAUSES ALTERNATING CURRENT TO FLOW HROUGH THE LOAD HE VOLTAGE MAY BE STEPPED UP OR DOWN DEPENDING ON HE DESIGN OF THE PRIMARY AND SECONDARY WINDINGS. HEN A LOAD DEVICE IS CONNECTED ACROSS THE SECONDARY INDING OF A TRANSFORMER, CURRENT FLOWS THROUGH THE CONDARY AND THE LOAD E MAGNETIC FIELD PRODUCED BY THE CURRENT IN THE CONDARY INTERACTS WITH THE MAGNETIC FIELD PRODUCED BY E CURRENT IN THE PRIMARY IS INTERACTION RESULTS FROM THE MUTUAL INDUCTANCE TWEEN THE PRIMARY AND SECONDARY WINDINGS. SIMPLE TRANSFORMER INDICATING PRIMARY- AND SECONDARY-WINDING FLUX RELATIONSHIP THE VOLTAGES IN THE PRIMARY & SECONDARY COILS DEPEND ON NUMBER OF TURNS IN COILS Vp = PRIMARY VOLTAGE Vs = SECONDARY VOLTAGE Np = NUMBER OF TURNS OF PRIMARY COIL Ns = NUMBER OF TURNS OF SECONDARY COIL THERE ARE 2 TYPES OF TRANSFORMERS STEP-UP TRANSFORMER Vs Vp Ns Np CIRCUIT SYMBOL STEP-DOWN TRANSFORMER CIRCUIT SYMBOL Vs < Vp Ns < Np IF NO POWER IS LOST IN A TRANSFORMER (NO POWER LOSS) F THE SECONDARY OF A TRANSFORMER HAS TWO TIMES AS ANY TURNS AS THE PRIMARY, THE VOLTAGE INDUCED INTO HE SECONDARY WILL BE TWO TIMES THE VOLTAGE ACROSS HE PRIMARY F THE SECONDARY HAS ONE-HALF AS MANY TURNS AS THE RIMARY, THE VOLTAGE ACROSS THE SECONDARY WILL BE NE-HALF THE VOLTAGE ACROSS THE PRIMARY. OWEVER, THE TURNS RATIO AND THE CURRENT RATIO OF A RANSFORMER HAVE AN INVERSE RELATIONSHIP. HUS, A 1:2 STEP-UP TRANSFORMER WILL HAVE ONE-HALF HE CURRENT IN THE SECONDARY AS IN THE PRIMARY. 2:1 STEP-DOWN TRANSFORMER WILL HAVE TWICE THE URRENT IN THE SECONDARY AS IN THE PRIMARY. POWER TRANSFORMERS : USED IN TRANSMISSION NETWORK OF HIGHER VOLTAGES, DEPLOYED FOR STEP-UP AND STEP DOWN TRANSFORMER APPLICATION (765 kV, 400 kV, 220 kV, 110 kV, 66 kV, 33kV,22kV) DISTRIBUTION TRANSFORMERS: USED FOR LOWER VOLTAGE DISTRIBUTION NETWORKS AS A MEANS TO END USER CONNECTIVITY. (11kV, 6.6 kV, 3.3 kV, 440V, 230V) TRANSFORMER CONNECTIONS DELTA/STAR: USED IN GENERATING STATIONS FOR STEP-UP STAR/DELTA: USED IN RECEIVING STATIONS FOR STEP-DOWN ALL GTs ARE DELTA/STAR CONNECTED ALL TIE IN TRANSFORMERS ARE STAR/STAR CONNECTED. TRANSFORMER CONNECTIONS STAR / STAR CONNECTION STAR / DELTA CONNECTION O-LOAD LOSSES TAKE PLACE MAINLY IN THE CORE SHEETS. IT ORRESPONDS TO ABOUT 25% OF THE TRANSFORMER LOSSES HE DC LOSSES TAKE PLACE EXCLUSIVELY IN WINDINGS HE EDDY/STRAY LOSSES TAKE PLACE IN ALL PIECES OF METAL NSIDE THE TRANSFORMER (FRAMES, CORE, WINDING, TANKS TC), A LARGE PART OF IT ARE GENERATED IN THE WINDINGS SPECIALLY DANGEROUS LOSSES ARE THE ONES CONCENTRATED IN SMALL VOLUME SINCE THEY MAY CAUSE A HOT-SPOT. TO MODEL A REAL TRANSFORMER ACCURATELY, WE