EMS-Series
Multi-Function Meters
Product Features
●
●
●
●
●
●
●
●
●
●
●
Microcontroller based multifunction AC Energy Meter.
Accuracy Class1.0 / (Class 0.5 calibration on Request).
CT /PT (Pri/Sec) Programmable.
Digital Measurement.
IEC 62052-11 IEC 62053-21 IEC 62053-22 IEC 62053-23.
RS 485 Serial Port with Modbus RTU Output.
Flush / Panel Mounting .
96 x 96 mm DIN Mounting.
Auto Scroll / Hold Facility.
Internal Resettable fuse for protection of device against voltage fluctuations.
Protection from dust and water as per IP-51.
Specifications
Model
EMS-01
Rated voltage (Aux. Supply)
85 to 270 V AC / DC
Rated Frequency
50 / 60Hz ± 5% for AC only
Power consumption
< 5 VA / 1W
Input voltage
3 Phase 4 wire (R,Y,B,N ) Range - 415 V AC (-40% to +20%) 110 V AC (-40% to +20%)
Input current
Current inputs (AR, AY, AB) 1A to 5A (to 200%)
Burden
< 0.2 VA per Volts / Amps input
Accuracy
Class 1 / Class 0.5
Recovery Time
2 sec minimum.
Communication
RS - 485 MODBUS RTU Protocol
Meter Constant
3200 Pulses / KWh 3200 pulses / KVArh
CT Ratio Selectable
Primary 1 to 5000A max. Secondary 1 to 5A.
PT Ratio Selectable
Primary 110 to 999KV Secondary 110 to 500V
Device ID
1 – 247
Baud rate
2400, 4800, 9600,19200bps
Pulse Output
Active Energy / Reactive Energy
Poles
1 - 28
Protection of configuration settings
User settable Password Ranging from 0001 to 9999
Ambient Temperature
Operation -10°C to + 55°C (14°F to 131°F) Storage -25°C to + 80°C (-13°F to 176°F)
Humidity
Up to 95% RH @ 40°C
Insulation resistance
>100M ohms @ 500V DC
Dielectric strength
2.5 KV AC, 50Hz for 1 minute (Between current carrying & non-current carrying parts)
Input Frequency
50 Hz ± 2%
Electrical connection
Screw type terminals with self lifting clamps.
Dimension
96 X 96 X 117 mm (W X H X D)
Connections
Dimensions
Accessories
Instruction Manual-----1No
Calibration certificate for energy meter-----1No
Side Anchors ----- 2 Nos
Hints On Correct Use
Tools and Fasteners Kindly use star – type screw driver for tightening the screws.
NOTE: Installation should include a disconnecting device, like switch or circuit breaker, with clear ON/OFF markings, to turn-off the auxiliary
supply(control power).The disconnecting device should be within the reach of the equipment and the operator.
Caution
●
●
●
Apply appropriate personal protective equipment(PPE) and follow safety work practices
Only qualified electrical workers should install this equipment. Such work should be performed only after reading this entire set of instructions.
If the equipment is not used in the manner specified by the manufacturer, the protection provided by the equipment may be impaired.
●
●
●
●
●
●
●
●
●
NEVER work alone.
Turn OFF all power supplying the energy meter and the equipment in which it is installed before working on it.
The successful operation of this equipment depends upon proper handling, installation and operation. Neglecting fundamental installation
requirements may lead to personal injury as well as damage to electrical equipment or other property
NEVER bypass external fusing.
NEVER short the secondary of PT
NEVER open circuit a CT; use the shorting block to short circuit the leads of CT before removing the connection from energy meter.
Before performing Dielectric or Megger testing on any equipment in which the energy meter is installed, disconnect all the input and output
wires to the energy meter. High voltage testing may damage electronic components contained in the energy meter.
The energy meter should be installed in a suitable electrical enclosure
EAPL is not responsible for any consequential damages arising out of use of our products, though the technology is cautiously chosen and
implemented like any other well designed good electric meter.