NEED TO ACCOUNT FOR THE FOLLOWING LOSSES: COPPER LOSSES:RESISTIVE HEATING IN THE WINDINGS I2R EDDY CURRENT LOSSES : RESISTIVE HEATING IN THE CORE, PROPORTIONAL TO THE SQUARE OF VOLTAGE APPLIED TO THE TRANSFORMER HYSTERESIS LOSSES : ENERGY NEEDED TO REARRANGE MAGNETIC DOMAINS IN THE CORE LEAKAGE FLUX : FLUX THAT ESCAPES FROM THE CORE AND FLUX THAT PASSES THROUGH ONE WINDING ONLY. NOT ALL THE MAGNETIC FIELD PRODUCED BY THE PRIMARY IS INTERCEPTED BY THE SECONDARY. A PORTION OF THE LEAKAGE FLUX MAY INDUCE EDDY CURRENTS WITHIN NEARBY CONDUCTIVE OBJECTS, SUCH AS THE TRANSFORMER'S SUPPORT STRUCTURE, AND BE CONVERTED TO HEAT. SSES IN THE TRANSFORMER ARE OF THE ORDER OF 1% OF ITS LL LOAD KW RATING ESE LOSSES GET CONVERTED IN THE HEAT THEREBY THE MPERATURE OF THE WINDINGS, CORE, OIL AND THE TANK RISES E HEAT IS DISSIPATED FROM THE TRANSFORMER TANK AND THE ADIATOR IN TO THE ATMOSPHERE RANSFORMER COOLING HELPS IN MAINTAINING THE MPERATURE RISE OF VARIOUS PARTS WITHIN PERMISSIBLE MITS CASE OF TRANSFORMER, COOLING IS PROVIDED BY THE RCULATION OF THE OIL RANSFORMER OIL ACTS AS BOTH INSULATING MATERIAL AND ALSO OOLING MEDIUM IN THE TRANSFORMER R SMALL RATING TRANSFORMERS HEAT IS REMOVED FROM THE RANSFORMER BY NATURAL THERMAL CONVECTION R LARGE RATING TRANSFORMERS THIS TYPE OF COOLING IS NOT DIFFERENT TRANSFORMER COOLING METHODS ARE: AIR COOLING FOR DRY TYPE TRANSFORMERS: AIR NATURAL TYPE (A.N.) AIR FORCED TYPE (A.F.) COOLING FOR OIL IMMERSED TRANSFORMERS: OIL NATURAL AIR NATURAL TYPE (O.N.A.N.) OIL NATURAL AIR FORCED TYPE (O.N.A.F.) OIL FORCED AIR NATURAL TYPE (O.F.A.N.) OIL FORCED AIR FORCED TYPE (O.F.A.F.) OIL IMMERSED WATER COOLING: OIL NATURAL WATER FORCED (O.N.W.F.) OIL FORCED WATER FORCED (O.F.W.F.) RANSFORMERS ABOVE 60 MVA EMPLOY A COMBINATION OF FORCED OIL ND FORCED AIR COOLING IL NATURAL AIR FORCED TYPE OF COOLING IS NOT ADEQUATE TO REMOVE HE HEAT CAUSED BY THE LOSSES WHICH IS APPROXIMATELY EQUAL TO % OF THE TRANSFORMER RATING (0.6MW) N CASE OF FORCED OIL AND FORCED AIR COOLING SYSTEM A SEPARATE OOLER IS MOUNTED AWAY FROM THE TRANSFORMER TANK HIS COOLER IS CONNECTED TO THE TRANSFORMER WITH PIPES AT THE OTTOM AND THE TOP HE OIL IS CIRCULATED FROM THE TRANSFORMER TO THE COOLER HROUGH THE PUMP HE COOLER IS PROVIDED WITH THE FANS WHICH BLAST AIR ON THE OOLING TUBES HIS TYPE OF COOLING IS PROVIDED FOR THE HIGHER RATING RANSFORMERS AVAILABLE AT THE SUBSTATIONS AND POWER STATIONS. IS TYPE OF COOLING SYSTEM NEEDS A HEAT EXCHANGER IN HICH THE HEAT OF THE TRANSFORMER OIL IS GIVEN TO THE OOLING WATER E COOLING WATER IS TAKEN AWAY AND COOLED IN SEPARATE OOLERS E OIL IS FORCED THROUGH THE HEAT EXCHANGER E OIL PUMP PUMPS THE OIL FROM TRANSFORMER TO THE HEAT CHANGER THOUGH THE TOP PIPES L FROM THE HEAT EXCHANGER IS PUMPED BACK TO THE RANSFORMER THROUGH THE BOTTOM PIPE IS TYPE OF COOLING IS PROVIDED FOR VERY LARGE RANSFORMERS WHICH HAVE RATINGS OF SOME HUNDREDS OF MVA ENERATING TRANSFORMER WILL HAVE VERY HIGH RATING AND ATING EQUAL TO THE RATING OF THE GENERATOR) IS TYPE OF TRANSFORMERS IS USED IN LARGE SUBSTATIONS AND GENERATOR TRANSFORMER (GT) STATION TRANSFORMER (ST) UNIT AUXILIARY TRANSFORMER (UAT) EXCITATION TRANSFORMER NEUTRAL GROUNDING TRANSFORMER AUXILIARY TRANSFORMERS AUTO TRANSFORMER GENERATOR TRANSFORMER: THE GENERATOR S CONNECTED TO THIS TRANSFORMER BY MEANS OF SOLATED BUS DUCTS. THIS TRANSFORMER IS USED TO STEP UP THE GENERATING VOLTAGE OF AROUND 15KV TO GRID VOLTAGE. THIS TRANSFORMER IS GENERALLY PROVIDED WITH OFAF COOLING. T IS ALSO PROVIDED WITH OFF CIRCUIT/ON LOAD TAPS ON THE HIGH VOLTAGE SIDE. THIS TRANSFORMER HAS ELABORATE COOLING SYSTEM CONSISTING OF NUMBER OF OIL PUMPS AND COOLING FANS APART FROM VARIOUS ACCESSORIES. HE UAT DRAWS ITS INPUT FROM THE MAIN BUSDUCT CONNECTING GENERATOR TO THE GENERATOR RANSFORMER. HE TOTAL KVA CAPACITY OF UNIT AUXILIARY RANSFORMER REQUIRED CAN BE DETERMINED BY ASSUMING 0.85 POWER FACTOR AND 0.9 EFFICIENCY FOR OTAL AUXILIARY MOTOR LOAD. T IS SAFE AND DESIRABLE TO PROVIDE ABOUT 20% EXCESS CAPACITY THAN CIRCULATE SO AS TO PROVIDE FOR MISCELLANEOUS AUXILIARIES AND POSSIBLE INCREASE IN AUXILIARY LOAD. WITH HIGHER UNIT RATINGS AND HIGHER STEAM CONDITIONS, THE AUXILIARY POWER REQUIRED ALSO NCREASES AND LIMITATIONS IMPOSED BY THE WITCHGEAR VOLTAGES AVAILABLE, INDICATE THE MAXIMUM SIZE OF UNIT AUXILIARY TRANSFORMER WHICH THE STATION TRANSFORMER IS REQUIRED TO FEED POWER TO THE AUXILIARIES DURING START UPS. THIS TRANSFORMER IS NORMALLY RATED FOR THE NITIAL AUXILIARY LOAD REQUIREMENTS OF UNIT. N TYPICAL CASES, THIS LOAD IS OF THE ORDER OF 60% OF THE LOAD AT FULL GENERATING CAPACITY. BUT IN LARGE STATIONS WHERE MORE THAN ONE UNITS ARE OPERATING, THE STATION TRANSFORMERS SHOULD HAVE SUFFICIENT CAPACITY TO START TWO UNITS AT A TIME IN ADDITION TO FEEDING THE COMMON AUXILIARIES. T IS ALSO PROVIDED WITH ON LOAD TAP CHANGER TO CATER TO THE FLUCTUATING VOLTAGE OF THE GRID. HESE TRANSFORMERS ARE EMPLOYED IN THE POWER PLANTS FOR ELIVERING POWER TO LOW VOLTAGE LOADS (VOLTAGE BELOW KV). HESE TRANSFORMERS CONNECTS BETWEEN HV DISTRIBUTION USES AND LV DISTRIBUTION BUSES OF THE PLANT. HEIR RATING WILL BE AROUND 1 TO 5MVA, NATURAL OIL OOLING OR AIR COOLED TRANSFORMERS ARE USED. OME OF THE POINTS RELATED RANSFORMERS ARE LISTED BELOW: TO STATION AUXILIARY HESE TRANSFORMERS ARE LOCATED IN POWER PLANT TO STEP OWN VOLTAGE FROM 6.6KV TO 415V. HE RATING FOR THIS TRANSFORMER CORRESPONDS TO THE ATING OF THE AUXILIARY LOAD IT SHOULD BE BEARING. HESE TRANSFORMERS ARE INDOOR TYPE AND USUALLY DRY TYPE RANSFORMERS ARE USED. CUTAWAY VIEW OF OIL MMERSED CONSTRUCTION TRANSFORMER THE CONSERVATOR (RESERVOIR) AT TOP PROVIDES OIL TO ATMOSPHERE ISOLATION AS COOLANT LEVEL AND TEMPERATURE CHANGES. THE WALLS AND FINS PROVIDE REQUIRED HEAT DISSIPATION BALANCE AUTOTRANSFORMER IS AN ELECTRICAL TRANSFORMER WITH ONLY ONE NDING. THE "AUTO“ PREFIX REFERS TO THE SINGLE COIL ACTING ON SELF AND NOT TO ANY KIND OF AUTOMATIC MECHANISM. AN AUTOTRANSFORMER, PORTIONS OF THE SAME WINDING ACT AS BOTH E PRIMARY AND SECONDARY SIDES OF THE TRANSFORMER. THE WINDING S AT LEAST THREE TAPS WHERE ELECTRICAL CONNECTIONS ARE MADE. TOTRANSFORMERS HAVE THE ADVANTAGES OF OFTEN BEING SMALLER, GHTER, AND CHEAPER THAN TYPICAL DUAL-WINDING TRANSFORMERS, BUT TOTRANSFORMERS HAVE THE DISADVANTAGE OF NOT PROVIDING ECTRICAL ISOLATION. SINGLE-PHASE TAPPED AUTOTRANSFORMER WITH OUTPUT VOLTAGE RANGE OF 40% – 115% OF INPUT STEP DOWN VALUES TO SAFE LEVELS FOR MEASUREMENT OTENTIAL TRANSFORMERS ALSO CALLED VOLTAGE TRANSFORMERS STANDARD OUTPUT 120V URRENT TRANSFORMERS STANDARD OUTPUT OF 1 OR 5 AMPS METERING AND RELAYING STANDARDS CAN PRODUCE HIGH VOLTAGES IF OPEN CIRCUITED TANK RADIATOR/ FAN/PUMP BUSHINGS TAP CHANGER CONSERVATOR BREATHER TEMPERATURE INDICATORS BUCHHOLZ RELAY/OIL SURGE RELAY OIL LEVEL GAUGE PRESSURE RELIEF DEVICE (PRD) VALVES ROLLER COOLER CONTROL CUBICLE (MARSHALLING BOX) REMOTE TAP CHANGER CONTROL CUBICLE (RTCC) RADIATORS ARE USED TO INCREASE THE COOLING AREA DUE TO TRANSFORMER OIL GETS HEATED UP, HOT OIL RISES TO TOP & FLOW TO RADIATOR IN RADIATOR WHILE FLOWING DOWN, OIL DISSIPATES HEAT TO COOLING MEDIUM COLD OIL AGAIN ENTERS TRANSFORMER AT BOTTOM OF RADIATOR ITH THE VARIATION OF TEMPERATURE THERE ORRESPONDING VARIATION IN THE OIL VOLUME IS O ACCOUNT FOR THIS, AN EXPANSION VESSEL CALLED ONSERVATOR IS ADDED TO THE TRANSFORMER WITH A ONNECTING PIPE TO THE MAIN TANK SMALLER TRANSFORMERS THIS VESSEL IS OPEN O ATMOSPHERE THROUGH DEHYDRATING BREATHERS O KEEP THE AIR DRY) LARGER TRANSFORMERS, AN AIR BAG IS MOUNTED SIDE THE CONSERVATOR WITH THE INSIDE OF BAG OPEN O ATMOSPHERE THROUGH THE BREATHERS AND THE UTSIDE SURFACE OF THE BAG IN CONTACT WITH THE OIL URFACE. ICA GEL BREATHER OTH TRANSFORMER OIL AND CELLULOSIC PAPER ARE IGHLY HYGROSCOPIC APER BEING MORE HYGROSCOPIC THAN THE MINERAL OIL O THE MOISTURE, IF NOT EXCLUDED FROM THE OIL URFACE IN CONSERVATOR, THIS WILL FIND ITS WAY INALLY INTO THE PAPER INSULATION AND CAUSES EDUCTION INSULATION STRENGTH OF TRANSFORMER. O MINIMISE THIS THE CONSERVATOR IS ALLOWED TO REATHE ONLY THROUGH THE SILICAGEL COLUMN, WHICH BSORBS THE MOISTURE IN AIR BEFORE IT ENTERS THEONSERVATOR AIR SURFACE. OST OF THE TRANSFORMER (SMALL TRANSFORMERS AVE ONLY OTI) ARE PROVIDED WITH INDICATORS HAT DISPLACE OIL TEMPERATURE AND WINDING EMPERATURE HERE ARE THERMOMETERS POCKETS PROVIDED IN THE ANK TOP COVER WHICH HOLD THE SENSING BULLS IN HEM IL TEMPERATURE MEASURED IS THAT OF THE TOP OIL, WHERE AS THE WINDING TEMPERATURE MEASUREMENT IS NDIRECT, THIS IS DONE BY ADDING THE EMPERATURE RISE OR PROPER FUNCTIONING OR OTI & WTI IT IS ESSENTIAL O KEEP THE THERMOMETERS POCKET CLEAN AND FILLED WITH OIL. RANSFORMERS TANK IS A PRESSURE VESSEL AS THE INSIDE RESSURE CAN GROUP STEEPLY WHENEVER THERE IS A AULT IN THE WINDINGS AND THE SURROUNDING OIL IS UDDENLY VAPORIZED ANKS ARE TESTED FOR A PRESSURE WITHSTAND CAPACITY F 0.35 kg/ cm2 TO PREVENT BURSTING OF THE TANK, THESE ANKS ARE IN ADDITION PROVIDED WITH EXPANSION VENTS ITH A THIN DIAPHRAGM MADE OF AKELITE/COPPER/GLASS AT THE END N PRESENT DAY TRANSFORMERS, PRESSURE RELIEF EVICES ARE REPLACING THE EXPANSION VENTS, THESE ARE MILAR TO SAFETY VALVES ON BOILERS (SPRING LOADED). WORKS AS A PRESSURE RELEASING VALVE EQUIPPED WITH ALARM/TRIP CONTACT OPERATING PRESSURE:8 kg/ cm2 WINDING AND TERMINAL FAULTS CORE FAULTS TANK AND TRANSFORMER ACCESSORY FAULTS ON–LOAD TAP CHANGER FAULTS ABNORMAL OPERATING CONDITIONS SUSTAINED OR UNCLEARED EXTERNAL FAULTS THE APPROXIMATE PROPORTION OF FAULTS DUE TO EACH OF THE CAUSES LISTED ABOVE IS SHOWN IN FIGURE FAILURES IN TRANSFORMERS CAN BE CLASSIFIED NTO INDING FAILURES DUE TO SHORT CIRCUITS (TURN-TURN AULTS, PHASE-PHASE FAULTS, PHASE-GROUND, OPEN INDING) ORE FAULTS AMINATIONS) (CORE INSULATION FAILURE, SHORTED RMINAL FAILURES (OPEN LEADS, LOOSE CONNECTIONS, HORT CIRCUITS) N-LOAD TAP CHANGER FAILURES (MECHANICAL, ECTRICAL, SHORT CIRCUIT, OVERHEATING) BNORMAL OPERATING CONDITIONS VERLOADING, OVERVOLTAGE) (OVERFLUXING, SOURCES OF ABNORMAL STRESS IN A TRANSFORMER ARE: OVERLOAD SYSTEM FAULTS OVERVOLTAGE REDUCED SYSTEM FREQUENCY VERLOAD CAUSES INCREASED 'COPPER LOSS' AND A ONSEQUENT TEMPERATURE RISE, OVERLOADS CAN BE ARRIED FOR LIMITED PERIODS YSTEM SHORT CIRCUITS PRODUCE A RELATIVELY INTENSE ATE OF HEATING OF THE FEEDING TRANSFORMERS, THE OPPER LOSS INCREASING IN PROPORTION TO THE SQUARE F THE PER UNIT FAULT CURRENT RANSIENT OVERVOLTAGES ARISE FROM FAULTS, WITCHING, AND LIGHTNING DISTURBANCES AND ARE IABLE TO CAUSE INTERTURN FAULTS EDUCTION OF SYSTEM FREQUENCY HAS AN EFFECT WITH EGARD TO FLUX DENSITY, SIMILAR TO THAT OF VERVOLTAGE. NSUFFICIENT OIL LEVEL EEPAGE OF WATER IN OIL ROLONGED OVER LOADING NGLE PHASE LOADING NBALANCED LOADING AULTY TERMINATION (IMPROPER SIZED LUGS ETC) OWER THEFT ROLONGED SHORT CIRCUIT AULTY OPERATION OF TAP CHANGER SWITCH ACK OF INSTALLATION CHECKS OURLY THE FOLLOWING PARAMETERS ARE TO BE CHECKED EVERY HOUR AND RECORDED, IF THE OBSERVED VALUE EXCEEDS THE VALUE GIVEN BY THE SUPPLIER, IMMEDIATE REMEDIAL ACTION SHOULD BE TAKEN. 1. WINDING TEMPERATURE 2. OIL TEMPERATURE 3. LOAD CURRENT 4. TERMINAL VOLTAGE NORMALLY, MAXIMUM ALLOWED WINDING TEMPERATURE IS 55ºC ABOVE AMBIENT AND OIL TEMPERATURE IS 45ºC ABOVE AMBIENT (ACTUAL ALLOWED VALUE MAY VARY FROM SUPPLIER TO SUPPLIER). AILY . OIL LEVEL IN MAIN CONSERVATOR . OIL LEVEL IN OLTC . OIL LEVEL IN BUSHING 4. LEAKAGE OF WATER INTO COOLER (OFWF) . WATER TEMPERATURE (OFWF) . WATER FLOW (OFWF) . COLOUR OF SILICA GEL UARTERLY CHECKING/ REPLACEMENT RECONDITIONING OF SILICA GEL BREATHER CHECKING OF WATER COOLER FUNCTIONING CHECKING OF COOLING FANS FUNCTIONING GEAR OIL FOR TAP CHANGER MECHANISM CHECKING OF COOLING PUMPS AND MOTOR FUNCTIONING ALF YEARLY INSPECTION OF ALL GASKETS AND JOINTS NNUALLY 1. PROTECTIVE RELAYS, ALARMS, METERS AND CIRCUITS TO BE CHECKED AND CALIBRATED 2. IR (INSULATION RESISTANCE) VALUE AND POLARISATION INDEX 3. TAN DELTA AND CAPACITANCE OF BUSHINGS 4. BDV (BREAK DOWN VOLTAGE) OF TRANSFORMER OIL 5. OIL RESISTIVITY 6. POWER FACTOR OF OIL 7. INTERFACIAL TENSION OF OIL 8. ACIDITY AND SLUDGE OF OIL ANNUALLY 9. FLASH POINT OF OIL 10. WATER CONTENT OF OIL 11. DISSOLVED GAS ANALYSIS 12. REPLACING OF OLTC OIL 13. THERMO VISION SCANNING 14. EARTHING MEASUREMENTS 15. TAN DELTA AND CAPACITANCE OF WINDING NCE IN FIVE YEARS 1. FURAN ANALYSIS (ONCE IN A YEAR AFTER THE FIRST 5 YEARS) . OVERHAULING OF OLTC DIVERTER SWITCH (ONCE IN 5 YEARS OR AFTER COMPLETION OF 50,000 OPERATIONS WHICHEVER IS EARLIER). NCE IN TEN YEARS OVERHAUL, INSPECTION INCLUDING LIFTING OF CORE AND WINDING. URAN ANALYSIS ON TRANSFORMER OIL INDICATES THE EGREE OF DEGRADATION OF THE TRANSFORMER PAPER NSULATION. HIS IS USUALLY DONE IN TRANSFORMERS AGING ABOVE 15 EARS. URAN INDICATES THE COMPOUNDS OF CARBON AND YDROGEN. WHEN THE FURAN COUNT IS ABOVE 2500PPB, IT MEANS THE RANSFORMER IS ABOUT TO FAIL. URAN ANALYSIS IS IMPORTANT IN DECIDING WHEN TO ISCARD A TRANSFORMER UNIT OR RETAIN. THANK YOU! RK JAISWAL NK TUTEJA • +91 9650993009 • [email protected] • +91 9810174125 • [email protected]